Two balanced three phase loads are connected in para. lag, and L 40 kVA at 0.9 pf lead. The loads are fed impedance of 0.15+j0.3 2/0. The line to neutral volta phase shift, the average power dissipated in the transm O A 5.20 O B. None OC 1.73 Q D. 62.45 O E. 46.84 QF. 15.61

icon
Related questions
Question
Two balanced three phase loads are connected in parallel, the loads are L= 40 kW at 0.84 pf
lag, and L= 40 kVA at 0.9 pf lead. The loads are fed from a distribution line with an
impedance of0.15+j0.3 2/0. The line to neutral voltage at the load end is 237 V and zero
phase shift, the average power dissipated in the transmission lines in kW is;
O A 5.20
O B. None
OC1.73
Q D. 62.45
O E. 46.84
Q F. 15.61
Transcribed Image Text:Two balanced three phase loads are connected in parallel, the loads are L= 40 kW at 0.84 pf lag, and L= 40 kVA at 0.9 pf lead. The loads are fed from a distribution line with an impedance of0.15+j0.3 2/0. The line to neutral voltage at the load end is 237 V and zero phase shift, the average power dissipated in the transmission lines in kW is; O A 5.20 O B. None OC1.73 Q D. 62.45 O E. 46.84 Q F. 15.61