Delmar's Standard Textbook Of Electricity
7th Edition
ISBN: 9781337900348
Author: Stephen L. Herman
Publisher: Cengage Learning
expand_more
expand_more
format_list_bulleted
Concept explainers
Textbook Question
Chapter 10, Problem 4PA
Using the above example, determine the wire size needed for the 400-ampere service in accordance with the National electrical Code. Assume that the conductors have type THWH insulation. (Note: As a general rule, for each 100 feet of conductor length the wire size is increased one standard size because of voltage drop.)
Expert Solution & Answer
Want to see the full answer?
Check out a sample textbook solutionStudents have asked these similar questions
3. The three bus-bar conductors in an outdoor sub-station are supplied by units ofpost insulators. Each unit
consists of a stack of 3-pin insulators fixed one on the top of the other. The voltage across the lowest
insulator is 8-45 kV and that across the next is 7-25 kV. Find the bus-bar voltage of the station.
[38-8 kV]
The following problems refer to grounding requirements.
1. What is the minimum size copper grounding electrode conductor for a service with
three sets of parallel 350 kcmil conductors (three conductors per phase)?
h.1. In an alternating-current system, the maximum size for a copper grounding electrode conductor isA. 250 kcmil.B. 3/0.C. 500 kcmil.D. 4/0.
h.2. The figure shows a fault condition in an ungrounded electrical system. Which of the following will occurbecause of the fault in this system?A. Only the overcurrent protector at Point A will trip open.B. The ground fault will heavily damage the service.C. Nothing will happen until a second ground fault occurs.D. The overcurrent protection will trip, shutting off all the line side power.
Chapter 10 Solutions
Delmar's Standard Textbook Of Electricity
Ch. 10 - What is the maximum temperature rating of Type...Ch. 10 - 2. Name two types of conductor insulation designed...Ch. 10 - A 10 AWG copper conductor with Type THW insulation...Ch. 10 - 4. Six 1/0 aluminum conductors are to be run in a...Ch. 10 - Name five conditions that must be met for running...Ch. 10 - What is the largest solid (nonstranded) conductor...Ch. 10 - Can Type TW cable be used in an area that has an...Ch. 10 - How is the grounded conductor in a flat...Ch. 10 - What three colors are ungrounded conductors not...Ch. 10 - Twenty-five 12 AWG copper conductors are run in...
Ch. 10 - A single-hase load is located 2800 ft from its...Ch. 10 - It is decided to use parallel 0000 conductors to...Ch. 10 - A three-phase motor operates on 480 V and is...Ch. 10 - You have been hired by a company to connect an...Ch. 10 - 2. You are a journeyman electrician in an...Ch. 10 - You are an electrician working in an industrial...Ch. 10 - Using the above example, determine the wire size...Ch. 10 - 1. A 2 AWG copper conductor is 450 ft long. What...Ch. 10 - 2. An 8 AWG conductor is 500 ft long and has a...Ch. 10 - 3. Three 500-kcmil copper conductors with Type RHH...Ch. 10 - 4. Eight 10 AWG aluminum conductors with Type THWN...Ch. 10 - 5. A three-phase motor is connected to 480 V and...Ch. 10 - 6. A 50-hp DC motor is connected to 250 volts. The...Ch. 10 - 7. A bank of electric heaters has a power rating...Ch. 10 - A 15-hp squirrel-cage induction motor is connected...Ch. 10 - Determine the resistance of a 16 AWG copper...Ch. 10 - Determine the ohms-per-mil-foot of an aluminum...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- 20.a. What's the primary disadvantage of using copper conductors?A. DurabilityB. CostC. AvailabilityD. Weight20.b. The NEC requires that each service-disconnecting means be suitable forA. hazardous locations.B. disconnecting the meter.C. wet conditions.D. the prevailing conditions 20.c. As a general rule, each building or structure is limited to a single service. What's an automatic exceptionto this rule?A. A second service deemed suitable for useB. A second service having the proper markingsC. Emergency systems or fire pumpsD. Higher building occupancyarrow_forwardThe ohms per 1000 feet measurements for conductors can be found in _____. Select one: a. article 100 definitions b. 310.15(B)(16) c. annex C d. chapter 9 Table 8arrow_forward12 - Due to the effect of the resistance of the cable connected to RTD, two-wire cables up to ……. meters and three-wire cables up to ……... meters are used in standard designs. A) 10-150B) 40-500C) 50-195D) 30-230E) 200-1000arrow_forward
- Most residential general lighting circuits are wired with 14-AWG copper conductors and are protected by 15-amp circuit breakers. However, there are many electricians who install 12-AWG copper conductors and protect them with 20-amp circuit breakers. How will you know which conductor size and which circuit breaker size will be used for the general lighting branch circuits in the house you are wiring?arrow_forwardThe following problems refer to grounding requirements. Give the source of yourresponses.1. What is the proper size copper grounding electrode conductor for a 100-ampere service that consists of 3/0 AWG ungrounded conductors?arrow_forwardThe resistance of a wire is 126.48 ohms at 1000C and 100 ohms at 300C. The temperature coefficient of this wire at 00C is ____________per C0.arrow_forward
- Assuming copper, standard wire type, and normal temperature rating, what is the typical conductor size (in awg) for a 60A service in the U.S.?arrow_forwardElectrical Engineering What is the smallest square box that will accommodate four No. 12 conductors and four No. 10 conductors if a. These conductors are pulled through without a splice? b. These conductors are all spliced in the box?arrow_forwardWhat is the withstand rating of a AWG copper conductor? A. 60,516 ampere squared seconds b. 121,032 ampere squared seconds c. 302,580 ampere squared seconds d. 605,160 ampere squared secondsarrow_forward
- 5. Which of the following descriptions of a ground ring is correct?A. A ground ring is a circular formation that's made up of six or more grounding electrodes.B. A ground ring is a coiled conductor that's buried underneath a utility pole.C. A ground ring is a device that's used to clamp a conductor to a water pipe.D. A ground ring is a bare copper conductor that will encircle an entire structure underground.arrow_forwardWhat is the minimum trade size PVC conduit to contain 201 #12AWG TW75 Copper conductors.arrow_forwardb. 63 rule where two different temperatures are encountered for the same conductors 38. An exception to the permits the application of the higher ampacity (lower temperature) if the length of the conductors that enter a higher temperature is not more than 10 ft (3.0 m) or not more than 10% of the total circuit length. C. ampacity rating d. flux rating a. circuit derating b. ampacity derating lood isarrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Delmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage LearningEBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Cengage Learning
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Why HIGH VOLTAGE DC power Transmission; Author: ElectroBOOM;https://www.youtube.com/watch?v=DFQG9kuXSxg;License: Standard Youtube License