A percentage differential protection scheme is to be designed for a Delta-Star connected, 20 MVA, 22/0.4 kV distribution transformer. The capacity of this transformer to handle the overload can be assumed in the range of 20-35%. The CTs to be used for sensing currents in the primary as well as secondary side of the transformer are available with 1A OR 5A rating. (i) Choose appropriate ratios for the CTs to be used in the protection scheme. QEAD Template A Rev: 04 ver 02 DateDf October 2018 Paget of3 F/QAP/021/001 (ii) Determine pilot wire currents on primary as well as secondary side. (ii) Identify whether interposing CTs are necessary. If they are necessary, outline their specifications and exact location.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.9P
icon
Related questions
Question
A percentage differential protection scheme is to be designed for a Delta-Star connected, 20 MVA,
22/0.4 kV distribution transformer. The capacity of this transformer to handle the overload can be
assumed in the range of 20-35%. The CTs to be used for sensing currents in the primary as well
as secondary side of the transformer are available with 1A OR 5A rating.
(i)
Choose appropriate ratios for the CTs to be used in the protection scheme.
QEAD Template A
Rey: 04 ver 02
Date0f'October 2018
Paget of3
F/QAP/021/001
(ii)
Determine pilot wire currents on primary as well as secondary side.
(i)
Identify whether interposing CTs are necessary. If they are necessary, outline their
specifications and exact location.
(iv)
Sketch the complete protection scheme showing primary/secondary windings for the
transformer, CTs used on primary/secondary sides and exact position of interposing
CTs;
(v)
For the differential relay of 40% setting, determine whether the relay will operate at
35% overload condition.
(vi)
Investigate if the interposing CTs will be necessary if
transformer connections are
changed to Star-Star instead of Delta-Star.
Transcribed Image Text:A percentage differential protection scheme is to be designed for a Delta-Star connected, 20 MVA, 22/0.4 kV distribution transformer. The capacity of this transformer to handle the overload can be assumed in the range of 20-35%. The CTs to be used for sensing currents in the primary as well as secondary side of the transformer are available with 1A OR 5A rating. (i) Choose appropriate ratios for the CTs to be used in the protection scheme. QEAD Template A Rey: 04 ver 02 Date0f'October 2018 Paget of3 F/QAP/021/001 (ii) Determine pilot wire currents on primary as well as secondary side. (i) Identify whether interposing CTs are necessary. If they are necessary, outline their specifications and exact location. (iv) Sketch the complete protection scheme showing primary/secondary windings for the transformer, CTs used on primary/secondary sides and exact position of interposing CTs; (v) For the differential relay of 40% setting, determine whether the relay will operate at 35% overload condition. (vi) Investigate if the interposing CTs will be necessary if transformer connections are changed to Star-Star instead of Delta-Star.
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning