PROBLEM: • A 2,000-KVA transformer (A) is connected in parallel with a 4,000-KVA transformer (B) to supply a 3-phase load of 5,000 KVA at 0.8 p.f. lagging. Determine the KVA supplied by each transformer assuming equal no-load voltages. The percentage volt drops in the windings at the rated loads are as follows: Transformer A: resistance 2%; reactance 8% Transformer B: resistance 1.6%; reactance 3%
SUBJECT:
Electrical Apparatus
INSTRUCTIONS:
• Please write clearly and understable way.
• Write all the corresponding Given before solving.
• Draw/Illustrate the diagram/circuit or drawings that is related to the problem, HIGHLY REQUIRED.
• Solve in step-by-step, no shortcut, with formulas before sulutions together with the units
• Underline twice the Final Answer.
PROBLEM:
• A 2,000-KVA transformer (A) is connected in parallel with a 4,000-KVA transformer (B) to supply a 3-phase load of 5,000 KVA at 0.8 p.f. lagging. Determine the KVA supplied by each transformer assuming equal no-load voltages. The percentage volt drops in the windings at the rated loads are as follows:
Transformer A: resistance 2%; reactance 8%
Transformer B: resistance 1.6%; reactance 3%
Step by step
Solved in 4 steps with 4 images