EET 114 Drawing Project Residential Example 2021

docx

School

Centennial College *

*We aren’t endorsed by this school

Course

EET114

Subject

Electrical Engineering

Date

Feb 20, 2024

Type

docx

Pages

64

Uploaded by sadia22tabassum11

Report
Section 1: Introduction
In this project, there was the practical knowledge application of 1 . ) Receptacles 2.) Lightings 3.) Service entrance sizing 4.) Branch circuits 5.) Overcurrent protections In order to fully complete this project, there was a need to 1 . ) Allocate receptacles, lights, and switches in the drawing and identify all the branch circuits. 2.) Assess the service entrance calculations of the dwelling unit. 3.) Select the conductor sizes and find the overcurrent protection devices for each branch circuit. 4.) Compute the voltage drops of the branch circuits. 5.) Insert specifications for the devices. In order to follow the minimum safety standards set by the CSA, this project was guided by the Canadian Electrical Code book. There was also the use of various computer programs including 1. ) AutoCAD which was used to add receptacles, lightings and their branch circuits in the drawing. 2.) Microsoft Word which was used for the various write ups. 3.) Photoshop which was used to design the cover page.
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
3
4.) Adobe Acrobat which was used to combine all the documents into pdf. 5.) Microsoft Excel which was used to perform calculations. The hand tools required were 1.) Pliers (various) for wire cutting. 2.) Screwdrivers (various) for installation of screws. 3.) Wire strippers for removing insulation from a conductor. 4.) Wire nuts to connect two or more conductors together. 5.) Hacksaws for cutting conduits. 6.) Staples used for wire fastening. 7.) Connectors to secure cables. 8.) Knife for skinning wires and other cutting purposes. This is a student project which gives the students the opportunity to test the validity of the project. This is not meant to be used outside of an academic setting.
Section 2: Load Estimation and Service Entrance Calculations 6
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Service Entrance Calculations Area: Basic Demand First floor area 170 m 2 8-110 (a) 170 m 2 x 100% = 170 m 2 Basement 170 m 2 8-110(c) 170 m 2 x 75% = 128 m 2 128 + 170 = 298 m 2 8-200(1 First 90 rn 2 is 5000 W 8-200(1 )(a)(ii) Next 90 m 2 or portion of, is 1000 W Basic demand: 5000W+ 1000W + 1000W +1000W = 8000 W Range 8-200(1 First 12 kW is 6000 W Over 12 kW 4200 W x 0.40 = 1680 W Therefore, demand is 6000 W + 1680 W: 7680 W Basement range + First floor range = 7680 W + 7680 W = 15360 W https://www.canadianappliance.ca/product/LG LREL6325F Range LG LREL6325F.ht ml Sauna (Hydromassage hot tub) 8-200(1 2300 w x 100% = 2300 w Basement hot tub + First floor hot tub = 2300 W +2300 W = 4600 W Reference: https://www.hydromassageproducts.com/shop/cascade-7242-platinum-series- withhydro-air-massaqe-size-72-x-42-x-26-iets-38-total-iets Air-conditioning(centralized)
8-106 (4) not interlocked with heating 8400 w x 100% = 8400 w 8
Reference: https://www.lowes.com/pd/MRCOOL-Signature-Series-Heat-Pump- PackageResidential-2-5- Ton-14-Seer-Central-Air-Conditioner/1002623786 Heating demand (electric furnace) 15000 W First 10 kW x 100% = 10000 W Remaining 5 kW x 75% = 3750 W Therefore, demand is 10000 W + 3750 W = 13750 W Additional Loads: Water Heater, Dryer, Water pump, Microwave Oven 8-200(1 Dryer 7200 W x 25% = 1800 W Reference: https://www.homedepot.ca/product/lg-electronics- 7-4-cu-ft-smart-e/ectric-dryer-with ultra- large-capacity-and-wi-fi-in-white-stackable-energy-star-/1001133690 8-200(1 Heater 4500 W x 25% = 1125 W Reference: https://www.lowes.com/pd/A-O-Smith-Signature-40-Gallon-Tall-6-year-Limited- 4500Watt-Double-Element-Electric-Water-Heater/1000213649 8-200(1 Water pump 3450 W x 25% = 860 W Reference: https://www.lowes.com/pd/Acquaer-1-HP-Dual- Voltaae-Cast-lron-Convertible- JetPump/5001226193 8-200(1 Microwave oven 1600 W x 25% = 400 W x 2 = 800 W Demand is 800 W + 860 W + 1125 W + 1800 W = 4585 W 9
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Total Demand (in watts) = 54695 W Ohm's Law I = P / E = 54695 W / 240 V = 228 A Size of Conductors Ungrounded Conductor: Copper wire RW90 (Table 2) 228 A for RW90 (90 0 C); therefore, use two # 410 AWG conductor. Ground Conductor: (Table 16); Rules 10-114 for minimum size, 10-614(2) Since we are using # 4/0 AWG for undergrounded conductor, therefore, the ground size is 4 AWG. Breaker Calculations (Table 13) Between 226 A to 250 A; Size of breaker 250 A Conclusion Standard available sizes of disconnect are 60A, IOOA, 200A, and 400A. Most residential applications are either 100 A, 200 A or 400 A. Therefore, the panel size is 400 A, and 500 kcmil RW90 will be required for the underground conductors. 10
Section 3: Receptacles and Lighting Outlets
LEGEN C L C)- W Ops PU FAN OUTLET RECESSED LUMIN ZSZOZSZ TR PADDLE FAN L $4 VARIABLE SINGLE RE DUPLEX R SPLIT-WIR 20A T-SLO NOTES: ALL SWITCH 2. ALL RECEPTACLES ARE TO WHICH WILL 3. RECEPTACLES ABOVE COU 4. ALL ELECTRICAL PANELS Al 5. LUMINAIRES ON LANDING O 6. PROVIDE TR, GFCI AND AFC Basement Plan
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
(Scale 1 : 100) Jn'D PROJECT NAME: ABC PROJECT DRAWING TITLE: BASEMENT LIGHTING AND RECEPTACLE LAYOUT PLAN DRAWN DRAWING NO.: AAAA-BBBBB-EA-CCCC-OOOI CHECKE FILE NAME: AAAA-BBBBB-EA-CCCC-OOOI RA AppRO
LEGEN C L C)- WALL Ops PULL FAN OUTLET RECESSED LUMIN ZSZOZSZ TR PADDLE FAN LI SINGLE POLE SWI 3 $4 VARIABLE SPEED SINGLE RECEPTA DUPLEX RECEPTP SPLIT-WIR 20A T-SLO NOTES: ALL SWITCH 2. ALL RECEPTACLES ARE TO WHICH WILL 3. RECEPTACLES ABOVE COU 4. CENTER OF WP RECEPTACI HORIZONTAL IN MA, 5. LUMINAIRES ON LANDING 6. PROVIDE TR, GFCI AND AFC Ground Floor Plan (Scale 1 : 100) PROJECT NAME: DRAWING TITLE: 14
Jn'D ABC PROJECT GROUND FLOOR LIGHTING AND RECEPTACLE LAYOUT PLAN DRAWN DRAWING NO.: AAAA-BBBBB-EA-CCCC-0002 CHECKE FILE NAME: AAAA-BBBBB-EA-CCCC-0002 RA AppRO 1 0 1 1 Section 4: Conductors and Over Current Protection Devices (OCPDs)
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Breaker Size and Conductor Size for Receptacles: 1. Living Room, Dining Room, Family Room, Hallway, Bedroom A. Breaker Size Maximum of 12 outlets per circuit, IA per outlet. (CEC Rule 8-304(1) and (2)) Use 15A, 120V, 2-wire branch circuit. B. Conductor Size Use No. 14 AWG copper conductors for 15A breaker. (CEC Rule and Table 2 2. Porch or Balcony A. Breaker Size Maximum of 12 outlets per circuit, IA per outlet. (CEC Rule 8-304(1) and (2)) Use 15A, 120V, 2-wire branch circuit. B. Conductor Size Use No. 14 AWG copper conductors for 15A breaker. (CEC Rule and Table 2 3. Bathroom Receptacles A. Breaker Size Use 15A, 120V, 2-wire branch circuit. B. Conductor Size Use No. 14 AWG copper conductors for 15A breaker. (CEC Rule and Table 2 4. Cord-connected Hydro-massage Bathtub A. Breaker Size The cord-connected hydro-massage bathtub in this residence has a rating of 2300W. Thus, I = W / E = 2300 / 120 = 19.2 amperes If we apply Rule 8-104, that is, to multiply the current rating by 125% to find the required circuit ampacity, we find that 19.2 amperes x 1.25 = 24 (30) amperes Accordingly, we use 30A, 120V, 2-wire branch circuit. B. Conductor Size Use No. 10 AWG copper conductors for 30A breaker. (CEC Rule and Table 2 16
5. Laundry Room Receptacles A. Breaker Size At least one branch circuit. (CEC Rule 26-652(b)) Use 15A, 120V, 2-wire branch circuit. B. Conductor Size Use No. 14 AWG copper conductors for 15A breaker. (CEC Rule and Table 2 6. Dryer C. Breaker Size The electric clothes dryer in this residence has a rating of 7200W. Thus, I = W / E = 7200 / 240 = 30 amperes If we apply Rule 8-104, that is, to multiply the current rating by 125% to find the required circuit ampacity, we find that 30 amperes x 1.25 = 37.5 (40) amperes Accordingly, we use 40A, 120/240V, 3-wire branch circuit. D. Conductor Size Use No. 8 AWG copper conductors as per Table 2. 7. Utility Room Receptacles A. Breaker Size At least one branch circuit. (CEC Rule 26-652(c)) Use 15A, 120V, 2-wire branch circuit. B. Conductor Size Use No. 14 AWG copper conductors for 15A breaker. (CEC Rule and Table 2 8. Electric Furnace A. Breaker Size The furnace in this residence has a rating of 15000W. Thus, I = W / E = 15000 / 240 = 62.5 amperes If we apply Rule 8-104, that is, to multiply the current rating by 125% to find the required circuit ampacity, we find that 17
62.5 amperes x 1.25 = 78.125 (80) amperes Accordingly, we use 80A, 240V, 3-wire branch circuit. A. Conductor Size Use No. 3 AWG copper conductors for 80A breaker as per Table 2. 9. Water Pump B. Breaker Size The water pump in this residence has a rating of 3450W. Thus, I = W / E = 3450 / 240 = 14.375 amperes If we apply Rule 8-104, that is, to multiply the current rating by 125% to find the required circuit ampacity, we find that 14.375 amperes x 1.25 = 18 (20) amperes Accordingly, we use 20A, 240V, 3-wire branch circuit. C. Conductor Size Use No. 12 AWG copper conductors for 20A breaker. (CEC Rule and Table 2 10. Water Heater D. Breaker Size The water heater in this residence has a rating of 4500W. Thus, I = W / E = 4500 / 240 = 18.75 amperes If we apply Rule 8-104, that is, to multiply the current rating by 125% to find the required circuit ampacity, we find that 18.75 amperes x 1.25 = 23.5 (30) amperes Accordingly, we use 30A, 240V, 3-wire branch circuit. E. Conductor Size Use No. 10 AWG copper conductors for 30A breaker. (CEC Rule and Table 2 11. Workbench Receptacles A. Breaker Size Maximum of 12 outlets per circuit, IA per outlet. (CEC Rule 8-304(1) and (2)) Use 15A, 120V, 2-wire branch circuit. B. Conductor Size 18
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Use No. 14 AWG copper conductors for 15A breaker. (CEC Rule and Table 2 12. Air Conditioner A. Breaker Size The specifications read "Full Load Amperage Requirement (Amps) is 35A." Use 40A, 240V, 3-wire branch circuit. B. Conductor Size Use No. 8 AWG copper conductors as per Table 2. 13. Kitchen A. Breaker Size At least two branch circuits and no more than two receptacles in a circuit. (CEC Rule Use 20A, 120V, 2-wire branch circuit. B. Conductor Size Use No. 12 AWG copper conductors for 20A breaker. (CEC Rule and Table 2 14. Electric Range A. Breaker Size The specifications read "Required Power Supply (amp) is 40A." Use 40A, 120/240V, 3-wire branch circuit. B. Conductor Size Use No. 8 AWG copper conductors as per Table 2. 15. Microwave F. Breaker Size The microwave oven in this residence has a rating of 1600W. Thus, I = W / E = 1600 / 120 = 14 amperes If we apply Rule 8-104, that is, to multiply the current rating by 125% to find the required circuit ampacity, we find that 14 amperes x 1.25 = 17.5 (20) amperes Accordingly, we use 20A, 120V, 2-wire branch circuit. G. Conductor Size 19
Use No. 12 AWG copper conductors for 20A breaker. (CEC Rule and Table 2 16. Refrigerator A. Breaker Size At least one branch circuit. (CEC Rule 26-652(a)) Use 15A, 120V, 2-wire branch circuit. B. Conductor Size Use No. 14 AWG copper conductors for 15A breaker. (CEC Rule and Table 2 17. Range Hood A. Breaker Size Use 15A, 120V, 2-wire branch circuit. B. Conductor Size Use No. 14 AWG copper conductors for 15A breaker. (CEC Rule and Table 2 20
