The four-bus power system in Figure 2 has following equipment parameters: G1: 500 MVA 13.8 KV, xd"=x1=x2=0.20, x0=0.10pu G2: 750 MVA, 18 kv, xd"=x1=x2=0.18, x0=0.09pu G3: 1000 MVA, 20 kv, xd"=x1=0.17, x2=0.20, x0=0.09pu T1: 500 MVA, 13.8/500 kv, delta-wye, x=0.12pu T2: 750 MVA, 18/500 kv, delta-wye, x=0.10pu T3: 1000 MVA, 20/500 kv, delta-wye, x=0.10pu Each Line: X1 = 50 Ω; X0 = 150 Ω All per-unit reactance values are given on the respective equipment rating (voltage and power) as the base. The inductor connected to generator G3 neutral has a reactance of 0.028 Ω. (a) Draw the zero- positive- and negative-sequence reactance diagrams using a 1,000 MVA, 20 kV base in the zone of generator G3. Neglect ∆ - Y transformer phase shift. (b) Faults at bus 1 are of interest. Determine the Thevenin equivalent of each sequence network as viewed from the fault bus. Prefault voltage is 1.0 pu. Prefault load currents and ∆ - Y transformer phase shift are neglected.

Electricity for Refrigeration, Heating, and Air Conditioning (MindTap Course List)
10th Edition
ISBN:9781337399128
Author:Russell E. Smith
Publisher:Russell E. Smith
Chapter17: Commercial And Industrial Air-conditioning Control Systems
Section: Chapter Questions
Problem 22RQ
icon
Concept explainers
Question

The four-bus power system in Figure 2 has following equipment parameters:

G1: 500 MVA 13.8 KV, xd"=x1=x2=0.20, x0=0.10pu

G2: 750 MVA, 18 kv, xd"=x1=x2=0.18, x0=0.09pu

G3: 1000 MVA, 20 kv, xd"=x1=0.17, x2=0.20, x0=0.09pu

T1: 500 MVA, 13.8/500 kv, delta-wye, x=0.12pu

T2: 750 MVA, 18/500 kv, delta-wye, x=0.10pu

T3: 1000 MVA, 20/500 kv, delta-wye, x=0.10pu

Each Line: X1 = 50 Ω; X0 = 150 Ω

All per-unit reactance values are given on the respective equipment rating (voltage and power) as the base. The inductor connected to generator G3 neutral has a reactance of 0.028 Ω.

(a) Draw the zero- positive- and negative-sequence reactance diagrams using a 1,000 MVA, 20 kV base in the zone of generator G3. Neglect ∆ - Y transformer phase shift.

(b) Faults at bus 1 are of interest. Determine the Thevenin equivalent of each sequence network as viewed from the fault bus. Prefault voltage is 1.0 pu. Prefault load currents and ∆ - Y transformer phase shift are neglected.



T1
T3
G3
j50.0 2
j50.0 2
j50.0 2
T2
G2
Transcribed Image Text:T1 T3 G3 j50.0 2 j50.0 2 j50.0 2 T2 G2
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 7 steps with 6 images

Blurred answer
Knowledge Booster
Fault analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Electricity for Refrigeration, Heating, and Air C…
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning