Situation 2 A gusset plate is connected to a main member with four A325 bolts with threads excluded from shear plane are used in standard holes. Determine the forces acting on the most critical bolt and its utilization ratio for shearing failure. Given: Pu = 55 kN e = 225 mm X = 150 mm Y = 250 mm Diameter of bolts = 16 mm Required: 1. Shear force acting on the most critical bolt due to direct shear (Q₁) kN 2. Horizontal component of the shear force acting on the most critical bolt due to torsion (Qmx) KN. 3. Vertical component of the shear force acting on the most critical bolt due to torsion (Qmy) kN. 4. Total shear force acting on the most critical bolt (V.) kN 5. Utilization ratio of the connection based on bolt shearing failure. X Pu

Steel Design (Activate Learning with these NEW titles from Engineering!)
6th Edition
ISBN:9781337094740
Author:Segui, William T.
Publisher:Segui, William T.
Chapter7: Simple Connections
Section: Chapter Questions
Problem 7.6.4P
icon
Related questions
icon
Concept explainers
Question
Situation 2 A gusset plate is connected to a main member with four A325 bolts with threads excluded from shear
plane are used in standard holes. Determine the forces acting on the most critical bolt and its utilization ratio for
shearing failure.
Given:
Pu= 55 kN
e = 225 mm
X = 150 mm
Y = 250 mm
Diameter of bolts = 16 mm
Required:
1. Shear force acting on the most critical bolt due to direct shear (Q₁) kN
2. Horizontal component of the shear force acting on the most critical bolt due
to torsion (Qmx) KN.
3. Vertical component of the shear force acting on the most critical bolt due to
torsion (Qmy) kN.
4. Total shear force acting on the most critical bolt (V₁) KN
5. Utilization ratio of the connection based on bolt shearing failure.
X
Pu
Transcribed Image Text:Situation 2 A gusset plate is connected to a main member with four A325 bolts with threads excluded from shear plane are used in standard holes. Determine the forces acting on the most critical bolt and its utilization ratio for shearing failure. Given: Pu= 55 kN e = 225 mm X = 150 mm Y = 250 mm Diameter of bolts = 16 mm Required: 1. Shear force acting on the most critical bolt due to direct shear (Q₁) kN 2. Horizontal component of the shear force acting on the most critical bolt due to torsion (Qmx) KN. 3. Vertical component of the shear force acting on the most critical bolt due to torsion (Qmy) kN. 4. Total shear force acting on the most critical bolt (V₁) KN 5. Utilization ratio of the connection based on bolt shearing failure. X Pu
Expert Solution
steps

Step by step

Solved in 6 steps with 5 images

Blurred answer
Knowledge Booster
Load and resistance factor design
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, civil-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Steel Design (Activate Learning with these NEW ti…
Steel Design (Activate Learning with these NEW ti…
Civil Engineering
ISBN:
9781337094740
Author:
Segui, William T.
Publisher:
Cengage Learning