Breaker Size and Conductor Size for Lighting and Switches: 1. Living Room, Dining Room, Guest Room, Hallway, Bedroom A. Breaker Size Branch circuit voltage shall not exceed 150 volts-to-ground in dwelling units. (CEC Rule 30-102(1)) Lightning equipment shall not be connected to a branch circuit protected by overcurrent devices rated or set more than 15 A in dwelling units. (CEC Rule 30-104(a)) Use 15 A, 120V B. Conductor Size Where the pendant cables supply mogul or medium-base screw shell lamp holders, they shall not be smaller than No. 14 AWG. (CEC Rule 30- 608(2)) Use No. 14 AWG copper conductors for 15A breaker. 2. Bathroom, Laundry Room A. Breaker Size Branch circuit voltage shall not exceed a nominal system voltage 347/600Y in other than dwelling units (CEC Rule 30-102(2)) Lightning equipment shall not be connected to a branch circuit protected by overcurrent devices rated or set more than 15 A in other than dwelling units, where the input voltage exceeds 347V nominal. (CEC Rule 30- 104(b)) Use 15 A, 120 V B. Conductor Size No. 14 AWG copper tap connection insulated conductors shall be permitted for a single luminaire and for luminaires mounted in a continuous row, on a branch circuit protected by an overcurrent device rated or a set at 20 A. Use No. 14 AWG copper conductors for 20 A breaker. 3. Kitchen and Dining Lighting A. Breaker Size Branch circuit voltage shall not exceed a nominal system voltage 347/600Y in other than dwelling units. (CEC Rule 30-102(2)) Lightning equipment shall not be connected to a branch circuit protected by overcurrent devices rated or set more than 15 A in other 21
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
than dwelling units, where the input voltage exceeds 347V nominal. (CEC Rule 30-104(b)) Use 15 A, 120 V B. Conductor Size Where the pendant cables supply mogul or medium-base screw shell lamp holders, they shall not be smaller than No. 14 AWG. (CEC Rule 30-608(2)) Use No. 14 AWG copper conductors for 15A breaker. 4. Closet A. Breaker Size Luminaires provided with an integral overcurrent device rated at not more than 15 A, where the input voltage does not exceed 120 V. Use 15 A, 120 V B. Conductor Size Where the pendant cables supply mogul or medium-base screw shell lamp holders, they shall not be smaller than No. 14 AWG. (CEC Rule 30- 608(2)) Use No. 14 AWG copper conductors for 15A breaker. 22
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Panel Schedule Main Service Panel A Circuit Number Circuit Ampere Ratin Volts Poles Wire Size Comments 1-3 80 40 240 240 Electric Furnace Air Conditioner 5-7 6-8 20 30 30 240 240 120 12 10 Water Pum Water Heater 10 30 120 10 10 14 Master Bath Hydromassage Tub Guest Bathroom Hydromassage Tub 11 12 15 15 120 120 14 14 Livin Room and Master Bedroom Li htin Bedroom 1, 2 and 3 Lig htin 13 14 15 15 120 120 14 14 Closet-M and Master Bathroom Li htin Master Bedroom Rece tacles 15 16 15 15 120 120 14 14 Worksho and Utili Area Li htin Closet 1, 2, 3 Li htin 17 18 15 15 120 120 14 14 Bedroom 1 Receptacles Bedroom 2 Receptacles 19 20 15 15 120 120 14 14 Bedroom 3 Rece tacles Workbench Rece tacles 22 15 15 120 120 14 Main Bathroom Receptacles Utili Room Rece tacles 23 24 25 15 15 15 120 120 120 14 14 14 14 Master Bathroom Receptacles First Floor Range Hood Basement Ran e Hood 26 27-29 15 200 120 120/240 Front Outdoor Rece tacles Sub Panel Feeder to Panel B 28 30 S are S are Panel B Circuit Number Circuit Ampere Rating 40 Volts Poles Wire Size Comments 1-3 40 120/240 120/240 120 14 Electric D er First Floor Ran e 6-8 15 40 120/240 14 LaundryRoom Rece tacles Basement Range 15 20 120 120 12 Entertain ment Ar ea R eceptacles Kitchen Is land Co unter Rec eptacles 10 11 20 15 120 120 12 14 14 Basement Counterto Rece tacles Entertainment Area and Kitchennet Li htin 23
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
12 13 14 15 15 120 120 14 14 Guest Room Receptacles Guest Bathroom Receptacles 15 15 20 120 120 12 Living Room Receptacles First Floor Microwave 16 17 20 120 12 14 Basement Microwave S are 18 19 15 15 120 120 14 Guest Room, Bathroom and Closet-G Li htin Laund Li htin 20 21 22 15 15 15 120 120 120 14 14 14 14 First Floor Refrigerator Basement Refrigerator Worksho Rece tacles 23 24 15 15 120 120 14 14 Dinin Area and Kitchen Li htin Main Bathroom Li htin 25 26 27 15 20 20 120 120 120 12 Dinin Area Rece tacles Countertop Receptacles near the dining area 28 20 120 12 12 14 Countertop Receptacles near the sink Counterto Rece tacles near the door 29 30 15 15 120 120 14 Back Outdoor Rece tacles Ent , Outside and Stairwa Li htin Voltage Drop Calculation: Formula The formula for calculating voltage drop on singlephase systems considers only the DC resistance of the conductors and the temperature of the conductor. K = resistance of conductor at 75 0 C For copper conductors • about 12 ohms per circular mil foot CMA • about 39.4 ohms per circular mil metre* For aluminum conductors about 19 ohms per circular mil foot about 63.3 ohms per circular mil metre* Current (l) Current in amperes flowing through the conductors. 24
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Lenqth (L) Length of the conductor from the beginning of the circuit to the load: In feet if the circular mil foot is used for K In metres if the circular mil metre is used for K The length of the cable can be estimated roughly, and to ensure that the estimate is not short, make all measurements "square". 25
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
CMA Cross-sectional area of the conductor in circular mils. Nominal AWG CM Area 14* 8 6 4 3 2 1 00 000 0000 4 110 6 530 10 380 16 510 26 240 41 740 52 630 66 360 83 690 105 600 133 100 167 800 211 600 •These sizes are customarily supplied with solid conductors. 26
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Voltage Drop Calculation *Maximum allowable voltage drop on a branch is 3%. Main Service Panel A Voltage Drop Calculation Circuit Number Circuit Ampere Ratin Volts Poles Wire Size Comments K (ohms per CM-ft L (ft) CMA Ed (V) Ed (%) 1-3 2-4 80 40 240 240 Electric Furnace Air Conditioner 12 12 62.5 35 54.5 72 52630 16510 1.55 3.66 2.14 0.65 1.53 20 30 240 240 12 10 Water Pum Water Heater 12 12 14.375 18.75 40.5 54.5 6530 10380 2.36 0.89 0.98 10 Il 30 30 15 120 120 120 10 10 14 Master Bath H dromassa e Tub Guest Bathroom_Hy dromas sage Tub Living Room a nd Master Bedroom Li htin 12 12 12 19.2 19.2 78.5 70.5 113.5 10380 10380 4110 3.48 3.13 3.31 2.90 2.61 2.76 12 13 15 15 120 120 14 14 Closet-M and Master Bathroom Li htin 12 12 4.5 92.5 137 4110 4110 2.43 2.40 2.03 2.00 14 15 15 15 120 120 14 14 Master Bedroom Rece tacles Worksho and Utili Area Li hti 12 12 5.8 98 4110 4110 3.43 1.83 2.86 1.52 16 17 15 15 120 120 14 14 Closet 1 2 3 Lighting Bedroom 1 Rece tacles 12 12 51 72 4110 4110 0.89 1.68 1.44 0.74 1.40 18 19 15 15 120 120 14 14 Bedroom 2 Rece tacles Bedroom 3 Rece tacles 12 12 61.5 55 4110 4110 1.28 1.20 1.07 20 22 23 15 15 15 15 120 120 120 120 14 14 1 4 14 14 Workbench Rece tacles Main Bathroom Receptacles Utility Room Receptacles Master Bathroom Rece tacles 12 12 40.5 42 4110 4110 4110 4110 1.66 1.47 1.38 1.23 0.28 2.76 12 12 57.5 94.5 45 0.34 3.31 24 25 15 15 15 120 120 120 14 14 First Floor Ran e Hood Basement Ran e Hood Front Outdoor Rece tacles 12 12 12 12 12 37 49 4110 4110 4110 3.15 2.59 0.29 2.63 2.16 0.24 27-29 200 120/240 3/0 Sub Panel Feeder to Panel B Spare S are Panel B Voltage Drop Calculation Circuit Number Circuit Ampere Ratin Volts Poles Wire Size Comments K (ohms per CM-ft CMA Ed (V) Ed (%) 1-3 40 40 120/240 120/240 Electric Dryer First Floor Ran e 12 12 30 40 71.5 73 16510 16510 3.12 4.24 1.30 1.77 15 40 120 1201240 14 Laund Room Rece tacles Basement Ran e 12 12 40 71.5 65 4110 16510 1.25 3.78 1.04 1.57 15 20 120 120 14 12 12 Entertainment Area Receptacles Kitchen Island Cou nter R eceptacles 12 12 16 71 60 4110 6530 2.90 3.53 2.42 2.94 10 20 15 120 120 14 Basement Counterto Rece tacles Entertainment Area and Kitchennet Li htin 12 12 16 60 65 6530 4110 3.53 2.66 2.94 2.21 12 13 15 15 120 120 14 14 14 12 Guest Room Rece tacles Guest Bathroom Receptacles 12 12 66 31.5 4110 4110 2.31 1.10 1.93 0.92 2.92 2.92 14 15 15 20 120 120 Living Room Receptacles First Floor Microwave 12 12 14 75 68 4110 6530 3.50 3.50 16 20 120 12 Basement Microwave S are 12 14 60 49 6530 3.09 2.57 18 19 15 15 15 15 120 120 120 120 14 14 14 14 14 Guest Room, Bathroom and Closet-G Li htl Laundry Lighting First Floor Refrigerator Basement Refri erator 12 12 12 12 5.2 3.7 12 12 71.5 50 42 4110 4110 4110 4110 1.49 1.54 3.50 2.94 1.24 1.29 2.92 2.45
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
23 15 15 120 120 14 W orksho Rece tacles Dinin Area and Kitchen Li htin 12 12 6.2 92 73 4110 4110 1.07 2.64 0.90 2.20 24 25 15 15 120 120 14 14 Main Bathroom Li hti Dining Area Receptacles 12 12 66 51 4110 4110 1.16 0.60 0.96 0.50 2.99 2.99 27 20 20 120 120 12 12 Countertop Receptacles near the dinin area Counterto Rece tacles near the sink 12 12 16 16 61 61 6530 6530 3.59 3.59 28 20 15 120 120 12 14 Counterto Rece tacles near the door Back Outdoor Rece tacles 12 12 16 61 51 6530 4110 3.59 0.30 2.99 0.25 15 120 14 Ent Outside and Stairwa Li hti 12 3.5 93 4110 1.90 1.58 22 28
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Section 5: Conclusion 29
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
This project, which was done according to the safety standard of the Canadian Electrical Code, uses practical knowledge to fix receptacles, lightings and similar devices. In order to fix these devices, it was necessary to compute various calculations such as voltage drops and service entrance calculations, find overcurrent devices and find specifications for each device installed. This was made possible due to various programs such as AutoCAD, Microsoft Word, Adobe Reader, and Microsoft Excel. There was the possibility for the use of hand tools like screwdrivers, pliers, wire nuts, connectors and so on. The making of this project allowed for the opportunity to develop new skills, and master old ones: 1. ) Learning how to use applications such as AutoCAD to aid in the drawing. 2.) Learning how to calculate voltage drop and service entrance calculations in a practical setting. 3.) Learning how to create schedules in a practical setting. 4.) Learning how to use the Canadian Electrical Code in real life situations. 30
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Section 6: Appendix 31
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Canadian Electrical Code 32
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
CEC RULES 8-200 Single dwellings 1) The calculated load for the service or feeder supplying a single dwelling shall be based on the greater of Item a) or b): a) i) a basic load of 5000 W for the first 90 m 2 of living area; plus ii) an additional 1000 W for each 90 m 2 or portion thereof in excess of 90 m 2 ; plus iii) any electric space- heating loads provided for with a demand factors as permitted in Section 62 plus any air-conditioning loads with a demand factor of 100%, subject to Rule 8-106 4); plus iv) any electric range load provided for as follows: 6000 W for a single range plus 40% of any amount by which the rating of the range exceeds 12 kW; plus v) any electric tankless water heaters or electric water heaters for steamers, swimming pools, hot tubs, or spas with a demand factor of 100%; plus vi) any loads provided for that have a rating in excess of 1500 W, in addition to those outlined in items i) to vi), at A. 25% of the rating of each load, if an electric range has been provided for; or B. 100% of the combined load up to 6000 W, plus 25% of the combined load that exceeds 6000 W, if an electric range has not been provided for; 62-118 Demand factors for service conductors and feeders 3) Where a heating installation in a building for residential occupancy is provided with automatic thermostatic control devices in each room or heated area, the ampacity of service conductors or feeders supplying heating devices only shall be based on the following: a. the first 10 kW of connected heating load at 100% demand factor; plus 33
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
b. the balance of the connected heating load at 75% demand factor. 8-106 Use of Demand factors 3) Where is it known that electric space-heating and air-conditioning loads are installed and will not be used simultaneously, whichever is the greater load shall be used in calculating the demand. 8-110 Determination of areas The living area shall be determined from inside dimensions and include the sum of a. 100% of the area on the ground floor b. 100% of any areas above the ground floor used for living purposes; c. 75% of the area below the ground floor 8-304 Maximum number of outlets per circuit l) There shall be not more than 12 outlets on any 2-wire branch circuit, except as permitted by other Rules of this Code. 2) Such outlets shall be considered to be rated at not less than I A per outlet, except as permitted by Subrule 3). 3) Where the connected load is known, the number of outlets shall be permitted to exceed 12, provided that the load current does not exceed 80% of the rating of the overcurrent device protecting the circuit. 34
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
4) Where fixed multi-outlet assemblies are used, each 1.5 m or fraction thereof of each separate and continuous length shall be counted as one outlet, but in locations where a number of electrical appliances are likely to be used simultaneously, each 300 mm or fraction thereof shall be counted as one outlet. 14-104 Rating of overcurrent l) The rating or setting of overcurrent devices shall not exceed the allowable ampacity of the conductors that they protect, except A a. where a fuse or circuit breaker having a rating or setting of the same value as the ampacity of the conductor is not available, and the maximum calculated or known load is in accordance with the Rules of Section 8, the ratings or settings given in Table 13 shall be permitted to be used within the maximum value of 800 A; b. in the case of equipment wire, flexible cord in sizes Nos. 16, 18, and 20 AWG copper, and tinsel cord, which are considered protected by 15 A overcurrent devices; or c. as provided for by other Rules of this Code. 2) Except as provided for by Subrule l) c), the rating of overcurrent protection shall not exceed a. 15 A for No. 14 AWG copper conductors; b. 20 A for No. 12 AWG copper conductors; c. 30 A for No. 10 AWG copper conductors; d. 15 A for No. 12 AWG aluminum conductors; and e. 25 A for No. 10 AWG aluminum conductors. 35
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
26-652 Branch circuits for residential occupancies Branch circuits for all residential occupancies (including dwelling units and single dwellings) shall meet the following requirements: a. receptacles installed for refrigerators in accordance with Rule 26-724 d) i) shall be supplied by at least one branch circuit that does not supply any other outlets, except a recessed clock receptacle intended for use with an electric clock; b. at least one branch circuit shall be provided solely for receptacles installed in the laundry room or in a space where the complete plumbing is installed to accommodate a washing machine; c. at least one branch circuit shall be provided solely for receptacles installed in the utility room; d. each receptacle installed in a cupboard, wall cabinet, or enclosure for the use of a microwave oven m accordance with Rule 26-720 h) shall be supplied by a branch circuit that does not supply any other outlets, and this circuit shall not be considered as forming part of the circuits required under Rule 26-654 b); e. a separate branch circuit shall be provided solely to supply power to each central vacuum system; f. the ampere rating of the branch circuit wiring supplying receptacles with CSA configuration 5-20R shall be not less than 20 A; and g. a separate branch circuit shall be provided solely to supply power to each receptacle described in Rule 26-720 n). 26-654 Branch circuits for dwelling units Branch circuits for dwelling units (including single dwellings) shall meet the following requirements: 36
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
a. branch circuits from a panelboard installed in accordance with Rule 26-602 shall not be connected to outlets or electrical equipment in any other dwelling unit; b. except as may be permitted by Items c) and d), at least two branch circuits shall be provided for receptacles (5-15R split or 5-20R) installed for kitchen counters of dwelling units in accordance with Rule 26-724 d) iii), iv), and v), and i) no more than two receptacles shall be connected to a branch circuit; and ii) no other outlets shall be connected to these circuits; c. notwithstanding Item b), where the provisions of Rule 26-724 d) iii) require only one receptacle, only one branch circuit need be provided; d. notwithstanding Item b) i), receptacles identified in Rule 26-720 d) shall be permitted to be connected to those receptacles required by Rule 26-724 d) iii), even though the circuit already supplies two receptacles; e. outdoor receptacles readily accessible from ground level and installed in accordance with Rule 26-726 a) shall be supplied from at least one branch circuit dedicated for those outdoor receptacles; and f. at least one branch circuit shall be provided solely for the receptacles in a carport or garage of a single dwelling, except that the luminaires and garage door operator for these areas shall be permitted to be connected to this circuit. 37
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Table Requirements 1: for Receptacle Allocation Room or Area Living room, dining room, family room, bedroom Provide No point along the floor line of a wall may be more than 1.8 m horizontally from a receptacle, including isolated wall spaces 900 mm or longer. Receptacles 5-15R and 5-20R are to be of the tamper-resistant type. For sleeping rooms and facilities, the receptacles must be protected by an arcfault circuit interrupter. One rece tacle for the air conditioner. s ecial outlet CEC Reference Rule 26-724(a) & (c) Hallway No point in a hallway may be more than 4.5 m from a receptacle. Receptacles in rooms off the hallway may be used if the opening to the room from the hallway is not fitt ed with a do or. 26-724(f) Laundry room Rece tacles 5-15R and 5-20R are to be of the tam er-resistant e. One receptacle for the w ashing machine. 26-720(e) At least one a dditional re ceptacle. Recepta cles 5-15R and 5-20R are to be of t he tamper-resistant t ype. The outlet must be protected by a Class A GFCI when located within 1.5 m of a sink or laundry tub. Bathroom One rece tacle for the electric clothes d er. s ecial outlet At least one receptacle, within 1 m of the washbasin and Ground Fault Circuit Interrupter (GFCI) protected. Receptacles 5-15R and 5-20R are to be of the tamper-resistant type. One receptacle for cord-connected hydro-massage bathtub located not less than 300 mm from the floor. Receptacles 5-15R and 5-20R are to be of the tamper- resistant type. The outlet must be protected by a Class A GFCI. s ecial outlet 26-704(f) Kitchen One receptacle for a refrigerator. One receptacle for a gas range if gas piping has been provided. 26-724(d) Counter receptacles such that no point measured along the back of the counter is more than 900 mm horizontally from a receptacle. Counter receptacles may be 15-A, three-conductor split circuit, or 20-A T slot. Any receptacle within 1.5 m of a sink must be protected by a Class A GFCI. Isolated work surfaces 300 mm or more require a receptacle. At least one receptacle for a permanently installed island; 15 A split or 20 A Tslot. At least one receptacle for counter peninsula; 15 A split or 20 A T- slot. At least one receptacle in a dining area forming part of a kitchen. One receptacle for a free-standing gas range installed at such a height that there is not more than 130 mm from the finished floor to the center of the receptacle and must be located in the center of the wall space behind the range. Receptacles 5-15R and 5-20R are to be of the tamper-resistant type. The built-in oven and/or ran e must be direct-connected. One rece tacle for a microwave in its own enclosure. s ecial outlet 26-720 h iii Utility room At least one receptacle. Receptacles 5-15R and 5-20R are to be of the tamper-resistant type. In the utility room, the water pump and water heater require special-purpose outlets. One rece tacle for the electric furnace. s ecial outlet 26-724(a) Unfinished basement areas At least one receptacle. 26-720(e) Balcony, porch, veranda Rece tacles 5-15R and 5-20R are to be of the tam er- resistant At least one receptacle. (GFCI, WP) 26-724(b) 38
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Table Requirements Outdoors Rece tacles 5-15R and 5-20R are to be of the tam er-resistant At least one rece tacle for the use of outdoor a liances. GFCI WP 26-726 a Gara e, car ort Miscellaneous One rece tacle for each s ace. One receptacle for a cord-connected central vacuum if ducting system is installed. Rece tacles 5-15R and 5-20R are to be of the tam er-resistant e. 26-726 b 26-7200) 2: for branch circuits supplying receptacles Room or Area Living room, dining room, family room, hallway, bedroom Provide Maximum of 12 outlets er circuit. CEC Reference Rule 8-304 15 A or 20 A, 120 V, 2-wire branch circuit. One branch circuit runs to the air conditioner. Laundry room, utility room At least one circuit solel for rece tacles in laund rooms. At least one circuit solel for rece tacles in utilit room or areas. 26-652 A separate circuit is provided in the laundry room for the electric clothes dryer. A separate circuit is recommended for the receptacle feeding the sump pump. circuit for the water heater. A separate A se arate circuit is re uired for the central heatin e ui ment. Bathroom No special requirements in CEC. It is recommended that a separate circuit be used for the cord-connected hydro massa e bathtub. Kitchen One circuit for the receptacle for a refrigerator. A receptacle provided for a clock outlet is permitted on this circuit. 26-652 A minimum of two circuits provided for counter receptacles, when more than one counter receptacle is provided. No more than two counter receptacles are permitted on a circuit except that receptacles provided for people with disabilities ma be added. 26-654 One circuit when a receptacle has been supplied for built-in microwave oven. 26-652 There must be a separate branch circuit, sized according to the oven and/or ran e ratin , or one feed for both the built-in oven and/or ran e. Balcony, porch, veranda Outdoors One circuit for a single dwelling unit and accessible from grade level. 15 A or 20 A, 120 V, 2-wire branch circuit. One circuit for rece tacles located outdoors. 26-654 26-654 Garage, carport One circuit for receptacles in garages or carports. The garage lighting and door o ener ma be on the same circuit. 26-654 Miscellaneous One circuit for a cord-connected central vacuum if ducting system is installed. 26-652 39
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Table Requirements 3: for Lighting and Switch Allocation Room or Area Living room, bedroom Provide At least one luminaire controlled by a wall switch or a receptacle controlled by a wall switch. CEC Reference Rule 30-502 30-500 Entrance Stairway A luminaire controlled b a wall switch inside the buildin All stairways must be lighted. A luminaire controlled by a switch at the top and bottom of the stairway when the stairways has four or more risers. If the stairway leads to an unfinished basement that does not have an outside exit a sin le switch at the to of the stairs ma be used. 30-504 Kitchen, dining room, hall, bathroom, vestibule, utility room At least one luminaire controlled by a wall switch. 30-502 Basement One luminaire for each 30m 2 or portion thereof of unfinished basement. The luminaire closest to the stairs must controlled by a switch at the top of the stairways. 30-506 30-508 Stora e room Garage and carport At least one luminaire in the storeroom. At least one luminaire controlled by a wall switch near the doorway. When a wall-mounted or ceiling luminaire that is not located above a space that would be occupied by a car is used, a built-in switch is permitted on the luminaire. 30-510 A carport that is lighted by a luminaire at the entrance to the building does not re quire additional li htin 40
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Table 2 Allowable ampacities for not more than three insulated copper conductors, rated not more than 5000 V and unshielded, in raceway or cable (based on an ambient temperature of 30 o c*) (See Rules 4-004, 8-104, 12-3034, 26-142, 42-008, and 42-016 and Tables 5A, 5C, 19, 39, and 1)3.) Size, AWG or kcmil Allowable ampacity 60 75 90 110 See Note 125 See Note 200 See Note 125 105 15 20 30 40 20 25 35 50 25 30 40 55 25 30 45 65 30 35 45 65 35 40 60 80 55 70 85 95 110 65 85 100 115 130 75 95 115 130 145 80 105 125 145 165 90 115 135 155 175 110 165 190 215 00 000 0000 125 145 165 195 150 175 200 230 170 195 225 260 190 220 255 290 200 235 270 310 245 290 330 380 250 300 350 400 500 215 240 260 280 320 255 285 310 335 380 290 320 350 380 430 320 360 390 425 480 345 385 420 450 510 600 700 750 800 900 350 385 400 410 435 420 475 490 520 475 520 535 555 585 530 580 600 620 655 565 620 640 660 700 1000 1250 1500 1750 2000 455 495 525 545 555 545 590 625 650 665 615 665 705 735 750 690 745 790 820 840 735 col. 1 col. 2 col. 3 Col. 4 col. 5 col. 6 col. 7 41
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Table * See Table 5A for the correction factors to be applied to the values in Columns 2 to 7 for ambient temperatures over 30 o c. t The ampacity of aluminum-sheathed cable is based on the type of insulation used on the copper conductors. (Continued) 13 Rating or setting of overcurrent devices protecting conductors* (See Rules 14-104 and 28-204.) Ampacity of conductor, A Rating or setting permitted, A Ampacity of conductor, A Rating or setting permitted, A 0-15 16-20 21-25 26-30 31-35 36-40 41-45 46-50 51-60 61-70 71-80 81—90 91-100 101-110 15 20 25 30 35 40 45 50 60 70 80 90 100 110 111-125 126-150 151-175 176-200 201-225 226-250 251-300 301-350 351-400 401-450 451-500 501-600 601-700 701-800 125 150 175 200 225 250 300 350 400 450 500 600 700 800 * For general use where not otherwise specifically provided for. 42
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Table 16 Minimum size of field-installed system bonding jumpers and bonding conductors (See Rule 10-614.) Ampere rating or setting of overcurrent device protecting conductor(s), equipment, etc. Allowable ampacity of largest ungrounded conductor or group of conductors. Minimum size of system bonding jumper and bonding conductor Wire Bus Copper, AWG or kcmil Aluminum, AWG or kcmil Copper, mm2 Aluminum, mm2 Not exceeding 20 14 12 2.0 3.5 30 12 10 3.5 5.5 60 10 8 5.5 8.5 100 8 6 8.5 10.5 200 10.5 21.0 300 4 2 21.0 26.5 400 3 1 26.5 33.5 500 2 33.5 42.5 600 1 00 42.5 53.5 800 000 53.5 67.5 1000 0000 67.5 84.0 1200 000 250 84.0 127.0 1600 0000 350 107.0 177.5 2000 250 400 127.5 203.0 2500 350 500 177.5 253.5 3000 400 600 203.0 355.0 4000 500 800 253.5 405.5 5000 700 1000 355.0 507.0 6000 800 1250 405.5 633.5 43
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Appliance Specification 44
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
AIR CONDITIONER MRCOOL Signature Series Heat Pump Package Residential 2_5-Ton 14Seer Central Air Conditioner Overview Specifications Reviews Questions & Answers Compare Product Features CommerciaVResidential Residential Line Set Length (Feet) Condenser Height (Inches) 3682 Liquid Line Diameter ENERGY STAR Certified System Size (Tons) 2.5 CA Residents: Prop 65 Waming(s) A Prop es WARNING(S) Suction Line Diameter Air Flow Direction Horizontal Full Load Amperage Requirement (Amps) 35 BTU Rating 28600 Full Load Voltage Requirement (Volts) 240 Series Name Signature Heat pump Package Quick Connect Fittings Safety Listing ETC safety listing Warranty 10-year limited Condenser Width (Inches) Color/Finish Family Condenser Depth (Inches) 4677 Decibel Rating (Decibels) 78 Condenser Weight (lbs.) 324 Compressor Type Scroll Evaporator Height (Inches) Cooling Stage Single-stage Evaporator Width (Inches) Coil style Fully cased Evaporator Depth (Inches) Phase Single-phase Evaporator Weight (lbs.) 45
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
ELECTRIC RANGE POWER/RATINGS Amp Rating at 208V 46.6A Amp Rating at mov 53.BA KW Rating at 208V 9.7 KW KW Rating at mov 12.8 KW Required Power Supply (amp) 40A 46
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
ELECTRIC FURNACE Winchester 15 KW Mobile Home Downflow Electric Furnace 3.5 Ton for delivery date estimate DEPTH INCHES 23-1/3 (59.27 cm) HEIGHT INCHES 33 (83.82 cm) CONSTRUCTION Galvanized Steel D.O.E. CAPACITY MBH 51 .2 VOLTAGE 240 KILOWATTS (KW) FUEL TYPE 15 IGNITION TYPE Heat Coil WEIGHT LBS 86 (39.09 kg) CFM HIGH 1400 3.5 EFFICIENCY RATING % (AFUE) STAGE 100 LISTING OR CERTIFICATIONS AHRI, ETL COLOR White Downflow LIMITED WARRANTY YEARS 5 MANUFACTURERS PART NUMBER WE30B4D-15 AMPS HIGH 62.50 SPEEDS 5 47
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
WATER PUMP Acquaer I-HP 115 and 230-Volt Cast Iron Shallow Well Jet Pump Inlet Diameter 1 .25 Cord Length (Feet) Water pump Application For shallow wells 25 t. deep or less 7.7 Package Quantity Inlet Connection NPT Package Contents Pump Sub Type Shallow jet pump Power Source Electric Horsepower (HP) Outlet Connection NPT Collection Name NIA Safety Listing CSA safety listing water (GPM) 17 Battery Voltage 12 VOC Warranty Switch Specialty 115 and 230 Outlet Diameter Cast iron Impeller Material Polypropylene 48
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
WATER HEATER A.O. Smith Signature 40-Gallon Tall 6-year Limited 4500-Watt Double Element Electric Water Heater Item #816154 Model #E6-40H45DV Height (Inches) Point of use 61.25 Warranty 6-year limited Insulation Thickness (Inches) 2.0 Installation Location Indoor Commercial/Residential Residential Series Name Signature™ Mobile Home Compatible Element Wpe x Element Wattage (Watts) 4500.0 Rated Storage Capacity 36-Gallon Family Size 3.0 uniform Energy Factor 0.92 Voltage (Volts) 240.0 49
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
ELECTRIC DRYER Electric 50 Room Large Stackable
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
HYDROMASSAGE TUB Cascade 7242 Platinum Series with Hydro & Air Massage — Size: 72" x 42" x 26" - Jets: 38 Total Jets Contact us for details Cascade 72" x 42' Platinum Series Hydro and Air Massage Bath SKU: CACP7242 Categories: 6 Foot, Cascade, Cascade, Cascade, Cascade, Combo Massage, CP. Drop-ln, Rectangle, side, Uncategorized Features: 38 Total Jets Back Massage System with 7 Jets Neck Massage Pillow with 2 Jets Sole Soother Jets AccuMassage Back and Neck Jets Ultra Flow Water Jets Classic Air Jets on Sidewall (2) 3.25 Hydro Power 3-Speed Pumps 1.25 Air Power Variable Speed Heated Air Pump with Pulse and Wave Cycle Quiet Pad Anti-Vibration Mounted Pump Stainless Steel Electric Heater Warm Back Rest Tubing Zone Air Switch On/Off Control for Chromatherapy Air Switch On/Off Control Electronic Variable Speed Air Massage Control Electronic Hydro Clean Water Purity System Hydro Cleanse'" Chromatherapy Lighting Deluxe Cable Drain Deluxe Cushion Pillow EZ Level Base (4) 115V Dedicated 20AMP GFCl-protected Circuits Required EZ ClearÜ Cast Acrylic Alcove or Deck Installation Side Drain 51
