No-load operation and short circuit tests were performed on three-phase, 50 Hz 480/220 delta / Y connected transformer. In these tests The line voltage, line current and three-phase total power have been measured from the high voltage windings and the test results are below. pictures. 100 A DC current when 1.08 V DC voltage from non-transferable software is applied to the low voltage windings has attracted. Find the single phase equivalent circuit parameters of this transformer. idle test: Voltage: 480V Power:114w current: 0.71A short circiut test: V: 10v P: 78w c: 18.3a
Three-Phase Transformers
Three-segment transformers are a type of transformer used to transform voltages of electrical systems into three ranges. Two type transformers are shell-type transformer and core type transformer. In brief, it could be described because of the exquisite kinds of configurations.
Transformer
Ever since electricity has been created, people have started using it in its entirety. We see many types of Transformers in the neighborhoods. Some are smaller in size and some are very large. They are used according to their requirements. Many of us have seen the electrical transformer but they do not know what work they are engaged in.
No-load operation and short circuit tests were performed on three-phase, 50 Hz 480/220 delta / Y connected transformer. In these tests
The line voltage, line current and three-phase total power have been measured from the high voltage windings and the test results are below.
pictures. 100 A DC current when 1.08 V DC voltage from non-transferable software is applied to the low voltage windings
has attracted.
Find the single phase equivalent circuit parameters of this transformer.
idle test:
Voltage: 480V Power:114w current: 0.71A
short circiut test:
V: 10v P: 78w c: 18.3a
Step by step
Solved in 2 steps with 1 images