7466 2022 05 10 Q2
docx
keyboard_arrow_up
School
Hong Kong Institute of Vocational Education (Tsing Yi) *
*We aren’t endorsed by this school
Course
2469
Subject
Electrical Engineering
Date
Nov 24, 2024
Type
docx
Pages
3
Uploaded by GoodShare
Q2. If a =9, b=9, c=9 An electric power system has 5 identical generators, each has a rating of 70MW and a force outage rate of (0.02+ (a/1000)). The table of its load vs the duration of the load is given as below: Load Demand (MW) Duration of the Load (in hours within a year) 73 2500 100 1950 240+b*5 956 180+c*5 1330 155 1550 300 480 Total number of hours = 8766 Hours (1 year = 365.25 day=365.25%24=8766 hours) (a) Determine the probability of expected loss of load of the power system in the unit of “number of days in 10 years™. (15 marks) (b) What should be the force outage rate of the system, if the probability of expected loss of load of the power system is required to be very close to (but less than) 0.1 days in 10 years? (5 marks)
Qs. If a =9, b=9 Check, whether it is possible to provide a CDT of 0.4 second in the IDMT overcurrent protection systems of the following diagram. If possible, suggest the values of TMS for all the three relays (show the detailed steps of calculations). If not possible, why not possible, and suggest any changes in the protection system design to make it possible (in this case, no detailed re-calculations on your suggested changes, just to give the area and direction of changes). Note: a) All relay is of the same type, and of 5A rating, b) The tripping time equation for the relays is: TMS * 0.14/(PSM°-1). c) For all IDMT relays, the TMS can be any value between 0.05 to 1.0 d) System voltage is 3-phase 380kV, base 3-phase power rating is 300MVA. (15 marks) 3 A - B » C Q AL Ay \AJ o L JVV LUV L_vv CcT CcT cr IDMT Relay | Plug setting | CT ratio Between the 2 points | line reactance per phase (in p.u.) is: A 125% 500/5 Source to A j(0.08+ (a/2000)) B 100% 400/5 Ato B 1(0.04+ (/2000)) C 75% 300/5 B to C 1(0.04+ (b/2000))
Q4. If a =9, b=9, c=9 For the power system shown in Figure Q4, the generator’s rating is 30 MVA and its inertia constant is 2MJoule.sec/elect radian. (a) What is generator’s synchronizing coefficient and frequency of oscillations under small disturbance when its output power is (0.7+(a/100))pu? (7 marks) (b) Find the critical clearing angle to maintain transient stability for the power system, if there is a solid short-circuit 3-phase symmetrical fault at exactly the middle point of the lower transmission line. The generator and the lines are assumed to be lossless. The electric power from generator at stable steady state is (0.7+(a/100))pu just before the fault. Show the detailed steps of calculations. (13 marks) j0.17 §0.17 |E|=1-15 jO.11 j(0.4+(6/100)) H s 10.08 — 1 — —{ — —O infinite O 3¢ et e S X ¢ j(0.3+(c/100)) e 1— —3 L 11— V=1.05/ 2-pole generator : . g j0.17 j0.17 Figure Q4: Power System for Q4 (all values are in pu, and all components are lossless)
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
- Access to all documents
- Unlimited textbook solutions
- 24/7 expert homework help
Related Questions
I:56)
arrow_forward
A 12 V generator has an internal resistance of 0.05 ohm. Two loads are
connected in parallel to its terminals, one drawing a 12 A current and the other
dissipating energy at the rate of 200 W. What is the terminal voltage of the
generator with this load? Ans. 0.82 volts
arrow_forward
12th sum Please solve me
arrow_forward
What will be the value of the twiddle factor:
W42
arrow_forward
Three generators are rated as follows:
G1: 100MVA, 33kV, xg1 = 0.1pu
G2: 150MVA, 32kV, xg2 = 0.08pu
G3: 110MVA, 30kV, xg3 = 0.12pu.
Determine the reactance of the generator corresponding to base values of 200MVA and 35kV
arrow_forward
PA 500 V de generator supplies a load 800 A at point A through 0.025 2
distributor and a load of 500 A at point B. Points A and B are joined by 0.03 Q.
Determine the current between
and B.
A
800 A
0.025N
500 V
0.032
0.022
500 A
P2- A two wire distributor 500 m long is loaded as shown below. The maximum
voltage drop allowed is 5% of the supply voltage. Calculate the cross sectional area
of the conductor to be used. P=1/50 Q/m/mm2.
150m
100m
100m
150m
arrow_forward
A d.c. serier generator, having an external characteristic which is a straight
line through zero to 50 V 200 A is connected as a booster between a station bus bar and a feeder
of 0.3 ohm resistane. Calculate the voltage difference between the station bus-bar and the far end
of the feeder qa current of (i) 200 A and (ii) 50 A.
arrow_forward
(Q1b) A separately excited de generator has a no-load voltage of 100 V. We increase the excitation
current by 10%. What voltage would we measure in the terminals?
(a) 100 V,
(b) 107 V,
(c) 110 V,
(d) 113 V
arrow_forward
SEE MORE QUESTIONS
Recommended textbooks for you

Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
Related Questions
- I:56)arrow_forwardA 12 V generator has an internal resistance of 0.05 ohm. Two loads are connected in parallel to its terminals, one drawing a 12 A current and the other dissipating energy at the rate of 200 W. What is the terminal voltage of the generator with this load? Ans. 0.82 voltsarrow_forward12th sum Please solve mearrow_forward
- What will be the value of the twiddle factor: W42arrow_forwardThree generators are rated as follows: G1: 100MVA, 33kV, xg1 = 0.1pu G2: 150MVA, 32kV, xg2 = 0.08pu G3: 110MVA, 30kV, xg3 = 0.12pu. Determine the reactance of the generator corresponding to base values of 200MVA and 35kVarrow_forwardPA 500 V de generator supplies a load 800 A at point A through 0.025 2 distributor and a load of 500 A at point B. Points A and B are joined by 0.03 Q. Determine the current between and B. A 800 A 0.025N 500 V 0.032 0.022 500 A P2- A two wire distributor 500 m long is loaded as shown below. The maximum voltage drop allowed is 5% of the supply voltage. Calculate the cross sectional area of the conductor to be used. P=1/50 Q/m/mm2. 150m 100m 100m 150marrow_forward
- A d.c. serier generator, having an external characteristic which is a straight line through zero to 50 V 200 A is connected as a booster between a station bus bar and a feeder of 0.3 ohm resistane. Calculate the voltage difference between the station bus-bar and the far end of the feeder qa current of (i) 200 A and (ii) 50 A.arrow_forward(Q1b) A separately excited de generator has a no-load voltage of 100 V. We increase the excitation current by 10%. What voltage would we measure in the terminals? (a) 100 V, (b) 107 V, (c) 110 V, (d) 113 Varrow_forward
arrow_back_ios
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning

Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning