A generating station forq a power system consists of five 189-MVA 15-kV 0.85-PF-lagging synchronous generators with identical speed droop characteristics operating in parallel. The governors on the generators’ prime movers are adjusted to produce a 2.5-Hz drop from no load to full load. four of these generators are each supplying a steady 139 MW at a frequency of 60 Hz, while the fifth generator (called the swing generator) handles all incremental load changes on the system while maintaining the system's frequency at 60 Hz. 1)At a given instant, the total system loads are 500 MW at a frequency of 60 Hz. Compute the no-load frequencies of each of the system’s generators? 2)If the system load rises to 600 MW and the generator’s governor set points do not change, compute the new system frequency be? 3)To what frequency must the no-load frequency of the swing generator be adjusted in order to restore the system frequency to 60 Hz

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
A generating station forq a power system consists of five 189-MVA 15-kV 0.85-PF-lagging synchronous generators with identical speed droop characteristics operating in parallel. The governors on the generators’ prime movers are adjusted to produce a 2.5-Hz drop from no load to full load. four of these generators are each supplying a steady 139 MW at a frequency of 60 Hz, while the fifth generator (called the swing generator) handles all incremental load changes on the system while maintaining the system's frequency at 60 Hz. 1)At a given instant, the total system loads are 500 MW at a frequency of 60 Hz. Compute the no-load frequencies of each of the system’s generators? 2)If the system load rises to 600 MW and the generator’s governor set points do not change, compute the new system frequency be? 3)To what frequency must the no-load frequency of the swing generator be adjusted in order to restore the system frequency to 60 Hz? 4)If the system is operating at the conditions described in part (c), what would happen if the swing generator were tripped off the line (disconnected from the power line)?
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 8 steps

Blurred answer
Knowledge Booster
Stability Analysis in Power System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,