CEE4210-HW6-F2022-SOLUTION
docx
keyboard_arrow_up
School
Ohio State University *
*We aren’t endorsed by this school
Course
4210
Subject
Mechanical Engineering
Date
Dec 6, 2023
Type
docx
Pages
8
Uploaded by AdmiralTree11989
CEE 4210/6210 Renewable Energy Systems – Fall 2022
Assignment 6
SOLUTION
Q1. Heat pumps (20 points)
A heat pump is to heat a building during a winter heating season from December 1 to March 15 where the heat requirement averages 21 kW for the entire period (i.e., on a 24-hour basis over the entire number of days elapsed). Assume that the building will be heated with an ideal ground-source heat pump that starts with refrigerant 134a in condition of 100% saturated vapor at pressure of P = 0.36 MPa and temperature of T = 5.8°C. The remaining values you need to analyze the heat pump cycle are in the table below. (Hint: You won’t need to use all the values in the table. It is a test of your understanding of the heat pump cycle to see that you can select the values that you do use. The refrigerant is compressed, then passes through a heat exchanger to return to saturated liquid state, then expanded through a throttling device that maintains constant enthalpy, then evaporated in another heat exchanger to return to the beginning of the cycle as a saturated vapor.
Electricity for this residential application costs $0.18/kWh.
Questions: (a) Sketch the values in the table onto a T-s diagram to visualize how the cycle works. It does not need to be to scale, a hand sketch is fine; (b) calculate the coefficient of performance of this heat pump; (c) the flow rate in kg/second of the R-134a refrigerant required to maintain 21 kW of heat output; (d) the cost of electricity to provide the required heat for the heating season, considering only the energy consumption of the compressor and ignoring electricity used for pumping, friction and thermal losses, etc.
Table of values for R-134a:
Point
Temp
Pressure
Enthalpy
Entropy
DegC
MPa
kJ/kg
kJ/kgDegK
1
5.8
0.36
253.81
0.9284
2
57.2
1.4
282.00
0.9284
3
52.4
1.4
276.12
0.9105
4
52.4
1.4
127.22
0.4532
5
5.8
0.36
121.23
0.4532
6
5.8
0.36
127.22
0.4748
1
Solution:
Part a. Sketch will look something like this, but with values labeled:
Part b. COP is based on compressor work and heat output:
Compressor: W
=
282
−
253.81
=
28.19
kJ
/
kg
Heat output: Q
=
282
−
127.22
=
154.78
kJ
/
kg
COP value: COP
=
Q
out
W
=
154.78
28.19
=
5.49
Part c. The heating rate of 21 kW is equivalent to 21 kJ/sec. Therefore, the flow rate is
q
=
21
kJ
/
s
154.78
kJ
/
kg
=
0.136
kg
/
s
Part d. The heating season is the entire months from December through February plus 15 days in March, so the number of days is 31 + 31 + 28 + 15 = 105. This amount is equivalent to 2520 hours. Power required by the compressor: P
=
Q
COP
=
21
5.49
=
3.83
kW
.
Therefore the total electricity consumed and cost are:
E
=
Pt
=
3.83
kW ×
2520
h
=
9639
kWh
Cost
=
9639
kWh×$
0.18
=
$
1735
2
Q2 Effluent Thermal Energy Recovery (ETER) (20 points)
The Ithaca Area Wastewater Treatment Facility, or IAWWTF, is a wastewater treatment plant (WWTP) that typically treats 6.5 million gallons of wastewater per day, or, in metric units, ~24.6 million liters per day. Suppose they decide to build up an Effluent Thermal Energy Recovery (ETER) system that diverts 7.6
million liters/day into a heat exchanger to extract heat for both the thermal needs of the plant and to provide to sales to surrounding customers for both building heating and process heat. The working fluid in the heat pump loop has a specific heat of 0.961 kJ/kg°C. The specific heat value of water is 4.186 kJ/kg°C, and you can assume a mass of water of 1 kg per 1 liter. The effluent flow from the WWTP passes through the heat exchanger on the cold side of the ETER system, entering at 10°C and leaving at 7°C. The working fluid enters the heat exchanger on the hot side at 57°C and exits at 41°C. Based on the
energy input to the compressor and the heat delivered, and ignoring all other energy inputs and losses, the COP of the system is COP = 3.2. The plant pays $0.105/kWh for electricity. A) What is the rate at which the ETER system delivers heat from the heat exchanger on the hot side, in kW? B) What is the rate
at which the refrigerant must flow in kg/s through the heat exchanger on the hot side to deliver the required heat, based on the amount of temperature change? C) Suppose the system runs at this rate continuously for a 24-hour period. What is the cost of the electricity for those 24 hours to operate the compressor? D) Suppose the WWTP could instead purchase natural gas for $11 per GJ and burn it in an 80%-efficient system to provide the same heat as the heat pump. Use a calculation of the 24-hour cost of natural gas to determine which option is cheaper, heat pump or natural gas. Hint: Solving this problem does not
require the use of a temperature-entropy diagram.
Solution:
The solution will actually be provided in the opposite order from which the problem was first posed, first
the heat output, then the refrigerant flow rate, then the cost.
Part a. Heat removed per day is: 7.6E6
kg×
(
10
−
7
)
×
4.186
=
95.4
GJ
/
day
. Therefore, the compressor work is: W
=
Q
COP
−
1
=
95.4
3.2
−
1
=
43.4
GJ
/
day
The heat output is then Q
=
95.4
+
4 3.4
=
138.8
GJ
/
day
It can be confirmed that the COP is correct: COP
=
138.8
43.4
=
3.2
.
There are 86400 seconds per day, so dividing heat output by seconds gives the rate in kW:
P
=
138.8
GJ
86400
s
=
1606
kW
Part b. We can use the temperature change and specific heat to convert power to fluid flow:
q
=
1606
kJ
/
s
0.961
(
57
−
41
)
=
104.5
kg
/
s
Part c. The compressor power requirement is: P
/
COP
=
1606
kW
/
3.2
=
501.8
kW
. Therefore the total electricity consumption per day and cost per day are:
3
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
- Access to all documents
- Unlimited textbook solutions
- 24/7 expert homework help
501.8
kW ×
24
=
12045
kWh
/
day
12045
×$
0.105
=
$
1265
/
day
Part d. 1606
kW
(
24
h
)
=
38544
kWh
=
138.8
GJ
Including losses, 138.8
GJ ÷
0.8
=
173.4
GJ
. Multiplying by fuel cost of $11/GJ gives $1908/day, so the ETER system is cheaper.
Q3 Thermodynamics of a microturbine (20 points)
A microturbine has a cycle that starts with air at ambient pressure and 295 K with a relative pressure of 1.3068, compresses the air by a ratio of 3.5 to 1, then heats it to a temperature of 580 K with a relative pressure of 14.38. The enthalpy values at the compressor entrance and at the highest temperature and pressure in the cycle are 295.2 and 586.0 kJ/kg, respectively. The turbine has an output of 65 kW
e
and the actual efficiency value is 75.8% of the ideal value based on thermodynamic analysis. The energy for the microturbine is provided from biogas generated in an anaerobic biodigester. Over a 24-hour day, the
microturbine operates with a capacity factor of 94.5%. A) What is the ideal efficiency value of the microturbine? B) What is the quantity of biogas required to operate the turbine in one 24-hour day, measured in therms? (1 therm = 10
5
Btu). Tables for interpolating the enthalpy values at the compressor exit and turbine exit are given in the table below, and note that this table is available for both the compression of the gas in the compressor and expansion of the gas in the turbine.
Temp (K)
h (kJ/kg)
P-r
400
400.98
3.806
410
411.12
4.153
420
421.26
4.522
430
431.43
4.915
Solution:
Part a. Based on the 3.5 : 1 ratio, the relative pressure at State 2 is 1.3068
×
3.5
=
4.57
.
Interpolating between the given values gives:
4.57
−
4.522
4.915
−
4.522
=
0.13
h
2
=
421.26
+
0.13
(
431.43
−
421.26
)
=
422.6
kJ
/
kg
Process for calculating h4 is similar. Based on the 3.5 : 1 ratio, the relative pressure at State 2 is 14.38
÷
3.5
=
4.109
.
