7466 2022 05 10 Q2
docx
keyboard_arrow_up
School
Hong Kong Institute of Vocational Education (Tsing Yi) *
*We aren’t endorsed by this school
Course
2469
Subject
Electrical Engineering
Date
Nov 24, 2024
Type
docx
Pages
3
Uploaded by GoodShare
Q2. If a =9, b=9, c=9 An electric power system has 5 identical generators, each has a rating of 70MW and a force outage rate of (0.02+ (a/1000)). The table of its load vs the duration of the load is given as below: Load Demand (MW) Duration of the Load (in hours within a year) 73 2500 100 1950 240+b*5 956 180+c*5 1330 155 1550 300 480 Total number of hours = 8766 Hours (1 year = 365.25 day=365.25%24=8766 hours) (a) Determine the probability of expected loss of load of the power system in the unit of “number of days in 10 years™. (15 marks) (b) What should be the force outage rate of the system, if the probability of expected loss of load of the power system is required to be very close to (but less than) 0.1 days in 10 years? (5 marks)
Qs. If a =9, b=9 Check, whether it is possible to provide a CDT of 0.4 second in the IDMT overcurrent protection systems of the following diagram. If possible, suggest the values of TMS for all the three relays (show the detailed steps of calculations). If not possible, why not possible, and suggest any changes in the protection system design to make it possible (in this case, no detailed re-calculations on your suggested changes, just to give the area and direction of changes). Note: a) All relay is of the same type, and of 5A rating, b) The tripping time equation for the relays is: TMS * 0.14/(PSM°-1). c) For all IDMT relays, the TMS can be any value between 0.05 to 1.0 d) System voltage is 3-phase 380kV, base 3-phase power rating is 300MVA. (15 marks) 3 A - B » C Q AL Ay \AJ o L JVV LUV L_vv CcT CcT cr IDMT Relay | Plug setting | CT ratio Between the 2 points | line reactance per phase (in p.u.) is: A 125% 500/5 Source to A j(0.08+ (a/2000)) B 100% 400/5 Ato B 1(0.04+ (/2000)) C 75% 300/5 B to C 1(0.04+ (b/2000))
Q4. If a =9, b=9, c=9 For the power system shown in Figure Q4, the generator’s rating is 30 MVA and its inertia constant is 2MJoule.sec/elect radian. (a) What is generator’s synchronizing coefficient and frequency of oscillations under small disturbance when its output power is (0.7+(a/100))pu? (7 marks) (b) Find the critical clearing angle to maintain transient stability for the power system, if there is a solid short-circuit 3-phase symmetrical fault at exactly the middle point of the lower transmission line. The generator and the lines are assumed to be lossless. The electric power from generator at stable steady state is (0.7+(a/100))pu just before the fault. Show the detailed steps of calculations. (13 marks) j0.17 §0.17 |E|=1-15 jO.11 j(0.4+(6/100)) H s 10.08 — 1 — —{ — —O infinite O 3¢ et e S X ¢ j(0.3+(c/100)) e 1— —3 L 11— V=1.05/ 2-pole generator : . g j0.17 j0.17 Figure Q4: Power System for Q4 (all values are in pu, and all components are lossless)
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
- Access to all documents
- Unlimited textbook solutions
- 24/7 expert homework help
Related Questions
I:56)
arrow_forward
Please help will like
arrow_forward
32.
The incremental cost characteristics of two
generators delivering a load of 200 MW are as
follows:
dF
= 2.0 + 0.01 P, dP,
dP
dF,
-= 1.6 + 0.02 P,
For economic operation the generators P, and
P, should be
(a) 120 MW and 80 MW
(b) 81 MW and 120 MW
(c) 120 MW and 120 MW
(d) 80 MW and 80 MW
arrow_forward
A generating station has the following daily load cycle:
Time (hours) 0–6
Load (MW) 20
6–10
10–12
12–16
16–20
20-24
25
30
25
35
20
Construct the load curve and find
(i)
(11)
(iii)
(iv)
Maximum demand
Units generated per day
Average load
Load factor
arrow_forward
A generating station has the following daily
load cycle :Time (Hours) 0-6 6–10 10–12
12–16 16–20 20-24 Load (MW) 50 60 70
60 80 50 Draw the load curve and find (i)
maximum demand (ii) units generated per
day (iii) average load and (iv) load factor.
arrow_forward
36ll
3G
1:00
%71
2 523573914...
لم يتم الحفظ بعد
H.W. 2 A generating station has
the following daily load cycle:
Time(Hours) 0-6 6–10
10–12 12-16 16–20
20-24
Load (MW) 40
50
60
50
70
40
Draw the load curve,
load
duration curve and find
1- maximum demand
2- units generated per day
3- average load.
4- load factor.
arrow_forward
A generator operating at 50 Hz delivers 1 p.u. power to an infinite bus through a transmission
circuit in which resistance is ignored. A fault takes place reducing the maximum power
transferable to 0.5 p.u. Where as before the fault, this power was 2.5 p.u. and after the clearance
of the fault, it is 2 p.u. The value of 8
is
max
arrow_forward
Please help will upvote sure
arrow_forward
Explain the types of generators used in wind turbines with a neat diagram and also discuss the grid-connected issues related to it
arrow_forward
Three generators are rated as follows:
G1: 100MVA, 33kV, xg1 = 0.1pu
G2: 150MVA, 32kV, xg2 = 0.08pu
G3: 110MVA, 30kV, xg3 = 0.12pu.
Determine the reactance of the generator corresponding to base values of 200MVA and 35kV
arrow_forward
SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
Related Questions
- I:56)arrow_forwardPlease help will likearrow_forward32. The incremental cost characteristics of two generators delivering a load of 200 MW are as follows: dF = 2.0 + 0.01 P, dP, dP dF, -= 1.6 + 0.02 P, For economic operation the generators P, and P, should be (a) 120 MW and 80 MW (b) 81 MW and 120 MW (c) 120 MW and 120 MW (d) 80 MW and 80 MWarrow_forward
- A generating station has the following daily load cycle: Time (hours) 0–6 Load (MW) 20 6–10 10–12 12–16 16–20 20-24 25 30 25 35 20 Construct the load curve and find (i) (11) (iii) (iv) Maximum demand Units generated per day Average load Load factorarrow_forwardA generating station has the following daily load cycle :Time (Hours) 0-6 6–10 10–12 12–16 16–20 20-24 Load (MW) 50 60 70 60 80 50 Draw the load curve and find (i) maximum demand (ii) units generated per day (iii) average load and (iv) load factor.arrow_forward36ll 3G 1:00 %71 2 523573914... لم يتم الحفظ بعد H.W. 2 A generating station has the following daily load cycle: Time(Hours) 0-6 6–10 10–12 12-16 16–20 20-24 Load (MW) 40 50 60 50 70 40 Draw the load curve, load duration curve and find 1- maximum demand 2- units generated per day 3- average load. 4- load factor.arrow_forward
- A generator operating at 50 Hz delivers 1 p.u. power to an infinite bus through a transmission circuit in which resistance is ignored. A fault takes place reducing the maximum power transferable to 0.5 p.u. Where as before the fault, this power was 2.5 p.u. and after the clearance of the fault, it is 2 p.u. The value of 8 is maxarrow_forwardPlease help will upvote surearrow_forwardExplain the types of generators used in wind turbines with a neat diagram and also discuss the grid-connected issues related to itarrow_forward
arrow_back_ios
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning