Atmospheric air enters an air-conditioning system at 30°C and 70 percent relative humidity with a volume flow rate of 4 m3/min and is cooled to 20°C and 20 percent relative humidity at a pressure of 1 atm. The system uses refrigerant-134a as the cooling fluid that enters the cooling section at 350 kPa with a quality of 20 percent and leaves as a saturated vapor. Show the process on the psychrometric chart. What is the heat transfer from the air to the cooling coils, in kW? If any water is condensed from the air, how much water will be condensed from the atmospheric air per min? Determine the mass flow rate of the refrigerant, in kg/min.
FIGURE P14–132
Show the process on the psychrometric chart; find the heat transfer from the air to the cooling coils, how much water will be condensed from the atmospheric air per min and the mass flow rate of the refrigerant.
Answer to Problem 132RP
The process on the psychrometric chart is shown below in Figure (1), the heat transfer from the air to the cooling coils is
Explanation of Solution
As the process is a steady flow and thus the mass flow rate of dry air remains constant during the entire process.
Here, the mass flow rate of air at inlet is
Express the mass flow rate of dry air.
Here, volume flow rate at inlet is
Express the mass flow rate of vapor at inlet.
Here, specific humidity at state 1 is
Express the mass flow rate of vapor at exit.
Here, specific humidity at state 2 is
Express the rate of condensation of water.
Express the enthalpy of condensate water.
Here, enthalpy of saturation liquid at temperature of
Express the rate required heat transfer rate from the atmospheric air to the evaporator fluid from an energy balance on the control volume.
Here, enthalpy at state 1 and 2 is
Express enthalpy of refrigerant at inlet.
Here, quality of refrigerant at inlet is
Express enthalpy of refrigerant at exit.
Here, quality of refrigerant at exit is
Express the mass flow rate of the refrigerant.
Here, enthalpy of refrigerant at inlet and exit is
Conclusion:
Show the psychrometric diagram as in Figure (1).
Hence, the psychrometric diagram is shown in Figure (1).
Refer Figure A-31, “psychometric chart at
Refer Figure A-31, “psychometric chart at
Substitute
Substitute
Substitute
Substitute
Hence, the amount of water condensed from the atmospheric air per min is
Refer Table A-4, “saturated water-temperature table”, and write the enthalpy of condensate water at temperature of
Here, enthalpy of saturation liquid is
Substitute
Substitute
Hence, the heat transfer from the air to the cooling coils is
Refer Table A-12, saturated refrigerant-134a-presure table”, and write enthalpy of saturation liquid at pressure of
Write the formula of interpolation method of two variables.
Here, the variables denote by x and y pressure and enthalpy of saturation liquid respectively.
Show the enthalpy of saturation liquid corresponding to pressure as in Table (1).
Pressure |
Enthalpy of saturation liquid |
320 | 55.14 |
350 | |
360 | 59.70 |
Substitute
Thus, the enthalpy of saturation liquid at pressure of
Refer Table A-12, saturated refrigerant-134a-presure table”, and write enthalpy of saturation vapor at pressure of
Show the enthalpy of saturation vapor corresponding to pressure as in Table (2).
Pressure |
Enthalpy of saturation liquid |
320 | 251.93 |
350 | |
360 | 253.86 |
Use excels and tabulates the values form Table (2) in Equation (X) to get,
Substitute
Substitute
Substitute
Hence, the mass flow rate of the refrigerant is
Want to see more full solutions like this?