Interpolating between the given values gives:
4.109
−
3.806
4.153
−
3.806
=
0.87
h
4
=
400.98
+
0.87
(
411.12
−
400.98
)
=
409.8
kJ
/
kg
4
5
We can now create a complete table of enthalpy values for all four states, as follows:
State
h (kJ/kg)
1
295.2
2
422.6
3
586.0
4
409.8
Turbine work, compressor work, and heat added are the following:
w
t
=
586.0
−
409.8
=
176.2
kJ
/
kg
w
c
=
422.6
−
295.2
=
127.4
kJ
/
kg
Q
¿
=
586.0
−
422.6
=
163.4
kJ
/
kg
Finally the thermal efficiency ignoring losses is as follows:
η
th
=
w
t
−
w
c
Q
¿
=
176.2
−
127.4
163.4
=
0.299
=
29.9%
Answer: Ideal efficiency is 29.9%
Part b. To calculate biogas required, first calculate actual efficiency:
0.299
×
0.7 45
=
0.226
=
22.6%
With a 94.5% capacity factor, the output in 24 hours will be: 65
kW ×
0.94.5
×
24
h
=
1474.2
kWh
The input energy required in units of kWh or therms is the following:
14 74.2
0.226
=
6523
kWh
6523
×
3.6
=
23.5
GJ
Answer to Part b: 23.5 GJ.
Q4 Economics of investment in biogas electricity generation at IAWWTF (20 points)
The Ithaca wastewater plant (IAWWTF) pays $0.105/kWh for electricity that it does not generate itself, being a large commercial user that therefore receives a favorable rate. It installs four 65-kW microturbines of the type analyzed in Q3 at the cost of $3100 per kW. The investment must be repaid over 12 years with a discount rate of 7%. Assume that the turbines operate at the same capacity factor as in Q3 for 365 days per year. All operating cost including maintenance and any other costs are incurred
at a rate of $0.02 per kWh produced. How much money could the plant expect to save per year by generating its own electricity with this system instead of purchasing the electricity from the grid?
Solution:
6
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
- Access to all documents
- Unlimited textbook solutions
- 24/7 expert homework help
The cost of the system is 4
×
65
kW ×$
3100
=
$
806
K
Annualizing gives (
$
806
K ,
6%
,
15
y
)
=
$
83
K
The total production based on Q3 is 1.474
MWh
/
d×
365
×
4
=
2152
MWh
/
yr
The total cost per year including operating cost is then:
$
83000
+
2152
MWh
/
yr×$
20
/
MWh
=
$
126
K
To procure the same power from the grid would cost: 2152
×$
0.105
×
1000
=
$
226
K
Savings are therefore $
226
K
−
$
126
K
=
$
100
K
/
year
.
Answer: ~$100,000 saved per year.
Q5. Energy from municipal solid waste (MSW) (20 points)
Consider a hypothetical WTE plant to be built in the greater Buffalo, NY, metro area. This area has a population of about 1.2 million people, according to the U.S. census.
Suppose the plant has a nameplate capacity of 65 MW
electric
, and over the period of a year, 100% output is
not possible, so assume an 88% capacity factor to account for downtime, etc. The thermal efficiency of the plant is based on the enthalpy values in the table below, where water is compressed from states (1) to (2), heated and converted to saturated vapor at (3), and then expanded in a turbine to (4). (Hint: pressure values are provided for reference only; you do not need to use them in this problem.) You can assume the plant achieves the thermal efficiency derived from the values in the table, i.e., the process is isentropic and you can ignore losses. The generator efficiency of the plant is 98% and the efficiency of the boiler that conducts the waste is 70%, lower than typical values for a coal-fired plant due to challenges with combusting waste. Municipal solid waste (MSW) can be treated as having an average energy content of 12.6 GJ/tonne (1 metric tonne = 1,000 kg), and the average person in the U.S. generates ~2 kg of MSW per day, including both what they throw out directly and waste directed into the
waste stream on their behalf (e.g., from supermarkets, etc.). Suppose the plant is able to obtain as much MSW as it needs from the population of the Buffalo region to meet all its combustion needs. What percent of the Buffalo region’s MSW is consumed by the plant?
Table of values:
State:
Enthalpy (kj/kg)
Pressure (kPa)
1. Condensed water
340.54
50
2. Compressed water
346.67
6000
3. Saturated vapor
2784.60
6000
4. Expanded water-vapor mix
2041.62
50
7
Solution:
The total electricity produced is 65
MW ×
0.88
×
8760
=
501.1
GWh
. When converted to Joules, this amount is equivalent to ~1.80 PJ or Petajoules.
