The ABCD parameters of a 215-kV 400km 50 Hz three phase transmission line are:
A=0.877/1.57"
B 191.616/79.1
C=0.0012/90.4"
D=0.877/1.57⁰
The line supplies 150 MW load af unity power factor. Determine, (a) the sending end
power, (b) the voltage regulation, and (c) the efficiency of transmission.
Transcribed Image Text:• The ABCD parameters of a 215-kV 400km 50 Hz three phase transmission line are: A=0.877/1.57" B 191.616/79.1 C=0.0012/90.4" D=0.877/1.57⁰ The line supplies 150 MW load af unity power factor. Determine, (a) the sending end power, (b) the voltage regulation, and (c) the efficiency of transmission.
Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Types of Distribution in Power System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning