A single phase transformer with 50 kVA, 2400V/240V, 50 Hz; Idle operating voltage 2400V, idle current is 0.2A and idling power is 180W. Short circuit operating voltage It is 55V, the short-circuit current is 20.83A, and the short-circuit power is 620W. According to this; a) Calculate the equivalent winding resistance reduced to primary, equivalent winding reactance and equivalent winding impedance. b) Calculate the magnetization reactance and core loss resistance. c) Copper and iron (core) losses for operation at 0.95 (reverse) power factor at half load. Find and calculate the efficiency of the transformer.
A single phase transformer with 50 kVA, 2400V/240V, 50 Hz; Idle operating voltage 2400V, idle current is 0.2A and idling power is 180W. Short circuit operating voltage It is 55V, the short-circuit current is 20.83A, and the short-circuit power is 620W. According to this; a) Calculate the equivalent winding resistance reduced to primary, equivalent winding reactance and equivalent winding impedance. b) Calculate the magnetization reactance and core loss resistance. c) Copper and iron (core) losses for operation at 0.95 (reverse) power factor at half load. Find and calculate the efficiency of the transformer.
Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
Related questions
Question
100%
A single phase transformer with 50 kVA, 2400V/240V, 50 Hz; Idle operating voltage 2400V, idle current is 0.2A and idling power is 180W. Short circuit operating voltage It is 55V, the short-circuit current is 20.83A, and the short-circuit power is 620W. According to this;
a) Calculate the equivalent winding resistance reduced to primary, equivalent winding reactance and equivalent winding impedance.
b) Calculate the magnetization reactance and core loss resistance.
c) Copper and iron (core) losses for operation at 0.95 (reverse) power factor at half load. Find and calculate the efficiency of the transformer.
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
This is a popular solution!
Trending now
This is a popular solution!
Step by step
Solved in 4 steps with 4 images
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,