A 300-MV A 20-kV three-phase generator has a subtransient reactance of 21%. The generator supplies a number of synchronous motors over a 64-km transmission line having transformers at both ends, as shown on the one-line diagram of the following figure. The motors, all rated 13.2 kV, are represented by just two equivalent motors. The neutral of one motor M, is grounded through reactance. The neutral of the second motor M2 is not connected to ground (an unusual condition). Rated inputs to the motors are 200 MVA and 100 MVA for M1 and M2, respectively. For both motors reactance XM = 20.6%. The three-phase transformer T, is rated 350 MVA, 230/20 kV with leakage reactance of 14%. Transformer T, is rated 220/13.2 kV, 300 MVA with leakage reactance of 10%. The series reactance of the transmission line is 0.44 Ohm/km. Draw the reactance diagram with all reactances marked in per unit. Select the generator rating as the base in the generator circuit.

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
A 300-MV A 20-kV three-phase generator has a subtransient reactance of 21%. The generator supplies a number of
synchronous motors over a 64-km transmission line having transformers at both ends, as shown on the one-line
diagram of the following figure. The motors, all rated 13.2 kV, are represented by just two equivalent motors. The
neutral of one motor M, is grounded through reactance. The neutral of the second motor M2 is not connected to
ground (an unusual condition). Rated inputs to the motors are 200 MVA and 100 MVA for M1 and M2, respectively.
For both motors reactance XM = 20.6%. The three-phase transformer T, is rated 350 MVA, 230/20 kV with leakage
reactance of 14%. Transformer T2 is rated 220/13.2 kV, 300 MVA with leakage reactance of 10%. The series reactance
of the transmission line is 0.44 Ohm/km. Draw the reactance diagram with all reactances marked in per unit. Select
the generator rating as the base in the generator circuit.
13.2 kV
T1
T2
200 MVA
M1 JXMI
64 km
G1
13.2 kV
M, 100 MVA
XMI
20/230 kV
220/13.2 kV
300 MVA
20 kV
350 MVA
300 MVA
XT1
XTI
Xg
Consider a solid three-phase to ground fault occurred at the terminal of motor M2 calculate the magnitude of the
fault current in kA.
Answer:
Transcribed Image Text:A 300-MV A 20-kV three-phase generator has a subtransient reactance of 21%. The generator supplies a number of synchronous motors over a 64-km transmission line having transformers at both ends, as shown on the one-line diagram of the following figure. The motors, all rated 13.2 kV, are represented by just two equivalent motors. The neutral of one motor M, is grounded through reactance. The neutral of the second motor M2 is not connected to ground (an unusual condition). Rated inputs to the motors are 200 MVA and 100 MVA for M1 and M2, respectively. For both motors reactance XM = 20.6%. The three-phase transformer T, is rated 350 MVA, 230/20 kV with leakage reactance of 14%. Transformer T2 is rated 220/13.2 kV, 300 MVA with leakage reactance of 10%. The series reactance of the transmission line is 0.44 Ohm/km. Draw the reactance diagram with all reactances marked in per unit. Select the generator rating as the base in the generator circuit. 13.2 kV T1 T2 200 MVA M1 JXMI 64 km G1 13.2 kV M, 100 MVA XMI 20/230 kV 220/13.2 kV 300 MVA 20 kV 350 MVA 300 MVA XT1 XTI Xg Consider a solid three-phase to ground fault occurred at the terminal of motor M2 calculate the magnitude of the fault current in kA. Answer:
Expert Solution
steps

Step by step

Solved in 3 steps with 1 images

Blurred answer
Knowledge Booster
Stability Analysis in Power System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,