A stream of ammonia is cooled from 100oC to 20oC at a rate of 180 kg/hr in the tube side of a double-pipe counter-flow heat exchanger. Water enters the heat exchanger at 10oC at a rate of 250 kg/hr. The outside diameter of the inner tube is 3 cm and the length of the pipe is 7m. Using the log-mean temperature difference, calculate the overall heat transfer coefficient (U) for the heat exchanger. Determine the log-mean temperature difference. Determine the heat transfer coefficient for the heat exchanger. Cp for ammonia is 5234J/kgK and cp for water is 4180J/kgK.
Heat Exchangers
Heat exchangers are the types of equipment that are primarily employed to transfer the thermal energy from one fluid to another, provided that one of the fluids should be at a higher thermal energy content than the other fluid.
Heat Exchanger
The heat exchanger is a combination of two words ''Heat'' and ''Exchanger''. It is a mechanical device that is used to exchange heat energy between two fluids.
A stream of ammonia is cooled from 100oC to 20oC at a rate of 180 kg/hr in the tube side of a double-pipe counter-flow heat exchanger. Water enters the heat exchanger at 10oC at a rate of 250 kg/hr. The outside diameter of the inner tube is 3 cm and the length of the pipe is 7m. Using the log-mean temperature difference, calculate the overall heat transfer coefficient (U) for the heat exchanger.
-
- Determine the log-mean temperature difference.
- Determine the heat transfer coefficient for the heat exchanger.
Cp for ammonia is 5234J/kgK and cp for water is 4180J/kgK.
Step by step
Solved in 4 steps with 16 images