The winter air conditioning system has a preheat coil, an air washer, and a reheat coil as processing units. It supplies air at 38°C db-temperature to a space maintained at 21°C db-temperature and 13°C wb-temperature. The sensible and latent heat loads on the space are 50 kW and 25 kW, respectively. Of the return air from the space, 40% by dry air mass is discharged to the ambient and replaced with fresh outdoor air at 2°C db-temperature and 95% relative humidity. In the preheater, the air is heated to a db-temperature of 21°C. Assume that the water added in the air washer is at the wb-temperature of the air entering it. The pressure is constant at 95 kPa. Determine: The mass flow rate of supply air in kg/s. The rate of heat input in the preheat coil in kW. The mass flow rate of water sprayed in the air washer in kg/s.
The winter air conditioning system has a preheat coil, an air washer, and a reheat coil as processing units. It supplies air at 38°C db-temperature to a space maintained at 21°C db-temperature and 13°C wb-temperature. The sensible and latent heat loads on the space are 50 kW and 25 kW, respectively. Of the return air from the space, 40% by dry air mass is discharged to the ambient and replaced with fresh outdoor air at 2°C db-temperature and 95% relative humidity. In the preheater, the air is heated to a db-temperature of 21°C. Assume that the water added in the air washer is at the wb-temperature of the air entering it. The pressure is constant at 95 kPa. Determine:
The mass flow rate of supply air in kg/s.
The rate of heat input in the preheat coil in kW.
The mass flow rate of water sprayed in the air washer in kg/s.
Step by step
Solved in 2 steps with 2 images