State which ungrounded conductors should be disconnected by the high-temperature limit control as per NEC 422.47 and provide the maximum water temperature that is limited by the high-temperature control.
Answer to Problem 1R
The high-temperature limit control should disconnect all the ungrounded conductors and the maximum water temperature limits to
Explanation of Solution
Discussion:
According to National Electric code NEC 422.47, the high-temperature limit control must disconnect all the ungrounded conductors.
Electric water heaters, which are utilized in residential, are listed under UL safety Standard 174, “Household Electric Storage Tank Water Heaters”.
The NEC and UL standard suggest that the electric water heater should be equipped with high temperature cut-off for safety purpose. The high-temperature control limits the water temperature into the maximum limit of
Conclusion:
Thus, the high-temperature limit control should disconnect all the ungrounded conductors and the maximum water temperature limits to
Want to see more full solutions like this?
Chapter 19 Solutions
ELECTRICAL WIRING:RESIDENT.-TEXT (PB)
- A(n) _________ is a reliable conductor used to ensure the required electrical conductivity between metal parts required to be electrically connected. a) Equipment bonding jumper b) Bonding conductor of jumper c) Main bonding jumper d) Equipment grounding conductorarrow_forwardQUESTION 3 We are running 3 wires and a ground in a RMC to a control panel with a 60 amp circuit breaker disconnect in the control panel. The conduit is run along the ceiling where the ambient air temperature is 100 degrees. The control panel feeds our secondary cooling pump. What size are the ungrounded conductors? All conductors have typeTHHN insulation.arrow_forwardA? Conductor is defined in NEC 240.2 as a conductor, other than a service conductor, having overcurrent protection ahead of its point of supply that exceeds the value permitted for similar conductors that are not taps. A. Faulted b. Tap c. Magnetic d. Copper-likearrow_forward
- UPVOTE WILL BE GIVEN. WRITE THE COMPLETE SOLUTIONS LEGIBLY (HANDWRITTEN) NO LONG EXPLANATION NEEDED. SOLVE IN 3 DECIMAL PLACES. BOX THE FINAL ANSWER.arrow_forward8.a. A _______ conductor does not carry current during normal operation.A. neutralB. groundingC. phaseD. grounded8.b. "The complete path of an electric current" describes an electric(al)A. fault.B. circuit.C. source.D. component.arrow_forward14. A grounded circuit conductor and the equipment grounding conductor should always be joined at theservice by aA. steel raceway.B. main bonding jumper.C. bus bar.D. short length of aluminum conductor.arrow_forward
- The ohms per 1000 feet measurements for conductors can be found in _____. Select one: a. article 100 definitions b. 310.15(B)(16) c. annex C d. chapter 9 Table 8arrow_forwardit's urgent please solve asaparrow_forward- Loads, Service, and Overcurrent Protection 6.a. The general lighting load is based on a _______ per square foot basis.A. kilowattB. number of circuitsC. volt-ampereD. general illumination6.b. What's the primary disadvantage of using copper conductors?A. AvailabilityB. WeightC. CostD. Durabilityarrow_forward
- 11. Specific rules apply for the installation of _______, but no identification requirements for them exists.A. grounding electrode conductorsB. grounding electrodes.C. main bonding jumpers.D. equipment grounding conductors.arrow_forward12. Which of the following statements about ground faults is true?A. They can happen if a conductive tool is dropped in an energized equipment's electrical enclosure.B. They usually occur between any grounded circuit conductor and the equipment grounding conductor.C. They can't result from human error.D. They're often normal and typically intentional.arrow_forwardof p o How many conductors enter the ceiling fan/light wall box? Switch ond out let boxes s tirst 10. What type and size of box may be used for the ceiling fan/light wall box?. 11. What type of covers are used with 4 in. square outlet boxes? 12. a. Does the circuit for the Master Bedroom have a grounded circuit conductor? b. Does it have an equipment grounding conductor? c. Explain the difference between a "grounded" conductor and an "equipment grounding" conductor. 13. Approximately how many feet (meters) of 2-wire cable and 3-wire cable are needed to ft complete the circuit supplying the Master Bedroom? Two-wire cable: ft (- m). m). Three-wire cable: 14. If the cable is laid in notches in the corner studs, what protection for the cable must be provided? 15. How high are the receptacles mounted above the finished floor in this bedroom? 16. Approximately how far from the bedroom door is the first receptacle mounted? (See the plans.) 17. What is the distance from the finished floor to…arrow_forward
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT