In the spaces provided, fill in the cover (depth) for the following residential underground installations. See NEC Table 300.5.
- a. Type UF. No other protection. ______________________ in.
- b. Type UF below driveway. ______________________ in.
- c. Rigid metal conduit under lawn. ______________________ in.
- d. Rigid metal conduit under driveway. ______________________ in.
- e. Electrical metallic tubing between house and detached garage. ______________________ in.
- f. UF cable under lawn. Circuit is 120 volts, 20 amperes, GFCI protected. ______________________ in.
- g. Rigid PVC conduit approved for direct burial. No other protection. ______________________ in.
- h. Rigid PVC conduit. Circuit is 120 volts, 20 amperes, GFCI protected. ______________________ in.
- i. Rigid conduit passing over solid rock and covered by 2 in. (50 mm) of concrete extending down to rock. ______________________ in.
a.
Find the cover (depth) for Type UF with no other protection.
Answer to Problem 13R
The cover (depth) for Type UF with no other protection is
Explanation of Solution
Discussion:
The National Electrical Code committee develops NEC – the standard electrical Code and the main objective for the origin of the Code is to protect and safeguard people and elements from electrical hazards. The codes for explaining underground installations are defined in an article NEC 300.5.
According to the table NEC Table 300.5, the depth for the circuits used for control of the irrigation and landscape lighting with Type UF for non-protected areas like streets, driveways, highways, parking lots, and roads is
Conclusion:
Thus, the cover (depth) for Type UF with no other protection is
b.
Find the cover (depth) for Type UF below driveway.
Answer to Problem 13R
The cover (depth) for Type UF below driveway is
Explanation of Solution
Discussion:
According to the table NEC Table 300.5, the depth for the circuits used for control of the irrigation and landscape lighting with Type UF for outdoor parking areas, areas used for dwelling purposes and dwelling driveways for one and two families is
Conclusion:
Thus, the cover (depth) for Type UF below driveway is
c.
Find the cover (depth) for the rigid metal conduit under lawn.
Answer to Problem 13R
The cover (depth) for the rigid metal conduit under lawn is
Explanation of Solution
Discussion:
According to the table NEC Table 300.5, the depth for the rigid or intermediate metal conduit under lawn areas is
Conclusion:
Thus, the cover (depth) for the rigid metal conduit under lawn is
d.
Find the cover (depth) for the rigid metal conduit under driveway.
Answer to Problem 13R
The cover (depth) for the rigid metal conduit under driveway is
Explanation of Solution
Discussion:
According to the table NEC Table 300.5, the depth for the rigid or intermediate metal conduit for parking areas in outdoor section, areas for dwelling purposes and dwelling driveways for one and two families is
Conclusion:
Thus, the cover (depth) for the rigid metal conduit under driveway is
e.
Find the cover (depth) for electrical metallic tubing between house and detached garage.
Answer to Problem 13R
Electric metallic tubing is not permitted for underground installations.
Explanation of Solution
Discussion:
Electrical metallic tubing is an unthreaded thin-wall raceway of the circular cross section which is designed for physical protection purposes and routing purposes for the cables and conductors. When utilizing appropriate fittings are installed, this tubing is used as an equipment grounding conductor.
Electrical metallic tubing cannot be used for residential underground installations.
Conclusion:
Thus, the electric metallic tubing is not permitted for underground installations.
f.
Find the cover (depth) for the UF cable under lawn, circuit with
Answer to Problem 13R
The cover (depth) for the UF cable under lawn, circuit with
Explanation of Solution
Discussion:
According to the table NEC Table 300.5, the depth for the residential branch circuits rated with
Conclusion:
Thus, the cover (depth) for the UF cable under lawn, circuit with
g.
Find the cover (depth) for the rigid PVC conduit approved for direct burial with no other protection.
Answer to Problem 13R
The cover (depth) for the rigid PVC conduit approved for direct burial with no other protection is
Explanation of Solution
Discussion:
The rigid PVC is a non-metal. According to the table NEC Table 300.5, the depth for the nonmetallic raceways that are listed for non-burial without the concrete encasement with no other protection is
Conclusion:
Thus, the cover (depth) for the rigid PVC conduit approved for direct burial with no other protection is
h.
Find the cover (depth) for the rigid PVC conduit circuit with
Answer to Problem 13R
The cover (depth) for the rigid PVC conduit circuit with
Explanation of Solution
Discussion:
According to the table NEC Table 300.5, the depth for the residential branch circuits rated with
Conclusion:
Thus, the cover (depth) for the rigid PVC conduit circuit with
i.
Find the cover (depth) for the rigid conduit passing over the solid rock.
Answer to Problem 13R
The cover (depth) for the rigid conduit passing over the solid rock is
Explanation of Solution
Discussion:
According to an article NEC 300.5, Note 5 to Table 300.5, the wiring should be installed in metal raceway or the nonmetallic raceway that are permitted for direct burial where the solid rock prevents the compliances with the cover values. The cover of the raceway should be covered by minimum of
Conclusion:
Thus, the cover (depth) for the rigid conduit passing over the solid rock is
Want to see more full solutions like this?
Chapter 16 Solutions
Electrical Wiring: Residental - With Plans (Paperback) Package
Additional Engineering Textbook Solutions
BASIC BIOMECHANICS
Starting Out With Visual Basic (8th Edition)
Degarmo's Materials And Processes In Manufacturing
Mechanics of Materials (10th Edition)
Fluid Mechanics: Fundamentals and Applications
Starting Out with Programming Logic and Design (5th Edition) (What's New in Computer Science)
- 1. A 30-ampere, 120-volt, UF cable circuit is buried from a dwelling unit to a detached outbuilding. The minimum depth of this cable is inches. A. 6 inches C. 24 inches Ans. B. D. 12 inches 18 inchesarrow_forward1.a. Which of the following is suitable as an equipment grounding conductor so long as it does so under morerestrictive conditions?A. Electrical metallic tubingB. Flexible metal conduitC. Rigid metal conduitD. Armored cable1.b. When rigid or intermediate metal conduit is installed in a hazardous location, it must be engaged by_______ threads into each connection.A. 4B. 3C. 2D. 5arrow_forward8. You're installing type AC cable. The armor coating of type AC cable is allowed for use as an equipmentgrounding conductor (EGC) because of itsA. liquid-tight fittings listed for EGC purposes.B. interlocking ribs that form a complete circuit.C. internal bare bonding strip.D. internal bare aluminum bonding conductor.arrow_forward
- 8.a. A _______ conductor does not carry current during normal operation.A. neutralB. groundingC. phaseD. grounded8.b. "The complete path of an electric current" describes an electric(al)A. fault.B. circuit.C. source.D. component.arrow_forwardEquipment Grounding 10. Which of the following statements about ground faults is true?A. They usually occur between any grounded circuit conductor and the equipment grounding conductor. B. They're often normal and typically intentional.C. They can't result from human error.D. They can happen if a conductive tool is dropped in an energized equipment's electrical enclosure.arrow_forward14. How many separate equipment grounding paths are required for branch circuits serving patient care spaces? A. One B. Two C. Four D. Threearrow_forward
- L1. Boxes are classified by type, construction, andA. installation location.B. luminaire support capability.C. number of knockouts.D. power rating L2. Which of the following devices must be placed at each end of an armored cable to prevent damage tothe conductors?A. An insulating sliderB. An insertion couplingC. An antishort bushingD. A metal loop fitting L3. Which of the following is the maximum cross-sectional conductor fill area for underfloor raceways?A. 50%B. 60%C. 40%D. 30%arrow_forwardWhen installing raceways underground in rigid nonmetallic conduit and other approved raceways, there must be a minimum of ___ of cover. a. 6in b. 12in. c. 18in. d. 22in.arrow_forward19. What size copper bonding jumper must be used in an AC electrical system that has 500 kcmil copper phase conductors? A. 4/0 B. 1/0 C. 2/0 D. 3/0 20. A neutral disconnect link is usually in the form of a _______ in larger service equipment. A. screwB. wireC. clamp D. busbararrow_forward
- 11. Specific rules apply for the installation of _______, but no identification requirements for them exists.A. grounding electrode conductorsB. grounding electrodes.C. main bonding jumpers.D. equipment grounding conductors.arrow_forwardEquipment Grounding 13. A metal elbow is a part of a nonmetallic, underground raceway. The elbow won't need to be grounded as long as it's encased in at least _______ inches of concrete. A. 4 B. 5 C. 2 D. 6 13 A. Which of the following can be in the form of a wire and is required to be installed with feeders and branch circuits? A. Phased neutral conductorB. Equipment grounding conductor C. Grounded neutral conductorD. Grounding electrode conductorarrow_forward10. Main bonding jumpers are required to be made of _______ or other corrosion-resistant material.A. copperB. aluminumC. copper-clad aluminumarrow_forward
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT