Figure Q2 shows a single line diagram of a power system and the associated data of this system are given in Table Q2. The pre-fault load current and A-Y transformer phase shift are neglected. (a) (b) If a Single Line-to-Ground (S-L-G) fault occurs at Bus 5 and the pre-fault voltage is 1.0 pu, calculate the subtransient fault current in Ampere. (c) (d) Using base of 100 MVA and 11 kV at generator G₁, construct the positive sequence, negative sequence and zero sequence networks with their corresponding component values indicated. (e) Recalculate (b) if the neutral on HV side of T3 is solidly grounded. Repeat part (b) with Line-to-line (L-L) fault. What will happen to L-L fault current in (d) if the neutral on the HV side of T3 is solidly grounded?

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
icon
Concept explainers
Question
Device
Generator G₁
Generator G₂
Generator G3
Transformer Ti
Transformer T2
Transformer T3
Line 1
Line 2
Capacity Voltage
(MVA)
(kV)
100
11
50
11
50
11
70
132/11
70
132/11
70
132/11
Table Q2
X' X₁ X₂
(pu)
X"
(pu) (pu)
0.15
0.4
0.12
0.35
0.12
0.35
0.07
0.07
0.07
Xo
(pu) (pu)
0.12
0.06
0.1
0.05
0.1
0.05
0.07
0.07
0.07
0.07
0.07
0.07
35 52
35 92
35 92
35 92
70 92
70 92
Xn
(pu)
0.035
Transcribed Image Text:Device Generator G₁ Generator G₂ Generator G3 Transformer Ti Transformer T2 Transformer T3 Line 1 Line 2 Capacity Voltage (MVA) (kV) 100 11 50 11 50 11 70 132/11 70 132/11 70 132/11 Table Q2 X' X₁ X₂ (pu) X" (pu) (pu) 0.15 0.4 0.12 0.35 0.12 0.35 0.07 0.07 0.07 Xo (pu) (pu) 0.12 0.06 0.1 0.05 0.1 0.05 0.07 0.07 0.07 0.07 0.07 0.07 35 52 35 92 35 92 35 92 70 92 70 92 Xn (pu) 0.035
Q2
Figure Q2 shows a single line diagram of a power system and the associated data of this system
are given in Table Q2. The pre-fault load current and A-Y transformer phase shift are
neglected.
(a)
(b)
If a Single Line-to-Ground (S-L-G) fault occurs at Bus 5 and the pre-fault voltage is
1.0 pu, calculate the subtransient fault current in Ampere.
(c)
(d)
(e)
Using base of 100 MVA and 11 kV at generator G₁, construct the positive sequence,
negative sequence and zero sequence networks with their corresponding component
values indicated.
G₁
Recalculate (b) if the neutral on HV side of T3 is solidly grounded.
Repeat part (b) with Line-to-line (L-L) fault.
What will happen to L-L fault current in (d) if the neutral on the HV side of T3 is
solidly grounded?
Bus 1
T₁
Bus 4
Line 1
Line 2
Figure Q2
Bus 5
T2
T3
Bus 2
Bus 3
G₂
G3
Transcribed Image Text:Q2 Figure Q2 shows a single line diagram of a power system and the associated data of this system are given in Table Q2. The pre-fault load current and A-Y transformer phase shift are neglected. (a) (b) If a Single Line-to-Ground (S-L-G) fault occurs at Bus 5 and the pre-fault voltage is 1.0 pu, calculate the subtransient fault current in Ampere. (c) (d) (e) Using base of 100 MVA and 11 kV at generator G₁, construct the positive sequence, negative sequence and zero sequence networks with their corresponding component values indicated. G₁ Recalculate (b) if the neutral on HV side of T3 is solidly grounded. Repeat part (b) with Line-to-line (L-L) fault. What will happen to L-L fault current in (d) if the neutral on the HV side of T3 is solidly grounded? Bus 1 T₁ Bus 4 Line 1 Line 2 Figure Q2 Bus 5 T2 T3 Bus 2 Bus 3 G₂ G3
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 6 steps with 21 images

Blurred answer
Knowledge Booster
Fault analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,