30 Avar 50 MW LI 30 Iver 50 MW 3 L2 Circuit Breaker G2 180 M 7 30 Mar 50 MW 14 LS 5. 13 30 Ever 50 MW 50 MW 30 Avar Generator Ratings G1: 100 MVA,13.8 kV, x-0.12.x2 -0.14x0-0.05 per unit G2: 200 MVA, 15.0 kV, x=0.12.x2 -0.14.x0-0.05 per unit The generator neutrals are solidly grounded Transformer Ratings T1: 100 MVA,13.8 kVA/230 kVY, x-0.1 per unit T2: 200 MVA, 15 kVA/230 kVY, x-0.1 per unit The transformer neutrals are solidly grounded Transmission Line Ratings All Lines: 230 kV, z₁ -0.08 10.5 /km, 20 0.2+1.5 Qkm, y₁ = 3.3 E-6 S/km, Maximum MVA - 400 Line Lengths: L₁-15 km. L2 assigned by the instructor ( 20 to 50 km), L340 km, L15 km, Ls = 50 km. Power Flow Data Bus 1: Swing bus, V₁ = 13.8 kV, a₁ = 0° Bus 2,3,4,5,6: Load buses Bus 7: Constant voltage magnitude bus, V7 15 kV, PG7 = 180 MW, - 87 Mar < OG7 < + $7 Mar System Base Quantities Spase-100 MVA (three-phase) Vbase 13.8 kV (line-to-line) in the zone of G1

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.9MCQ: Match the following: (i) Hysteresis loss (a) Can be redud by constructing the core with laminated...
Question

For the single-line diagram in the image, convert the zero-, positive-, and negative-sequence reactance date to per-unit using the given base quantities. Use subtransient machine reactances.
Then, USE PowerWorld Simulator, create the generator, transmission line, and transformer input data files.
Next, run the Simulator to compute subtransient fault currents for (1) single line-to-ground, (2) line-to-line, and (3) double line-to-ground bolted faults at each bus. Assume 1.0 per unit prefault voltage and neglect prefault load currents and all losses. Note: L2 = 25 km
Show input data files (machine, transmission line and transformers), output data (fault currents, bus volatges and line currents), and screenshots of the Simulation.

30 Avar
50 MW
LI
30 Iver
50 MW
3
L2
Circuit
Breaker
G2
180 M
7
30 Mar
50 MW
14
LS
5.
13
30 Ever
50 MW
50 MW
30 Avar
Generator Ratings
G1: 100 MVA,13.8 kV, x-0.12.x2 -0.14x0-0.05 per unit
G2: 200 MVA, 15.0 kV, x=0.12.x2 -0.14.x0-0.05 per unit
The generator neutrals are solidly grounded
Transformer Ratings
T1: 100 MVA,13.8 kVA/230 kVY, x-0.1 per unit
T2: 200 MVA, 15 kVA/230 kVY, x-0.1 per unit
The transformer neutrals are solidly grounded
Transmission Line Ratings
All Lines: 230 kV, z₁ -0.08 10.5 /km,
20 0.2+1.5 Qkm, y₁ = 3.3 E-6 S/km,
Maximum MVA - 400
Line Lengths: L₁-15 km. L2 assigned by the instructor (
20 to 50 km), L340 km, L15 km, Ls = 50 km.
Power Flow Data
Bus 1: Swing bus, V₁ = 13.8 kV, a₁ = 0°
Bus 2,3,4,5,6: Load buses
Bus 7: Constant voltage magnitude bus, V7 15 kV,
PG7 = 180 MW, - 87 Mar < OG7 < + $7 Mar
System Base Quantities
Spase-100 MVA (three-phase)
Vbase
13.8 kV (line-to-line) in the zone of G1
Transcribed Image Text:30 Avar 50 MW LI 30 Iver 50 MW 3 L2 Circuit Breaker G2 180 M 7 30 Mar 50 MW 14 LS 5. 13 30 Ever 50 MW 50 MW 30 Avar Generator Ratings G1: 100 MVA,13.8 kV, x-0.12.x2 -0.14x0-0.05 per unit G2: 200 MVA, 15.0 kV, x=0.12.x2 -0.14.x0-0.05 per unit The generator neutrals are solidly grounded Transformer Ratings T1: 100 MVA,13.8 kVA/230 kVY, x-0.1 per unit T2: 200 MVA, 15 kVA/230 kVY, x-0.1 per unit The transformer neutrals are solidly grounded Transmission Line Ratings All Lines: 230 kV, z₁ -0.08 10.5 /km, 20 0.2+1.5 Qkm, y₁ = 3.3 E-6 S/km, Maximum MVA - 400 Line Lengths: L₁-15 km. L2 assigned by the instructor ( 20 to 50 km), L340 km, L15 km, Ls = 50 km. Power Flow Data Bus 1: Swing bus, V₁ = 13.8 kV, a₁ = 0° Bus 2,3,4,5,6: Load buses Bus 7: Constant voltage magnitude bus, V7 15 kV, PG7 = 180 MW, - 87 Mar < OG7 < + $7 Mar System Base Quantities Spase-100 MVA (three-phase) Vbase 13.8 kV (line-to-line) in the zone of G1
Expert Solution
steps

Step by step

Solved in 2 steps with 6 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L