T1 transformer full load current, inrush current and damage points. Customer transformer full load current, inrush current and damage points. Initial relay setting criteria (50A, 50B, 51): At the feeder breaker, the 50 A is set for the fault current at 1 km. 50 B is set for the fault current at the recloser. At the recloser, the 50 A (high set) element pickup is set for 4 times customer transformer inrush, then rounded to the nearest 50 amps primary. 50 B is set for 2 times customer transformer inrush (rounded to nearest 50 amps). The 51 element pickup for both relays is set for 55% of the customer transformer inrush, with that value rounded to the nearest 50 amps. Time dial and curve family is specified for each relay location on results sheet. Fault currents and 51 relay operating times for faults at various points in the power system F2 3/0 ASCR: (0.348 + j0.502) Ω/km, recloser at 2.5 km, total length 5 km, feeder voltage 7.20 kV
Synchronous Generator
In comparison to an asynchronous generator, it is a machine where the rotor speed is equal to the rotating magnetic field produced by the stator, i.e., mechanical speed is equal to the electrical speed, thus called synchronous, and not asynchronous.
Salient Pole Rotor
Salient pole rotor includes a large number of exposed poles mounted on a magnetic wheel. The construction of a bright pole is as shown in the image on the left. The proposed poles are made of metal laminations. The rotor winding is provided on these poles and is supported by pole shoes.
. T1 transformer full load current, inrush current and damage points.
- Customer transformer full load current, inrush current and damage points.
- Initial relay setting criteria (50A, 50B, 51):
- At the feeder breaker, the 50 A is set for the fault current at 1 km. 50 B is set for the fault current at the recloser.
- At the recloser, the 50 A (high set) element pickup is set for 4 times customer transformer inrush, then rounded to the nearest 50 amps primary. 50 B is set for 2 times customer transformer inrush (rounded to nearest 50 amps).
- The 51 element pickup for both relays is set for 55% of the customer transformer inrush, with that value rounded to the nearest 50 amps. Time dial and curve family is specified for each relay location on results sheet.
Fault currents and 51 relay operating times for faults at various points in the power system
F2 3/0 ASCR: (0.348 + j0.502) Ω/km, recloser at 2.5 km, total length 5 km, feeder voltage 7.20 kV
![Georgian T1 | Full Load
Georgian T1 I inrush
25X damage (2 sec)
10X damage (9.5 sec)
Customer Transformer | Full Load
Customer Transformer I inrush
25X damage (2 sec)
10X damage (9.5 sec)
50A Setting - Feeder Breaker
50B Setting-Feeder Breaker
50A Setting - Recloser
50B Setting - Recloser
51 Pickup Setting
Georgian B1 bus fault
Customer T2 HV bushing fault
Customer LV bus fault
F2 relay 51P1T-U3
PU =
A
TD=3
F2R1 relay 51P2T-U4
PU =
A
TD = 3
Distance
0 km
0.5 km
1.0 km
1.5 km
2.0 km
2.5 km
3.0 km
3.5 km
4.0 km
4.5 km
5.0 km
2.5 km
3.0 km
3.5 km
4.0 km
4.5 km
5.0 km
Feeder Current
Calculated at 7.20kV
Amps
Customer LV Bus Fault
Calculated at 480V
Multiples
Time (s)](/v2/_next/image?url=https%3A%2F%2Fcontent.bartleby.com%2Fqna-images%2Fquestion%2F59fee194-813e-48b3-afac-012d36abfaa8%2F2a15bc73-4844-4a3c-8158-c684650ee95d%2Fpkygng6_processed.jpeg&w=3840&q=75)
![](/static/compass_v2/shared-icons/check-mark.png)
Step by step
Solved in 3 steps
![Blurred answer](/static/compass_v2/solution-images/blurred-answer.jpg)
![Introductory Circuit Analysis (13th Edition)](https://www.bartleby.com/isbn_cover_images/9780133923605/9780133923605_smallCoverImage.gif)
![Delmar's Standard Textbook Of Electricity](https://www.bartleby.com/isbn_cover_images/9781337900348/9781337900348_smallCoverImage.jpg)
![Programmable Logic Controllers](https://www.bartleby.com/isbn_cover_images/9780073373843/9780073373843_smallCoverImage.gif)
![Introductory Circuit Analysis (13th Edition)](https://www.bartleby.com/isbn_cover_images/9780133923605/9780133923605_smallCoverImage.gif)
![Delmar's Standard Textbook Of Electricity](https://www.bartleby.com/isbn_cover_images/9781337900348/9781337900348_smallCoverImage.jpg)
![Programmable Logic Controllers](https://www.bartleby.com/isbn_cover_images/9780073373843/9780073373843_smallCoverImage.gif)
![Fundamentals of Electric Circuits](https://www.bartleby.com/isbn_cover_images/9780078028229/9780078028229_smallCoverImage.gif)
![Electric Circuits. (11th Edition)](https://www.bartleby.com/isbn_cover_images/9780134746968/9780134746968_smallCoverImage.gif)
![Engineering Electromagnetics](https://www.bartleby.com/isbn_cover_images/9780078028151/9780078028151_smallCoverImage.gif)