A room is maintained at 20°C by removing heat at a rate of 3 kW. The required power input to the air conditioning unit is 1.5 kW. Determine the COP. A For question 4 above, determine the rate of heat rejection to the outside air in kW.

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter35: Comfort And Psychrometrics
Section: Chapter Questions
Problem 12RQ: A gas furnace has an output of 60,000 Btu/h. The return air temperature is 72F, and the temperature...
icon
Related questions
Question
Part a b and c please
A room is maintained at 20°C by removing
heat at a rate of 3 kW. The required power
input to the air conditioning unit is 1.5 kW.
Determine the COP.
A
For question 4 above, determine the rate of
B
heat rejection to the outside air in kW.
Transcribed Image Text:A room is maintained at 20°C by removing heat at a rate of 3 kW. The required power input to the air conditioning unit is 1.5 kW. Determine the COP. A For question 4 above, determine the rate of B heat rejection to the outside air in kW.
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Free Body Diagram
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning