Draw the reactance diagram with all  reactance  marked in p.u. Select the generator rating as the base in the generator circuit.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.9P
icon
Related questions
Question

A 50 MVA, 15 kV three phase generator has a subtransient reactance of 0.2 p.u. The generator supplies two motors over a transmission line having transformers at both ends as shown in Fig. The motors have rated inputs of 30 MVA and 20 MVA both 30 kV with 0.15 p.u. subtransient reactance. The rating of the sending end transformer, Tr1 is 50 MVA, 11 kV / 132 kV  with leakage reactance of 0.1 p.u. Transformer Tr2 at the receiving end has three single phase transformers  and the rating of each individual transformer is 20 MVA , 33 / 76 kV with leakage reactance of 0.12 p.u. Series reactance of the line is 25  ohms. Draw the reactance diagram with all  reactance  marked in p.u. Select the generator rating as the base in the generator circuit.

Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning