The distribution network shown in Figure below is to supply two factories A & B with load curves indicated in Fig. Assume that both factories have lagging power factor of 0.8. a) Select the required sizes of transformers for substation supplying both factories such that in the case of a failure in one transformer the overload on the remaining ones should not exceed 12% . b)Calculate the annual energy losses in the transformers. Assuming that transformers are in operation continuously c) Select the reauired sizes of fuses to be installed at both sides of

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
The distribution network shown in Figure below is to supply two factories
A & B with load curves indicated in Fig. Assume that both factories have
a lagging power factor of 0.8.
a) Select the required sizes of transformers for substation supplying
both factories such that in the case of a failure in one transformer
the overload on the remaining ones should not exceed 12%.
b)Calculate the annual energy losses in the transformers. Assuming
that transformers are in operation continuously
c) Select the required sizes of fuses to be installed at both sides of
transformers.
d)Select the required size of the 11 kV, XLPE cable for section S1, if
the cable is to be laid direct in ground with a maximum ground
temperature of 30° C.
e) Calculate the maximum expected voltage drop in section S1.
1
400V
11KV, XLPE Cable
Multi-Core Copper
S
A
4 Km
B
S (KVA)
S (KVA)
400
400
300
300
200
200
100
100
Time (hr)
24
Time (hr)
24
12
18
12
18
Load curve of Factory (A)
Load curve of Factory (B)
Transcribed Image Text:The distribution network shown in Figure below is to supply two factories A & B with load curves indicated in Fig. Assume that both factories have a lagging power factor of 0.8. a) Select the required sizes of transformers for substation supplying both factories such that in the case of a failure in one transformer the overload on the remaining ones should not exceed 12%. b)Calculate the annual energy losses in the transformers. Assuming that transformers are in operation continuously c) Select the required sizes of fuses to be installed at both sides of transformers. d)Select the required size of the 11 kV, XLPE cable for section S1, if the cable is to be laid direct in ground with a maximum ground temperature of 30° C. e) Calculate the maximum expected voltage drop in section S1. 1 400V 11KV, XLPE Cable Multi-Core Copper S A 4 Km B S (KVA) S (KVA) 400 400 300 300 200 200 100 100 Time (hr) 24 Time (hr) 24 12 18 12 18 Load curve of Factory (A) Load curve of Factory (B)
Expert Solution
steps

Step by step

Solved in 4 steps

Blurred answer
Knowledge Booster
Compensation Techniques in Transmission Line
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,