A 1.5 KVA, 220:110 V, 60 Hz, single-phase transformer gave the following test results: Open-circuit test: Short-circuit test: V-110 V V-8.25 V I=0.4 A I-13.6 A P=25 W P = 40 W a) Determine the parameters of the approximate equivalent circuit of the transformer referred to the high-voltage side. b) Determine the efficiency of the transformer at full-load, 110 V, and 0.8 power factor leading. Use the approximate circuit.
A 1.5 KVA, 220:110 V, 60 Hz, single-phase transformer gave the following test results: Open-circuit test: Short-circuit test: V-110 V V-8.25 V I=0.4 A I-13.6 A P=25 W P = 40 W a) Determine the parameters of the approximate equivalent circuit of the transformer referred to the high-voltage side. b) Determine the efficiency of the transformer at full-load, 110 V, and 0.8 power factor leading. Use the approximate circuit.
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.11MCQ: For a short-circuit test on a 2-winding transformer, with one winding shorted, can you apply the...
Related questions
Question
thank u!! anything helps
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 2 steps with 3 images
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning