Question

Answer all

Q1 (a) A balanced star connected load of (8 + j3) Q is connected to a 3-phase, 415 V
and 50 Hz supply.
Draw the circuit diagram, indicating VRN, VRY and all line currents.
Calculate:
(i)
(ii)
The 3 line currents (IR, Iy and IB).
The total real power (W) and power factor at the 3 phase
supply.
(b)
An unbalanced delta connected load consisting of the phase impedances ZRY
(10+j3) 2, ZYB (12+j0) 2 and ZBr (8+j3) N is connected to a 3-phase, 440
V, 50 Hz supply. Draw the circuit diagram including the implementation of
a 2 wattmeter power measurement.
Using the information above:
(i)
(ii)
Calculate the 3 load phase currents (IRY, IYB and IBR).
Draw a scaled phasor diagram indicating all phase and line
voltages and the three load phase currents.
Using the scaled phasor diagram or otherwise determine the 3
line currents (IR, Iy and IB).
(iii)
Transcribed Image Text:Q1 (a) A balanced star connected load of (8 + j3) Q is connected to a 3-phase, 415 V and 50 Hz supply. Draw the circuit diagram, indicating VRN, VRY and all line currents. Calculate: (i) (ii) The 3 line currents (IR, Iy and IB). The total real power (W) and power factor at the 3 phase supply. (b) An unbalanced delta connected load consisting of the phase impedances ZRY (10+j3) 2, ZYB (12+j0) 2 and ZBr (8+j3) N is connected to a 3-phase, 440 V, 50 Hz supply. Draw the circuit diagram including the implementation of a 2 wattmeter power measurement. Using the information above: (i) (ii) Calculate the 3 load phase currents (IRY, IYB and IBR). Draw a scaled phasor diagram indicating all phase and line voltages and the three load phase currents. Using the scaled phasor diagram or otherwise determine the 3 line currents (IR, Iy and IB). (iii)
Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Analog to digital converters
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning