The busbars of a gonerating station are divided into two soctions A and B by a busbar reactor rated at 8000KVA with 9% reactive drop. On busbar A there are two generators each of 8000 KVA with 12.5% reactance and on busbar B there are two generatore each of 10,000KVA with 10% reactance. Feeders are taken. from sections A and B separately. Calculate the rupturing capacity of each foeder switchgear for 3-phase faults which may occur on any feeder.
Three-Phase Transformers
Three-segment transformers are a type of transformer used to transform voltages of electrical systems into three ranges. Two type transformers are shell-type transformer and core type transformer. In brief, it could be described because of the exquisite kinds of configurations.
Transformer
Ever since electricity has been created, people have started using it in its entirety. We see many types of Transformers in the neighborhoods. Some are smaller in size and some are very large. They are used according to their requirements. Many of us have seen the electrical transformer but they do not know what work they are engaged in.
The busbars of a gonerating station are divided into two soctions A and B by a busbar reactor rated at 8000KVA with 9% reactive drop. On busbar A there are two generators each of 8000 KVA with 12.5% reactance and on busbar B there are two generatore each of 10,000KVA with 10% reactance. Feeders are taken. from sections A and B separately. Calculate the rupturing capacity of each foeder switchgear for 3-phase faults which may occur on any feeder.
Ans: Feeder A 189 MVA; Feeder B 252 MVA
Step by step
Solved in 3 steps with 5 images