A 30-MW 10-kV Y-connected three-phase 60-Hz synchronous generator is connected to a grid. The gen- rator has six poles, and resistance and reactance of this generator are 0.1 Ohm and 0.75 Ohm, respectively. a) Find the speed of this generator both in rpm and rad/sec. b) Find the internal voltage (Ea) and generator efficiency (7) when it is supplying its full load at rated voltage and frequency with power factor of 0.85 lagging. Assume friction and windage losses to be 1 MW and core losses to be 800 kW. c) If the load of Part (b) is suddenly dropped, find the terminal voltage of the generator. d) When the load is 25 MVA at rated voltage with 0.80 lag. power factor, find the voltage regulation of the generator.

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
icon
Concept explainers
Question
A 30-MW 10-kV Y-connected three-phase 60-Hz synchronous generator is connected to a grid. The gen-
erator has six poles, and resistance and reactance of this generator are 0.1 Ohm and 0.75 Ohm, respectively.
a) Find the speed of this generator both in rpm and rad/sec.
b) Find the internal voltage (Ea) and generator efficiency (n) when it is supplying its full load at rated
voltage and frequency with power factor of 0.85 lagging. Assume friction and windage losses to be 1
MW and core losses to be 800 kW.
c) If the load of Part (b) is suddenly dropped, find the terminal voltage of the generator.
d) When the load is 25 MVA at rated voltage with 0.80 lag. power factor, find the voltage regulation of
the generator.
Transcribed Image Text:A 30-MW 10-kV Y-connected three-phase 60-Hz synchronous generator is connected to a grid. The gen- erator has six poles, and resistance and reactance of this generator are 0.1 Ohm and 0.75 Ohm, respectively. a) Find the speed of this generator both in rpm and rad/sec. b) Find the internal voltage (Ea) and generator efficiency (n) when it is supplying its full load at rated voltage and frequency with power factor of 0.85 lagging. Assume friction and windage losses to be 1 MW and core losses to be 800 kW. c) If the load of Part (b) is suddenly dropped, find the terminal voltage of the generator. d) When the load is 25 MVA at rated voltage with 0.80 lag. power factor, find the voltage regulation of the generator.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 5 steps with 5 images

Blurred answer
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,