1. A 20 MVA, 3-phase, star-connected, 50-Hz, salient-pole has X = 1 p.u.; X = 0.65 p.u. and R₁ = 0.01 p.u. The generator delivers 15 MW at 0.8 p.f. lagging to an 11-kV, 50-Hz system. What is the load angle and excitation e.m.f. under these conditions? [18°; 1.73 p.u]
1. A 20 MVA, 3-phase, star-connected, 50-Hz, salient-pole has X = 1 p.u.; X = 0.65 p.u. and R₁ = 0.01 p.u. The generator delivers 15 MW at 0.8 p.f. lagging to an 11-kV, 50-Hz system. What is the load angle and excitation e.m.f. under these conditions? [18°; 1.73 p.u]