EBK ELECTRICAL WIRING RESIDENTIAL
19th Edition
ISBN: 9781337516549
Author: Simmons
Publisher: CENGAGE LEARNING - CONSIGNMENT
expand_more
expand_more
format_list_bulleted
Concept explainers
Textbook Question
Chapter 24, Problem 8R
If you use 600-volt rated conductors for Class 2 wiring, does the Code permit pulling these conductors through the same raceway as the power conductors? (Yes) (No) (Circle the correct answer.) Give the NEC section number. ____________
Expert Solution & Answer
Want to see the full answer?
Check out a sample textbook solutionStudents have asked these similar questions
9. How is equipment containing ungrounded electrical systems required to be marked? A. With green wiresB. With a sign reading "Caution: Ungrounded System Operating at _______ Volts Between Conductors" C. With a red X
D. With a sign reading "Danger: Do Not Touch Ungrounded System, Operating at _______ Volts"
of p
o How many conductors enter the ceiling fan/light wall box?
Switch ond out let boxes
s tirst
10. What type and size of box may be used for the ceiling fan/light wall box?.
11. What type of covers are used with 4 in. square outlet boxes?
12. a. Does the circuit for the Master Bedroom have a grounded circuit conductor?
b. Does it have an equipment grounding conductor?
c. Explain the difference between a "grounded" conductor and an "equipment
grounding" conductor.
13. Approximately how many feet (meters) of 2-wire cable and 3-wire cable are needed to
ft
complete the circuit supplying the Master Bedroom? Two-wire cable:
ft (-
m).
m). Three-wire cable:
14. If the cable is laid in notches in the corner studs, what protection for the cable must be
provided?
15. How high are the receptacles mounted above the finished floor in this bedroom?
16. Approximately how far from the bedroom door is the first receptacle mounted? (See
the plans.)
17. What is the distance from the finished floor to…
A means shall be provided in each metal box over 100 cubic inches for the connection of an equipment grounding conductor. The means shall be permitted to be ______.
a tapped hole
the cover screw
III. a screw used to mount the box
(a.) I only (c.) I & II only (b.) II only (d.) I, II or III
Chapter 24 Solutions
EBK ELECTRICAL WIRING RESIDENTIAL
Ch. 24 - Prob. 1RCh. 24 - Prob. 2RCh. 24 - Prob. 3RCh. 24 - In a home, the low-voltage wiring between the...Ch. 24 - Prob. 5RCh. 24 - The nameplate on a transformer will indicate...Ch. 24 - If Class 2 conductors are insulated for 150 volts,...Ch. 24 - If you use 600-volt rated conductors for Class 2...Ch. 24 - The NEC is very strict about securing anything to...Ch. 24 - Does the Code permit attaching the low-voltage...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- The NEC requires that a(n)_______ be installed at each conductor splice or connection point? A. insulated wire connector B. grounding electrode conductor (ground wire) C. receptacle or junction box D. A, B, and C E. none of thesearrow_forwardEquipment Grounding 10. Which of the following statements about ground faults is true?A. They usually occur between any grounded circuit conductor and the equipment grounding conductor. B. They're often normal and typically intentional.C. They can't result from human error.D. They can happen if a conductive tool is dropped in an energized equipment's electrical enclosure.arrow_forwardConductors other than service conductors must not be installed in the same____. A. Service raceway B. Service cable C. Enclosure D. A or Barrow_forward
- 12.a. FMC and LFMC wiring methods are permitted to be used for service-entrance conductors in lengths ofup toA. 12 feet.B. 9 feet.C. 6 feet.D. 3 feet. 12.b. The NEC states that service-drop conductors with voltage limited to 300 volts to ground shall have aminimum of _______ feet vertical clearance from final grade over residential property, driveways, andthose commercial areas not subject to truck traffic.A. 12B. 20C. 15D. 18arrow_forwardA ____shall be used to connect the equipment grounding conductors, the service equipment enclosures, and where the system is grounded, the grounded service conductor to the grounding electrode. (a.) bus bar ( b.) 5/8” ground rod (c.) neutral conductor (d.) grounding electrode cond. For equipment rated 1200 amperes or more 600 volts or less, and over 6 feet wide, containing overcurrent devices, switching devices, or control devices, there shall be one entrance not less than ____inches wide and 6 ½ feet high at each end. (a.) 24 (b.) 36 (c.) 30 (d.) 48 When calculating the conductor fill for strut-type channel raceway with internal joiners, the raceway shall be permitted to be filled to _____% of the cross-sectional area. (a.) 20 ( c.) 30 (b.) 25 (d.) 40arrow_forward11. Specific rules apply for the installation of _______, but no identification requirements for them exists.A. grounding electrode conductorsB. grounding electrodes.C. main bonding jumpers.D. equipment grounding conductors.arrow_forward
- When a three-conductor multi-wire circuit is used in place of two separate branch circuits to supply split-wired receptacles, the grounded (neutral) conductor is required to be ____. A. durably markedB. pigtailed so that its continuity does not depend on the presence of a wiring deviceC. connected to the white or silver-colored receptacle binding screwD. both b and carrow_forwardA(n) _________ is a reliable conductor used to ensure the required electrical conductivity between metal parts required to be electrically connected. a) Equipment bonding jumper b) Bonding conductor of jumper c) Main bonding jumper d) Equipment grounding conductorarrow_forwardequipment grounding 1. The only exception to the need for all information technology equipment to be satisfactorily grounded is where the equipment is A. DC powered.B. backup generator powered. C. double-insulated.D. isolated equipment. 2. Which section of the National Electrical Code lists sizing requirements for wire-type equipment grounding conductors? A. 250.66 B. 250.118 C. 250.4 D. 250.122arrow_forward
- If a grounding electrode conductor is connected at the first system disconnecting means or overcurrent device, the bonding jumper is sized the same as the ____. Select one: A. EQUIPMENT BONDING JUMPER B. POSITIVE CONDUCTOR C. SUPPLY-SIDE BONDING JUMPER D. NEUTRAL CONDUCTORarrow_forward- Loads, Service, and Overcurrent Protection 6.a. The general lighting load is based on a _______ per square foot basis.A. kilowattB. number of circuitsC. volt-ampereD. general illumination6.b. What's the primary disadvantage of using copper conductors?A. AvailabilityB. WeightC. CostD. Durabilityarrow_forwardThe wording that I am running into with questions such as "The number of conductors required to be installed between three-way and four-way switches is " is confusing. The text is not expalining this in a way that I am understanding anything other than grounding conductor, which is optional unless I am using a metal box. So what type of "conductor" is beng discussed?arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Types of House Wiring - Types of Electrical Wiring - Electrical Wiring; Author: Learning Engineering;https://www.youtube.com/watch?v=A5P-buWX-dA;License: Standard Youtube License