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
MICROWAVE OVEN HOME APPUANCES LG COOKING NeoChef Countertop Microwave Oven 52 I -5 cu.ft- Oven Capacity LMc157 5
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Electrical Devices 53
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
BREAKERS Schneider Electric - Square D Single Pole 15 Amp QO Plug-On Circuit Breaker Pole 30 Amp Homeline Plug-On Circuit Breaker Technical Specs Panelbo.rd ln•rior Circut Breaker SeQs Stu-t Qrrent RaMg 277/480" AC Sus Mien* Circuit Breaker Tyr Plug In Wniatwe Schneider Electric - Square D Double Pole 15 Amp 00 Plug-On Circuit Breaker Square D Single Pole 15 Amp QO Combination Arc Fault Pigtail Circuit Breaker Schneider Electric Square D Double Pole 40 Amp QO Plug-On Circuit Breaker Man Circuit Breaker Man Nrnber Of Space RecorMTHjed Erclcsure S c h n e i d e r E l e c t r i c - S q u a r e D D o u b l e 54
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
P o l e 2 0 A m p Q O Plug-On Circuit Breaker Eaton Plug-ln Replacement Br Breaker - 2P IOOA Convertible, Main Lug 400 A 42 Circuit Breakers PANELBOARD Square D QO 200-Amp 30-Spaces 3D-Circuit Main Breaker Plug-On Neutral Load Center Item #622871 Model #Q0130M200PC 55
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
IJL listed for residential, commercial and industrial power distribution Engineered for a quick Plug-on Neutral breaker connection on every' circuit, fewer connections, faster installation and no pigtails frees up gutter space Includes a factory-installed indoor cover Accommodates plug-on secondary surge arrestor (sold separately) Overhead/underground feed Simply by rotating the device before installing Rated 120/240 VAC and 22,000 AIR short circuit current rating Designed with straight-in mains to save expensive cable and time Split branch neutral with terminal screws backed out offering with up to 50% more terminals than I-JL requires increases wiring flexibility saving installation time and simplifies wiring Square D 40-Circuit 30-Space 400-Amp Main Breaker Load Center Item #107297 Model #SU3040D400CN The Square D 400 Amp 30-Space 40-Circuit Combination Meter Socket and Dual Main Breaker Load Center is suitable for use as a combination service entrance device (CSED) and is a ring-type unit It is suitable for underground service applications Accommodates plug-on secondary surge arrestor, and features a Plug-in design for easy installation This CSED is built with a plated, aluminum bus bar that is tested and listed only for Homeline circuit breakers rated 120/240Vac 4 jaw meter socket NEMA type 3R enclosure 56
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Bypass Type-none Designed with straight-In mains to save expensive cable and time Distributed split branch neutral with terminal screws backed out offering with up to 50% more terminals than UL requires increases wiring flexibility saving installation time and simplifies wiring 57
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Leviton Commercial Duplex Receptacle 15 Amp 125v, Gray RECEPTACLES Leviton Decora 20 Ar-np Tamper- Resistant Slim GFCI Receptacle/Outlet With Wall Plate Leviton Decora Duplex USB Charger 3.6A I Tamper Resistant Receptacle 15A 30A Dryer Receptacle 40A Stove Receptacle (14-30R) (14-50R) 58
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Leviton Decora Single Pole Switch, White Leviton Single Pole Switch, White - Leviton SureSlide Universal Slide Dimmer with Preset in White SWITCHES Leviton Decora 3 Way Switch Gray Leviton Framed Toggle 3-Way Switch, White Monte Carlo Fans White 2-1/2 in. Wall Fan Switch Leviton Decora 4fWay 15 Amp Switch, White Leviton 4 Way Switch, Ivory Leviton Lamp holder With Pull Chain Switch 59
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Hampton Bay 6-Light Black LED Fixed Track Square Tube LUMINAIRES PROJECT SOURCE Project Source Round Flush Mount Ceiling Fixtures - LED 12-in - Metal/Acrylic - Oil Format 12 0 x4.45•-2UN Canarm MONTANA 16"H I-light black outdoor wall light with clear glass panels LEADVISION Leadvision Recessed Dimmable Lights - Slim LED - 4in -10 w 60
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
More Options Available southWit-e 12/3 NMD90 75M Romex SIMpulI Electrical Wire - Yellow More Options Available SouthWire 14/3 NMD90 75M Romex SIMpull Electrical Wire - White C O N D U C T O R S More Options Avadable More Options Available Southwire 8/3 NMD9010M Romex SIMpull Electrical Wire - White Southwire 12/2 NMD90 75M Romex SIMpull Electrical Wire - Yellow More Options Available southWire 10/3 NMD90 10M Romex SIMpull Electrical Wire - Orange SIMpulI Southwire Electrical 14/2 NMD90 Wire - 75M WhiteRomex southWire..E.12Cluca.LCa1212Q QQL Southwire AC90 14/2 20M Armoured Cable 61
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
EET 114 Drawing Interpretation S MUST BE DUE ON, 6th Nov 2023 TIME: 03:59am 1. Intro Explain what has been done Methods used 2. Load Estimates Panel Location of Switches 4. Conductors and Over Current Protection Devices Wire Size OCPD in Panel 5. Conclusion 6. Appendixes on all electrical equipment used 7. FWFactor Professional Drawings (to scale, colour, etc) Cover Page Electronically presented (not hand written) Extras Panel schedule Project XO/// e /3 /3 Total out of 60 /3 /3 /3 /3 /3 /3 /3
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help
56
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
  • Access to all documents
  • Unlimited textbook solutions
  • 24/7 expert homework help