Based on the table of values, the pump work is 346.67 – 340.54 = 6.13 kJ/kg, the boiler input is 2784.6 – 346.67 = 2437.9 kJ/kg, and the turbine output is 2784.6 – 2041.62 = ~743.0. Therefore the turbine efficiency is:
η
=
wt
−℘
q
=
743.0
−
6.13
2437.0
=
30.2%
The overall efficiency is then 0.7 x 0.302 x 0.98 = ~20.7%. Therefore, the energy input from MSW into the plant per year is
Q
=
1.80
PJ
0.207
=
8.71
PJ
/
yr
Converting to tons of MSW per year gives (8.71 PJ)/(12.6 GJ/tonne) = ~6.916 x 10
5
tonnes/year. The average resident generates 2 kg per day, equivalent to 0.730 tonnes/year. Therefore, the population generates in one year (
0.73
tonne
) (
1.2
M
)
=
876,000
tonne
and the fraction used is:
691600
876000
=
79%
8
Related Documents
Related Questions
You must submit the answer within 20 Minutes, Please make sure the answer is correct before submission.
arrow_forward
0
Required information
NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part.
A Carnot heat pump is to be used to heat a house and maintain it at 25°C in winter. On a day when the average
outdoor temperature remains at about 2°C, the house is estimated to lose heat at a rate of 55,000 kJ/h. The heat
pump consumes 4.8 kW of power while operating.
55,000 kJ/h
Determine the total heating costs, assuming an average price of $0.11/kWh for electricity.
The total heating cost is $40.33
(You must provide an answer before moving to the next part.)
arrow_forward
The Ocean Thermal Energy Conversion (OTEC)
system in Hawaii utilizes the surface water and
deep water as thermal energy reservoirs. Assume
the ocean temperature at the surface to be 20 "C
and at some depth to be 6 "C
Determine the maximum possible thermal efficiency achievable by a heat engine.
Express the thermal efficiency as a percentage to three significant figures.
Thh = 478 %
Previous Answers
Correct
Part B
What-if Scenario What would the maximum efficiency be if the surface water temperatun
increased to 25 C?
|
Express the thermal efficiency as a percentage to three significant figures.
arrow_forward
2) A heat pump with the amount of heat of liquid refrigerant (mix) when it will enter the expansion of 480 Btu/lb. while the amount of heat from the refrigerant vapor after leaving the evaporator is 412 Btu/lb. What is the coefficient of performance (COP) if the heat amount of the superheated refrigerant after being compressed by the compressor has a value of 572 Btu/lb?
arrow_forward
Problem Statement
A heat engine receives heat at a rate of 15 kW from a reservoir at 400 K. It delivers all of the
shaft power it produces to a heat pump that delivers 25 kW of heat transfer to a reservoir
at 350 K. The heat pump draws heat from a reservoir at 320 K. What is the temperature of
the warmest region that the heat engine can reject heat to?
Answer Table
Stage
Description
1
Max COP for heat pump
2
Shaft power (kW)
3
Max thermal efficiency of heat engine
4
Warmest region temperature (K)
Your Answer
Correct
Answer
*
Due Date
Grade
(%)
Part
Weight Attempt Action/Message Type
Nov 7, 2024 11:59 pm
0.0
1
1/5
Submit Stage 1
Nov 7, 2024 11:59 pm
Nov 7, 2024 11:59 pm
0.0
1
1/5
0.0
1
1/5
Nov 7, 2024 11:59 pm
0.0
1
1/5
arrow_forward
Submit correct and complete solutions.
give propriate Explanation.
Provide step-by-step detailed explanations.
arrow_forward
!
Required information
NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part.
A Carnot heat pump is to be used to heat a house and maintain it at 25°C in winter. On a day when the average outdoor
temperature remains at about 2°C, the house is estimated to lose heat at a rate of 55,000 kJ/h. The heat pump consumes
5.15 kW of power while operating.
HP
25°C
2°C
55,000 kJ/h
How long did the heat pump run on that day?
arrow_forward
Questions:
1.
b.
As the power plant engineer, you are asked by the power plant manager to design a new steam-based power
plant with a net power output target of 200 MW with a thermal efficiency of 40%. Thermodynamics calculation
should be conducted for the known condition illustrated in Figure 1.
Boiler
P₁ =
8.0 MPa
Saturated
vapor
Condenser
Pump
Turbine
of Vapor and Gas]
Cooling
water
8.0 MPa
0.008 MPa
tw.
Saturated
liquid at 0.008 MPa
Figure 1. Illustration of steam turbine system and its T-S diagram
a. Calculate the back work ratio, the system's mass flow rate, and the cooling water's mass flow rate.
What kind of efforts should be conducted if the plant manager asks you to increase the system's efficiency
to 50% ? Explain and provide proof in the form of calculation!
VIOL
arrow_forward
A heat pump is used to heat a house. When the outside air temperature is 266K and the inside is maintained at 293K, the heat loss from the
house is 195 kW.
a. What is the minimum electric power (kW) required to operate the heat pump?
b. What is the rate of heat transfer to the heat pump?
C. What is the COP for an ideal heat pump operating between these temperatures?
arrow_forward
Please answer fast i give you upvote.
arrow_forward
Pls. Answer thank you!
A logging firm in Isabella operates a Diesel Electric Plant to supply its electric energy requirements. During a 2 hour period, the plant consumed 250 gallons of fuel at 80°F and produced 2900 kW-hrs. Industrial fuel is used at 30°API and was purchased at P30/li at 60°F. Determine the overall thermal efficiency in percent of the plant.
arrow_forward
Required information
Problem 07.025 - DEPENDENT MULTI-PART PROBLEM - ASSIGN ALL PARTS
NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part.
Refrigerant-134a enters the coils of the evaporator of a refrigeration system as a saturated liquid-vapor mixture at a
pressure of 140 kPa. The refrigerant absorbs 200 kJ of heat from the cooled space, which is maintained at -10°C, and
leaves as saturated vapor at the same pressure.
Problem 07.025.c - Total entropy change of the process
Determine the total entropy change for this process.
The total entropy change for this process is
kJ/K.
arrow_forward
Refrigerationa.) Explain why you can’t cool down your kitchen by leaving your refrigerator or freezer door open with your refrigerator plugged in for an extended period of time.b.) The condenser of a home refrigerator is commonly underneath the appliance, thus the condensing refrigerant exchanges heat with household air, which averages 70oF. It is proposed toreconfigure a refrigerator so that the condenser is in the garage, where the average yearly temperature is about 50oF. Assume a freezer temperature of 0oF, a minimum temperature difference of 10K for heat transfer, and an actual coefficient of performance of 60% that of a Carnot cycle. Calculate the Coefficient of Performance for both configurations and discuss the pros and cons of this proposal.c.) Which is the most effective way to increase the coefficient of performance of a Carnot refrigerator: to increase TC with TH held constant or to decrease TH with TC held constant? Justify mathematically. For a real refrigerator, do…
arrow_forward
12
arrow_forward
Please answer a,b, and c
arrow_forward
SEE MORE QUESTIONS
Recommended textbooks for you

Principles of Heat Transfer (Activate Learning wi...
Mechanical Engineering
ISBN:9781305387102
Author:Kreith, Frank; Manglik, Raj M.
Publisher:Cengage Learning
Related Questions
- You must submit the answer within 20 Minutes, Please make sure the answer is correct before submission.arrow_forward0 Required information NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part. A Carnot heat pump is to be used to heat a house and maintain it at 25°C in winter. On a day when the average outdoor temperature remains at about 2°C, the house is estimated to lose heat at a rate of 55,000 kJ/h. The heat pump consumes 4.8 kW of power while operating. 55,000 kJ/h Determine the total heating costs, assuming an average price of $0.11/kWh for electricity. The total heating cost is $40.33 (You must provide an answer before moving to the next part.)arrow_forwardThe Ocean Thermal Energy Conversion (OTEC) system in Hawaii utilizes the surface water and deep water as thermal energy reservoirs. Assume the ocean temperature at the surface to be 20 "C and at some depth to be 6 "C Determine the maximum possible thermal efficiency achievable by a heat engine. Express the thermal efficiency as a percentage to three significant figures. Thh = 478 % Previous Answers Correct Part B What-if Scenario What would the maximum efficiency be if the surface water temperatun increased to 25 C? | Express the thermal efficiency as a percentage to three significant figures.arrow_forward
- 2) A heat pump with the amount of heat of liquid refrigerant (mix) when it will enter the expansion of 480 Btu/lb. while the amount of heat from the refrigerant vapor after leaving the evaporator is 412 Btu/lb. What is the coefficient of performance (COP) if the heat amount of the superheated refrigerant after being compressed by the compressor has a value of 572 Btu/lb?arrow_forwardProblem Statement A heat engine receives heat at a rate of 15 kW from a reservoir at 400 K. It delivers all of the shaft power it produces to a heat pump that delivers 25 kW of heat transfer to a reservoir at 350 K. The heat pump draws heat from a reservoir at 320 K. What is the temperature of the warmest region that the heat engine can reject heat to? Answer Table Stage Description 1 Max COP for heat pump 2 Shaft power (kW) 3 Max thermal efficiency of heat engine 4 Warmest region temperature (K) Your Answer Correct Answer * Due Date Grade (%) Part Weight Attempt Action/Message Type Nov 7, 2024 11:59 pm 0.0 1 1/5 Submit Stage 1 Nov 7, 2024 11:59 pm Nov 7, 2024 11:59 pm 0.0 1 1/5 0.0 1 1/5 Nov 7, 2024 11:59 pm 0.0 1 1/5arrow_forwardSubmit correct and complete solutions. give propriate Explanation. Provide step-by-step detailed explanations.arrow_forward
- ! Required information NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part. A Carnot heat pump is to be used to heat a house and maintain it at 25°C in winter. On a day when the average outdoor temperature remains at about 2°C, the house is estimated to lose heat at a rate of 55,000 kJ/h. The heat pump consumes 5.15 kW of power while operating. HP 25°C 2°C 55,000 kJ/h How long did the heat pump run on that day?arrow_forwardQuestions: 1. b. As the power plant engineer, you are asked by the power plant manager to design a new steam-based power plant with a net power output target of 200 MW with a thermal efficiency of 40%. Thermodynamics calculation should be conducted for the known condition illustrated in Figure 1. Boiler P₁ = 8.0 MPa Saturated vapor Condenser Pump Turbine of Vapor and Gas] Cooling water 8.0 MPa 0.008 MPa tw. Saturated liquid at 0.008 MPa Figure 1. Illustration of steam turbine system and its T-S diagram a. Calculate the back work ratio, the system's mass flow rate, and the cooling water's mass flow rate. What kind of efforts should be conducted if the plant manager asks you to increase the system's efficiency to 50% ? Explain and provide proof in the form of calculation! VIOLarrow_forwardA heat pump is used to heat a house. When the outside air temperature is 266K and the inside is maintained at 293K, the heat loss from the house is 195 kW. a. What is the minimum electric power (kW) required to operate the heat pump? b. What is the rate of heat transfer to the heat pump? C. What is the COP for an ideal heat pump operating between these temperatures?arrow_forward
- Please answer fast i give you upvote.arrow_forwardPls. Answer thank you! A logging firm in Isabella operates a Diesel Electric Plant to supply its electric energy requirements. During a 2 hour period, the plant consumed 250 gallons of fuel at 80°F and produced 2900 kW-hrs. Industrial fuel is used at 30°API and was purchased at P30/li at 60°F. Determine the overall thermal efficiency in percent of the plant.arrow_forwardRequired information Problem 07.025 - DEPENDENT MULTI-PART PROBLEM - ASSIGN ALL PARTS NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part. Refrigerant-134a enters the coils of the evaporator of a refrigeration system as a saturated liquid-vapor mixture at a pressure of 140 kPa. The refrigerant absorbs 200 kJ of heat from the cooled space, which is maintained at -10°C, and leaves as saturated vapor at the same pressure. Problem 07.025.c - Total entropy change of the process Determine the total entropy change for this process. The total entropy change for this process is kJ/K.arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Principles of Heat Transfer (Activate Learning wi...Mechanical EngineeringISBN:9781305387102Author:Kreith, Frank; Manglik, Raj M.Publisher:Cengage Learning

Principles of Heat Transfer (Activate Learning wi...
Mechanical Engineering
ISBN:9781305387102
Author:Kreith, Frank; Manglik, Raj M.
Publisher:Cengage Learning