A generator rated 100 MVA, 20 kV has X1=X2=20% and X0 =5% Its neutral is grounded through reactor of 0.32 ohms. The generator is operating at rated voltage with load and is disconnected from the system when a single line to ground fault occurs at its terminals. Find the subtransient current in the faulted phase and line to line voltage.
Synchronous Generator
In comparison to an asynchronous generator, it is a machine where the rotor speed is equal to the rotating magnetic field produced by the stator, i.e., mechanical speed is equal to the electrical speed, thus called synchronous, and not asynchronous.
Salient Pole Rotor
Salient pole rotor includes a large number of exposed poles mounted on a magnetic wheel. The construction of a bright pole is as shown in the image on the left. The proposed poles are made of metal laminations. The rotor winding is provided on these poles and is supported by pole shoes.
A generator rated 100 MVA, 20 kV has X1=X2=20% and X0 =5% Its neutral is grounded through reactor of 0.32 ohms. The generator is operating at rated voltage with load and is disconnected from the system when a single line to ground fault occurs at its terminals. Find the subtransient current in the faulted phase and line to line voltage.