The ABCD constants of a 60 Hz, 3-phase long transmission lines are as follows B = 191.62/79.1⁰ C = 0.0012/90.4° A=D=0.877/1.57° This supplies 100 MW load at 230 kV with 90% power factor. What is the sending voltage ? A. 248 KV B. 245 KV C 269 KV D. 238 KV

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.14MCQ: The instantaneous power absorbed by the load in a single-phase ac circuit, for a general R LC load...
icon
Related questions
icon
Concept explainers
Question
The ABCD constants of a 60 Hz, 3-phase long transmission lines are as follows
B = 191.62/79.1⁰
C = 0.0012/90.4°
A=D=0.877/1.57°
This supplies 100 MW load at 230 kV with 90% power factor. What is the
sending voltage ?
A. 248 KV
B. 245 KV
C 269 KV
D. 238 KV
Transcribed Image Text:The ABCD constants of a 60 Hz, 3-phase long transmission lines are as follows B = 191.62/79.1⁰ C = 0.0012/90.4° A=D=0.877/1.57° This supplies 100 MW load at 230 kV with 90% power factor. What is the sending voltage ? A. 248 KV B. 245 KV C 269 KV D. 238 KV
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Transmission line parameter
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning