In the following power system all bus voltages are 6.9 kV 2 R12 1974/197 (0.07 + j1)Ω 1₁ = 120A R23 (0.5+ j6)Ω 1₁ = 120A Distance relay R₁2 provides primary protection to line 1-2 while distance relay R23 provides primary protection to line 2-3. Both are of mho type. Maximum loads at buses 2 and 3 are shown. Available CT ratios are N:5 with N value 50, 75, 100, 150, 200, 250, 300, 400, 500, 600, 800, 1000, 1200, 1500, 1600, 2000, 2400, 2500 For both relays the voltage transformer ratio is 6900:120. (a) What turns ratios should be used for R₁2 and R₂3? Assume that the secondary current should not exceed 5.2 A under maximum load. (b) What is the Zone 1 setting of relay R₂3? (c) What is the Zone 3 setting of relay R₁2?

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
icon
Concept explainers
Question
In the following power system all bus voltages are 6.9 kV
2
(0.07 + j1)Ω
R12
I₁ = 120A
I₁=120A
Distance relay R₁2 provides primary protection to line 1-2 while distance relay R23 provides
primary protection to line 2-3. Both are of mho type. Maximum loads at buses 2 and 3 are
shown. Available CT ratios are N:5 with N value
50, 75, 100, 150, 200, 250, 300, 400, 500, 600, 800, 1000, 1200, 1500, 1600, 2000, 2400, 2500
For both relays the voltage transformer ratio is 6900:120.
(a) What turns ratios should be used for R₁2 and R₂3? Assume that the secondary current should
not exceed 5.2 A under maximum load.
(b) What is the Zone 1 setting of relay R₂3?
(c) What is the Zone 3 setting of relay R₁2 ?
R23
(0.5+ j6)Ω
3
Transcribed Image Text:In the following power system all bus voltages are 6.9 kV 2 (0.07 + j1)Ω R12 I₁ = 120A I₁=120A Distance relay R₁2 provides primary protection to line 1-2 while distance relay R23 provides primary protection to line 2-3. Both are of mho type. Maximum loads at buses 2 and 3 are shown. Available CT ratios are N:5 with N value 50, 75, 100, 150, 200, 250, 300, 400, 500, 600, 800, 1000, 1200, 1500, 1600, 2000, 2400, 2500 For both relays the voltage transformer ratio is 6900:120. (a) What turns ratios should be used for R₁2 and R₂3? Assume that the secondary current should not exceed 5.2 A under maximum load. (b) What is the Zone 1 setting of relay R₂3? (c) What is the Zone 3 setting of relay R₁2 ? R23 (0.5+ j6)Ω 3
Relay setting guideline summary from Horowitz and Phadke
Instantaneous overcurrent relay
(1.35) I, x≤1 pu≤(0.9) 1
nogo,max
If I>I the relay trips "instantly."
pu
Inverse, time-delay overcurrent relay
21 <I < I
load,max
pu
fault,min
pu
If I>I the relay trips after a delay given by corresponding TDS operating curve with "x" coordinate
I/Ipu. Set TDS as low as possible while allowing for relay coordination time of 0.3-0.5 seconds.
Nonpilot distance relay. Relays types: impedance, directional impedance, mho
Zone 1: Z=(0.9) Zline and min TDS. Do not overlap Zone 1 of another relay.
Zone 2: Z=(1.2) Zline and TDS to coordinate with Zone 1. Overlap Zone 1 of subsequent
relays, but do not overlap their Zone 2.
Zone 3: Z=Zline+(1.2) Z next TDS to coordinate with Zone 2.
Pilot relay, directional comparison blocking (mho type)
M trip (1.75)Z line
M 1 block=(1.25) (M trip-Z line)
go,min
Transcribed Image Text:Relay setting guideline summary from Horowitz and Phadke Instantaneous overcurrent relay (1.35) I, x≤1 pu≤(0.9) 1 nogo,max If I>I the relay trips "instantly." pu Inverse, time-delay overcurrent relay 21 <I < I load,max pu fault,min pu If I>I the relay trips after a delay given by corresponding TDS operating curve with "x" coordinate I/Ipu. Set TDS as low as possible while allowing for relay coordination time of 0.3-0.5 seconds. Nonpilot distance relay. Relays types: impedance, directional impedance, mho Zone 1: Z=(0.9) Zline and min TDS. Do not overlap Zone 1 of another relay. Zone 2: Z=(1.2) Zline and TDS to coordinate with Zone 1. Overlap Zone 1 of subsequent relays, but do not overlap their Zone 2. Zone 3: Z=Zline+(1.2) Z next TDS to coordinate with Zone 2. Pilot relay, directional comparison blocking (mho type) M trip (1.75)Z line M 1 block=(1.25) (M trip-Z line) go,min
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 5 steps with 23 images

Blurred answer
Knowledge Booster
Fault analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,