Unit 1 550 MW Unit 4 Unit 5 Unit 2 Unit 3 Western Region 1640 MW Eastern Region 1450 MW Unit 1: 1000 MW Unit 4: 1200 MW Unit 2: 800 Mw Unit 5: 600 MW Unit 3: 800 MW
Short Transmission Line
A short transmission line is a transmission line that has a length less than 80 kilometers, an operating voltage level of less than 20 kV, and zero capacitance effect.
Power Flow Analysis
Power flow analysis is a topic in power engineering. It is the flow of electric power in a system. The power flow analysis is preliminary used for the various components of Alternating Current (AC) power, such as the voltage, current, real power, reactive power, and voltage angles under given load conditions and is often known as a load flow study or load flow analysis.
Complex Form
A power system is defined as the connection or network of the various components that convert the non-electrical energy into the electric form and supply the electric form of energy from the source to the load. The power system is an important parameter in power engineering and the electrical engineering profession. The powers in the power system are primarily categorized into two types- active power and reactive power.
Suppose a power system consists of two isolated regions: a western region and an eastern region. Five units have been committed to supply 3090 MW as shown below. The two systems are separated by a transmission line that can handle a maximum transfer of 550 MW in either direction.
Calculate the spinning reserve for the overall system and for each
region.
Step by step
Solved in 4 steps