ELECTRICAL WIRING:RESIDENTAL-6 PLANS
ELECTRICAL WIRING:RESIDENTAL-6 PLANS
18th Edition
ISBN: 9781305098329
Author: MULLIN
Publisher: CENGAGE L
bartleby

Concept explainers

bartleby

Videos

Textbook Question
Book Icon
Chapter 8, Problem 14R

The following problems pertain to luminaires in clothes closets.

  1. a. Does the Code permit bare incandescent lamps to be installed in porcelain key-less or porcelain pull-chain lampholders? ________________
  2. b. Does the Code permit bare fluorescent lamp luminaires to be installed? ________________
  3. c. Does the Code permit pendant lampholders to be installed? ________________
  4. d. What is the minimum clearance from the storage area to surface-mounted incandescent luminaires? ________________
  5. e. What is the minimum clearance from the storage area to surface-mounted fluorescent luminaires? ________________
  6. f. What is the minimum distance between recessed incandescent or recessed fluorescent luminaires and the storage area? ________________
  7. g. Define the “storage area.”

    ______________________________________

    ______________________________________

    ______________________________________

    ______________________________________

    ______________________________________

    ______________________________________

  8. h. If a clothes hanging rod is installed where there is access from both sides, such as might be found in a large walk-in clothes closet, define the storage area under that rod.

    ___________________________________

    ___________________________________

a.

Expert Solution
Check Mark
To determine

Find whether the code permits to install bare incandescent lamps in porcelain keyless or porcelain pull-chain lamp holders.

Answer to Problem 14R

No, the code does not permit to install bare incandescent lamps in porcelain keyless or porcelain pull-chain lamp holders.

Explanation of Solution

Discussion:

The National Electrical Code committee develops NEC - the standard electrical code, and the main objective for the origin of the code is to protect and safeguard people and elements from the electrical hazards. The codes for defining clothes closet luminaires are explained in an article NEC 410.16.

According to an article NEC 410.16(B), the incandescent luminaires with fully open or partially enclosed lamps and the pendant luminaires or pendant lamp holders are not permitted to be installed in a closet.

Therefore, the bare incandescent lamp that is an uncovered lamp is not permitted to be installed in a closet.

Conclusion:

Thus, the code does not permit to install bare incandescent lamps in porcelain keyless or porcelain pull-chain lamp holders.

b.

Expert Solution
Check Mark
To determine

Find whether the code permits to install bare fluorescent lamp luminaires in a closet.

Answer to Problem 14R

Yes, the code permits to install bare fluorescent lamp luminaires in a closet.

Explanation of Solution

Discussion:

According to an article NEC 410.16(A)(2), the recessed fluorescent luminaires or surface-mounted luminaires are permitted to be installed in a closet.

Therefore, the bare fluorescent lamp luminaires, which are uncovered lamps, are permitted to be installed in a closet.

Conclusion:

Thus, the code permits to install bare fluorescent lamp luminaires in a closet.

c.

Expert Solution
Check Mark
To determine

Find whether the code permits to install pendant lamp holders in a closet.

Answer to Problem 14R

No, the code does not permit to install pendant lamp holders in a closet.

Explanation of Solution

Discussion:

According to an article NEC 410.16(B), the incandescent luminaires with fully open or partially enclosed lamps and the pendant luminaires or pendant lamp holders are not permitted to be installed in a closet.

Conclusion:

Thus, the code does not permit to install pendant lamp holders in a closet.

d.

Expert Solution
Check Mark
To determine

Find the minimum clearance distance from the storage area to surface-mounted incandescent luminaires.

Answer to Problem 14R

The minimum clearance distance from the storage area to surface-mounted incandescent luminaires is 12in.(300mm)_.

Explanation of Solution

Discussion:

According to an article NEC 410.16(C)(1), the minimum clearance distance between surface-mounted incandescent or LED luminaires with fully enclosed light source that is permitted to be installed on the wall either above the ceiling or the door and the nearest point of a closet space is 300mm(12in).

Conclusion:

Thus, minimum clearance distance from the storage area to surface-mounted incandescent luminaires is 12in.(300mm)_.

e.

Expert Solution
Check Mark
To determine

Find the minimum clearance distance from the storage area to surface-mounted fluorescent luminaires.

Answer to Problem 14R

The minimum clearance distance from the storage area to surface-mounted fluorescent luminaires is 6in.(150mm)_.

Explanation of Solution

Discussion:

According to an article NEC 410.16(C)(2), the minimum clearance distance between surface-mounted fluorescent luminaires, which are permitted to be installed on the wall either above the ceiling or the door and the nearest point of a closet space, is 150mm(6in.).

Conclusion:

Thus, minimum clearance distance from the storage area to surface-mounted fluorescent luminaires is 6in.(150mm)_.

f.

Expert Solution
Check Mark
To determine

Find the minimum clearance distance between the storage area and recessed incandescent luminaires or fluorescent luminaires.

Answer to Problem 14R

The minimum clearance distance between the storage area and recessed incandescent luminaires or fluorescent luminaires is 6in.(150mm)_.

Explanation of Solution

Discussion:

According to an article NEC 410.16(C)(3), the minimum clearance distance between recessed incandescent luminaires or LED luminaires with fully enclosed light source that is permitted to be installed on the wall above the ceiling or the door and the nearest point of a closet space is 150mm(6in).

Conclusion:

Thus, minimum clearance distance between the storage area and recessed incandescent luminaires or fluorescent luminaires is 6in.(150mm)_.

g.

Expert Solution
Check Mark
To determine

Define the term “storage area”.

Explanation of Solution

Discussion:

According to an article NEC 410.2, the volume is bounded by the back and sides of the closet walls and the planes that extend from the closet floor in vertical to the height of 1.8m(6ft) or to the highest clothes hanging rod, and it is parallel to the walls at the horizontal distance of 600mm(24in.) from the back and sides of the closet walls, and it continues in vertical to the closet ceiling that is parallel to the walls at horizontal distance of 300mm(12in.) or the shelf width.

Conclusion:

Thus, the term “storage area” is defined.

h.

Expert Solution
Check Mark
To determine

Find the storage area space under the clothes hanging rod.

Answer to Problem 14R

The storage area space under the clothes hanging rod is 12in.(300mm)_.

Explanation of Solution

Discussion:

According to an article NEC 410.2, the closet can provide access to both sides of the hanging rod; the space can include the volume that is below the highest rod and extends 300mm(12in.) on either side of the hanging rod on a plane that is horizontal to the floor that extends the entire length of the hanging rod.

Conclusion:

Thus, storage area space under the clothes hanging rod is 12in.(300mm)_.

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
If a recessed  luminary without an integral junction boxes installed what extra wiring must be provided
All recessed incandescent luminaires must be equipped with factory - installed terminal protection, unless the luminaire is identified for use and installed in____.a. copper b. Aluminum c. Stainless steel d. Poured concrete
1. A14/2 type copper used for a general lighting branch circuit.                                                Ampacity:______________              Maximum Fuse or Circuit Breakers Sizes:________________      2.Three 8 AWG copper conductors with THHN insulation Installed in garage in electrical metallic tubing (EMT). The ambient temperature in the garage can reach as high as 110'F. All termination points for this circuit are rated 60'C.                            Ampacity:______________                  Maximum Fuse or Circuit Breakers Sizes:________________ 3.Four 4 AWG copper conductor with THWN insulation imstalled in EMT in a basement. All termination points are rated at 60'C.                                 Ampacity:______________                  Maximum Fuse or Circuit Breakers Sizes:________________  4. An 8/3 Type UF copper cable installed underground from a house to a detached garage to feed a 120/240-volt subpanel. All termination points are rated at 60'C.…

Additional Engineering Textbook Solutions

Find more solutions based on key concepts
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
What is an electric furnace and how does it work?; Author: Fire & Ice Heating and Air Conditioning Inc;https://www.youtube.com/watch?v=wjAWecPGi0M;License: Standard Youtube License