A 10 kVA, single-phase transformer has a turns ratio of 12:1 and is supplied from a 2.4 kV supply. Neglecting losses, determine: (i) the full load secondary current. the minimum value of load resistance which can be clanected across the secondary winding without the kVA rating being exceeded. (ii) (iii) the primary current.
A 10 kVA, single-phase transformer has a turns ratio of 12:1 and is supplied from a 2.4 kV supply. Neglecting losses, determine: (i) the full load secondary current. the minimum value of load resistance which can be clanected across the secondary winding without the kVA rating being exceeded. (ii) (iii) the primary current.
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.34P: Three single-phase, two-winding transformers, each rated 450MVA,20kV/288.7kV, with leakage reactance...
Related questions
Concept explainers
Three-Phase Transformers
Three-segment transformers are a type of transformer used to transform voltages of electrical systems into three ranges. Two type transformers are shell-type transformer and core type transformer. In brief, it could be described because of the exquisite kinds of configurations.
Transformer
Ever since electricity has been created, people have started using it in its entirety. We see many types of Transformers in the neighborhoods. Some are smaller in size and some are very large. They are used according to their requirements. Many of us have seen the electrical transformer but they do not know what work they are engaged in.
Question
![A 10 kVA, single-phase transformer has a turns ratio of 12: 1 and is supplied from a
2.4 kV supply. Neglecting losses, determine:
(i)
the full load secondary current.
the minimum value of load resistance which can be cdanected across the
secondary winding without the kVA rating being exceeded.
(ii)
(iii)
the primary current.](/v2/_next/image?url=https%3A%2F%2Fcontent.bartleby.com%2Fqna-images%2Fquestion%2F5fb00f86-2df7-4b63-b255-84ccdfe8e3ed%2Fb6aefd27-9b1c-4e67-946e-bfba14cc70f5%2Fiq6gasw_processed.png&w=3840&q=75)
Transcribed Image Text:A 10 kVA, single-phase transformer has a turns ratio of 12: 1 and is supplied from a
2.4 kV supply. Neglecting losses, determine:
(i)
the full load secondary current.
the minimum value of load resistance which can be cdanected across the
secondary winding without the kVA rating being exceeded.
(ii)
(iii)
the primary current.
Expert Solution
![](/static/compass_v2/shared-icons/check-mark.png)
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 4 steps
![Blurred answer](/static/compass_v2/solution-images/blurred-answer.jpg)
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
![Power System Analysis and Design (MindTap Course …](https://www.bartleby.com/isbn_cover_images/9781305632134/9781305632134_smallCoverImage.gif)
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
![Power System Analysis and Design (MindTap Course …](https://www.bartleby.com/isbn_cover_images/9781305632134/9781305632134_smallCoverImage.gif)
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning