A double line-to-ground fault occurs at F in the system shown in Fig. 6-22. Draw the sequence networks for the system, and calculate the line current I,.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.39P
icon
Related questions
icon
Concept explainers
Question
A double line-to-ground fault occurs at F in the system shown in Fig. 6-22. Draw the sequence networks
for the system, and calculate the line current I,.
Ans.
Fig. 6-23; 4469/123.8° A
35 MVA
11 kV
X = 0.6 pu
X2 = 0.4 pu
F
Line
G
35 MVA
11 kV: 110 kV
X = X2 = Xo = 0.05 pu
Fig. 6-22.
Transcribed Image Text:A double line-to-ground fault occurs at F in the system shown in Fig. 6-22. Draw the sequence networks for the system, and calculate the line current I,. Ans. Fig. 6-23; 4469/123.8° A 35 MVA 11 kV X = 0.6 pu X2 = 0.4 pu F Line G 35 MVA 11 kV: 110 kV X = X2 = Xo = 0.05 pu Fig. 6-22.
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning