Concept explainers
In problem 35, it is desired to keep the voltage drop to 3% maximum. What minimum size wire would be installed to accomplish this 3% maximum voltage drop? See 210.19(A), Informational Note No. 4 and 215.2(A)(1), Informational Note No. 2.
Find the minimum size wire that should be installed to accomplish 3% maximum voltage drop.
Answer to Problem 36R
10 AWG or larger value conductor should be installed to accomplish 3% maximum voltage drop.
Explanation of Solution
Given data:
Supply voltage is 120-volt.
Current is 10 A.
The distance between panel and heater is approximately 140 ft.
14 AWG, 12 AWG, 10AWG, and 8 AWG copper conductor.
Calculation:
Write the expression for voltage drop in a single-phase circuit.
Here,
K is the approximate resistance in ohms per circular-mil foot at
I is the current, and
CMA is cross-sectional area of the conductors.
Modify Equation (1) for 14 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 14 AWG is 4110.
Substitute
Modify Equation (1) for 12 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 12 AWG is 6530.
Substitute
Modify Equation (1) for 10 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 10 AWG is 10,380.
Substitute
Modify Equation (1) for 8 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 8 AWG is 16,510.
Substitute
Tabulate the calculated value of the voltage drop as shown in Table 1.
Table 1
Sl. No. | Conductor Size | Voltage drop |
1 | 14 AWG | |
2 | 12 AWG | |
3 | 10 AWG | |
4 | 8 AWG |
Find the value of
Compare the obtained value of 3% voltage drop of applied voltage with voltage drops of each conductor as tabulated in Table 1.
A voltage drop of 8AWG conductor (that is 2.19 Volts drop) is less than
Conclusion:
Thus, 10 AWG or larger value conductor should be installed to accomplish 3% maximum voltage drop.
Want to see more full solutions like this?
Chapter 4 Solutions
EBK ELECTRICAL WIRING RESIDENTIAL
Additional Engineering Textbook Solutions
SURVEY OF OPERATING SYSTEMS
Electric Circuits. (11th Edition)
Thermodynamics: An Engineering Approach
Modern Database Management
Automotive Technology: Principles, Diagnosis, And Service (6th Edition) (halderman Automotive Series)
Starting Out with Programming Logic and Design (5th Edition) (What's New in Computer Science)
- 3. The zero sequence current is times the current in neutral wire.arrow_forwardPlease choose the correct answer and explain if possible. Thank you. 4. The main terminal voltage across an ON conducting SCR depends on the instantaneous main terminal current in the following way: a. They are proportional b. The voltage increases as the current increases, but no quite proportionally c. The voltage increases as the current increases, by a squared (seond power) relationship d. They are virtually non-related 5. To turn Off a conducting SCR in a dc-powered circuit, it is necessary to: a. Interrupt (stop) the gate current b. Wait for the main terminal current to fall below IHO when the supply voltage crosses through zero c. Deliver a pulse of negative gate current via the gate lead d. Place a temporary reverse bias across the SCR’s main terminals 6. In a simple RC charging circuit used for trigger-control of an SCR, a good range of adjustment of the RC time-constant is: a. 1 to 5 msec b. 1 to 30 msec c. 0.1 to 10 msec d. 2 to 25 μsecarrow_forwardWhat is the minimum trade size PVC conduit to contain 201 #12AWG TW75 Copper conductors.arrow_forward
- 20. What is the maximum operating temperature of type THWN conductor? a. 750C b. 900C c. 700C d. 1100Carrow_forward22. The voltage applied to the h.v. side of a trans- former during short-circuit test is 2% of its rated of voltage. The core loss will be........percent the rated core loss. (a) 4 (b) 0.4 (c) 0.25 (d) 0.04arrow_forwardh.1. In an alternating-current system, the maximum size for a copper grounding electrode conductor isA. 250 kcmil.B. 3/0.C. 500 kcmil.D. 4/0. h.2. The figure shows a fault condition in an ungrounded electrical system. Which of the following will occurbecause of the fault in this system?A. Only the overcurrent protector at Point A will trip open.B. The ground fault will heavily damage the service.C. Nothing will happen until a second ground fault occurs.D. The overcurrent protection will trip, shutting off all the line side power.arrow_forward
- Why Kelvin bridge is used for measurement of low resistance ____________________. a. due to a large current flow b. due to power dissipation across the circuit c. due to contact and lead resistance d. due to emf source usedarrow_forward14arrow_forwardSketch the figure and explain in detail about the HVDC circuit breakers?arrow_forward
- Describe the construction and symbol of semi conductor devicearrow_forwardMost residential general lighting circuits are wired with 14-AWG copper conductors and are protected by 15-amp circuit breakers. However, there are many electricians who install 12-AWG copper conductors and protect them with 20-amp circuit breakers. How will you know which conductor size and which circuit breaker size will be used for the general lighting branch circuits in the house you are wiring?arrow_forwardWhich of the following Surge Diverter use non-linear resistances in its fabrication? Rod - Gape SD. Lightning Arrester SD. Expulsion Tube SD. O All of the above.arrow_forward
- Electricity for Refrigeration, Heating, and Air C...Mechanical EngineeringISBN:9781337399128Author:Russell E. SmithPublisher:Cengage LearningPower System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage LearningEBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT