The time required to cool the truck from
Answer to Problem 142RP
The time required to cool the truck from
Explanation of Solution
Determine the mass of the air in the truck.
Here, the density of air is
Determine the amount of heat removed from the truck.
Here, the specific heat at the average temperature is
Determine the average temperature in the truck during precooling.
Determine the average rate of heat gain by transmission.
Here, the rate of transmission heat gain occurs is
Determine the time required to cool the truck.
Conclusion:
From the Table A-2, “Ideal-gas specific heats of various common gases” to obtain value of density of air and the specific heat at the average temperature of
Substitute
Substitute 116 kg for
Substitute
Substitute
Substitute 2320 kJ for
Thus, the time required to cool the truck from
Want to see more full solutions like this?
Chapter 6 Solutions
Thermodynamics: An Engineering Approach
- The heat removal rate from a refrigerated space is 7.2 kW and the power input to the compressor is 1.8 kW. The coefficient of performance (COP) of the refrigerator isarrow_forwardDetermine the COP (coefficient of performance) of a heat pump if the rate of heat rejected is 360 kJ/min and power supplied is 2 kW.arrow_forwardAn air-conditioning system is used to maintain a house at 70°F when the temperature outside is 100°F. The house is gaining heat through the walls and the windows at a rate of 800 Btu/min, and the heat generation rate within the house from people, lights, and appliances amounts to 100 Btu/min. Determine the minimum power input required for this airconditioning system.arrow_forward
- A water fountain is designed to cool water initially at 22.8∘C to a cool 7.7∘C at an average rate of 47 L/hr. It is expected that the water reservoir will absorb 46 W of heat from the surroudings. The refrigeration system has a COP of 1.79. (Assume the water has a constant specific heat.) What is the rate of heat absorption for this water fountain?arrow_forwardThe heat removal rate from a refrigerated space and the power input to the compressor are 8.5kW and 1.7 respectively. The coefficient of performance of the refrigerantarrow_forwardA heat pump can use a maximum of 2 kW power for maintaining a house at 20°C during winter. The rate of heat transfer from the roof and walls is 3000 kJ/h per degree temperature difference between inside and outside. The coefficient of performance is 25% of a reversible heat pump. Determine the minimum outside temperature for which the heat pump can meet the heating requirements of the house.arrow_forward
- A household refrigerator draws 113.9 W of electricity in order to keep its refrigerated compartment at a steady 4.7 ºC; the insulation of the compartment is such that heat passes from the room to the refrigerated compartment at 53.9 kJ per minute. Rejected heat is dumped to the room in which the refrigerator is placed. By comparison to the coefficient of performance for an ideal refrigerator, determine the maximum room temperature in which the refrigerator could operate. Give your answer in ºC to 1 decimal place.arrow_forwardDuring winter, a mechanical heat pump is turned on to supply heat to a house, which is maintained at 18°C. The wall of this house is not perfectly insulated and estimated to have heat loss at a rate of 140,000 kJ/h. The house has electrical appliances that are always turn on, and generate heat at a rate of 27,000 kJ/h. Assume that the mechanical heat pump is reversible and the outdoor temperature is 2°C. List the necessary assumption, sketch the appropriate schematic to visualize the process and calculate the coefficient of performance (COP) for this mechanical heat pump.[Semasa musim sejuk, suatuarrow_forwardDuring winter, a mechanical heat pump is turned on to supply heat to a house, which is maintained at 18°C. The wall of this house is not perfectly insulated and estimated to have heat loss at a rate of 140,000 kJ/h. The house has electrical appliances that are always turn on, and generate heat at a rate of 27,000 kJ/h. Assume that the mechanical heat pump is reversible and the outdoor temperature is 2°C. List the necessary assumption, sketch the appropriate schematic to visualize the process and calculate the coefficient of performance (COP) for this mechanical heat pump.arrow_forward
- Define coefficient of performance (COP). The food compartment of a refrigerator as shown in figure is maintained at 4 °C by removing heat from it at a rate of 360 kJ/min. If the required power input to the refrigeration is 2 kW, determine the coefficient of performance of the refrigerator. Kitchen R QH QL= net,in = 2 kW = 360 kJ/min Food compartment 4°Carrow_forwardA cooling machine operates in an environment with a temperature of 23 ° C and gives 210 kJ of heat per minute to this environment. The performance coefficient of the refrigerator is 4.5. Find the required power (in kW) to operate this cooling machine and the lowest temperature inside the cooling machine.arrow_forwardQ 1- A Carnot refrigerator operates in a room in which the temperature is 22°C and consumes 2 kW of power when operating. If the food compartment of the refrigerator is to be maintained at 3°C, determine the rate of heat removal from the food compartment.arrow_forward
- Elements Of ElectromagneticsMechanical EngineeringISBN:9780190698614Author:Sadiku, Matthew N. O.Publisher:Oxford University PressMechanics of Materials (10th Edition)Mechanical EngineeringISBN:9780134319650Author:Russell C. HibbelerPublisher:PEARSONThermodynamics: An Engineering ApproachMechanical EngineeringISBN:9781259822674Author:Yunus A. Cengel Dr., Michael A. BolesPublisher:McGraw-Hill Education
- Control Systems EngineeringMechanical EngineeringISBN:9781118170519Author:Norman S. NisePublisher:WILEYMechanics of Materials (MindTap Course List)Mechanical EngineeringISBN:9781337093347Author:Barry J. Goodno, James M. GerePublisher:Cengage LearningEngineering Mechanics: StaticsMechanical EngineeringISBN:9781118807330Author:James L. Meriam, L. G. Kraige, J. N. BoltonPublisher:WILEY