Chapter 14 Solutions
THERMODYNAMICS LLF W/ CONNECT ACCESS
- P=19 Moist air goes into air-conditioning unit at a degree-30 C and 70% relative humidity, and it is cooled to 20-degree C and 20% relative humidity at a constant pressure of 1.01325 bar. The mass flow rate of dry air is mda=63 kg/s The unit applies refrigerant R-134a as the cooling fluid that enters inside the tubes of the cooling coil at 3.6 bar with a quality of 0.2 and leaves as a saturated vapor at the same pressure of 3.6 bar. Use the psychometric chart to determine: a) Mass flow rate of condensed water in kg/s b) The heat transfer rate from the air to the cooling coil in kW (Use the psychometric chart) c) The mass flow rate of R-134a that is needed in kg/sarrow_forwardA winter air-conditioning system adds for humidification 0.0025 kg/s of saturated steam at 100 kPa pressure to an airflow of 0.36 kg/s. The air is initially at a temperature of 15°C with a relative humidity of 20 percent. The barometric pressure is 90 kPaa. What is the dry temperature of the air leaving the humidifier °C?arrow_forwardi was trying to understand and studying thermodynamics course but this example had seen pretty hard to me. thanks to the person who can explain the solution of that example to me.arrow_forward
- Using a psychrometric diagram, describe the heating and humidification process from the following data. Initially the air was at a dry bulb temperature (DBT) of 40 ° C and RH60%. The air is heated to DBT 90 ° C. The heated air is then flowed through a humidifier to increase the RH to 25%. For this process, calculate, a. Change in absolute humidity of air from initial to final conditions = kg water / kg air). b. The change in air enthalpy from initial to final conditions. = (kj / kg air)arrow_forwardAn air-conditioning system operates at a total pressure of 1 atm and consists of a heating section and an evaporative cooler. Air enters the heating section at 15OC and 55 percent relative humidity at a rate of 30 m3 /min, and it leaves the evaporative cooler at 25OC and 45 percent relatively humidity. Determine the TOR.arrow_forwardMoist air at 32 degrees Cdb and relative humidity of 60% enter a refrigeration system with a flow rate of 90 kg/min. Saturated air at 15 degrees Cdb leaves the system. Calculate the heat and moisture removed in kW and kg/s respectively.arrow_forward
- An air conditioned space is to be supplied with 300 cmm of air at 20°C dry bulb and 40% relative humidity. Unconditioned air from atmosphere at 32°C dry bulb and 28°C dew point is supplied to the dehumidifier coils, from where the same passes on to a heating coil before entering the conditioned space. Determine the cooling required. Solve the problem both from first principles and with Psychrometric chart.arrow_forward1. In the process of air conditioning in a humidifier, the air at a dry bulb temperature of 20 °C and 25% RH increases its RH to 40%. Determine the amount of moisture added in the humidifier per kg of dry air. = (kg water/kg air). 2. The air has a dry bulb temperature of 34 °C and a wet bulb temperature of 22°C. The liquid is heated in a heater so that the dry bulb temperature increases to 80 °C. Then the air is passed through the corn kernels to dry. The air coming out of the corn kernels is at bulb temperature. dry 55 °C Then this air is passed to the dehumidifier to reduce its RH to 10%. Draw the course of the air change process on a psychrometric diagram. The rate of air flow through the corn kernels and dehumidifier is 4.0 m/s and the cross-sectional diameter of the pile is 0.7 m. a) Determine the amount of water content lost from the pile of corn kernels (in grams of water/second) b) Determine the amount of water content lost from the air when passing through the…arrow_forwardUse the concept of evaporative cooling to explain how air’s relative humidity is measured using a sling psychrometerarrow_forward
- Saturated steam at standard atmospheric pressure is injected into a passing air stream in an amount sufficient to raise the absolute humidity from 0.0057 to 0.0143 kg w.v./kg d.a. If the air enters the humidifier at 21°C DBT, deter- mine its leaving state.arrow_forward6-Prove that the enthalpy of the humid air remains constant along a wet bulb temperature line on the psychrometric chartarrow_forwardQI: An air conditioning system is used to keep indoor condition of 24°C and 50% relative humidity inside a space as shown in Figure 1. An amount of 75% of returned air is mixed with 25% fresh ambient air at 40°C and 40% relative humidity before entering to the air filter. The air is cooled though the air cooling coil of surface effective temperature (apparatus dew point temperature) equals to 10°C and bypass factor is 0.2. Find the following: a. State of air after mixing (point m). b. State of air at coil outlet (point c). c. Sketch the process on the psychometric chart. d. Sensible heat factor of the space. space exhaust (25%) cooling coil filter fan m fresh air (25%) Figure 1arrow_forward
- Elements Of ElectromagneticsMechanical EngineeringISBN:9780190698614Author:Sadiku, Matthew N. O.Publisher:Oxford University PressMechanics of Materials (10th Edition)Mechanical EngineeringISBN:9780134319650Author:Russell C. HibbelerPublisher:PEARSONThermodynamics: An Engineering ApproachMechanical EngineeringISBN:9781259822674Author:Yunus A. Cengel Dr., Michael A. BolesPublisher:McGraw-Hill Education
- Control Systems EngineeringMechanical EngineeringISBN:9781118170519Author:Norman S. NisePublisher:WILEYMechanics of Materials (MindTap Course List)Mechanical EngineeringISBN:9781337093347Author:Barry J. Goodno, James M. GerePublisher:Cengage LearningEngineering Mechanics: StaticsMechanical EngineeringISBN:9781118807330Author:James L. Meriam, L. G. Kraige, J. N. BoltonPublisher:WILEY