A 400V (line-to-line), 50Hz, six-pole, 3-phase induction motor is taking 40kVA at 0.8 power factor. It is running at a slip of 2.5%. The stator copper losses are 0.4kW and rotational losses are 2.5kW. Determine: a) The rotor copper losses. b) The shaft hp. c) The shaft torque.

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter32: Three-phase Motors
Section: Chapter Questions
Problem 6RQ: Name three factors that determine the torque produced by an induction motor.
icon
Related questions
Question
100%
A 400V (line-to-line), 50Hz, six-pole, 3-phase induction motor is taking 40kVA at 0.8 power
factor. It is running at a slip of 2.5%. The stator copper losses are 0.4kW and rotational losses
are 2.5kW. Determine:
a) The rotor copper losses.
b) The shaft hp.
c) The shaft torque.
Transcribed Image Text:A 400V (line-to-line), 50Hz, six-pole, 3-phase induction motor is taking 40kVA at 0.8 power factor. It is running at a slip of 2.5%. The stator copper losses are 0.4kW and rotational losses are 2.5kW. Determine: a) The rotor copper losses. b) The shaft hp. c) The shaft torque.