1. Tests of a 10 kVA, 230/2300 V single-phase transformer have yielded the following results: Vacuum test low voltage side: current = 0.45A  Po = 70WLow side short circuit test: voltage = 11.6V  Pcc = 224.3WDetermine: a. Parameters Rcc and Xcc of the equivalent circuit referring to the secondary.b. Transformer voltage regulation, if feeding a load of 4kVA, fp = 0.75 in delayc. Efficiency if the load is 7kVA, fp = 0.8 inductive

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.11MCQ: For a short-circuit test on a 2-winding transformer, with one winding shorted, can you apply the...
icon
Related questions
Question

1. Tests of a 10 kVA, 230/2300 V single-phase transformer have yielded the following results:

Vacuum test low voltage side: current = 0.45A  Po = 70W
Low side short circuit test: voltage = 11.6V  Pcc = 224.3W
Determine:

a. Parameters Rcc and Xcc of the equivalent circuit referring to the secondary.
b. Transformer voltage regulation, if feeding a load of 4kVA, fp = 0.75 in delay
c. Efficiency if the load is 7kVA, fp = 0.8 inductive

Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning