A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -30°C by rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.29 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 65°C and leaves at 42°C. The inlet state of the compressor is 60 kPa and -34°C and the compressor is estimated to gain a net heat of 430 W from the surroundings. The heat exchanger loses no heat to the environment.

Elements Of Electromagnetics
7th Edition
ISBN:9780190698614
Author:Sadiku, Matthew N. O.
Publisher:Sadiku, Matthew N. O.
ChapterMA: Math Assessment
Section: Chapter Questions
Problem 1.1MA
icon
Related questions
Question
!
Required information
NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part.
A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -30°C by
rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.29 kg/s and leaves at 26°C. The
refrigerant enters the condenser at 1.2 MPa and 65°C and leaves at 42°C. The inlet state of the compressor is 60 kPa and
-34°C and the compressor is estimated to gain a net heat of 430 W from the surroundings. The heat exchanger loses no
heat to the environment.
26°C ↑
42°C
Condenser
Expansion
valve
Evaporator
OL
Water
18°C
2
kW.
1.2 MPa
65°C
W;
in
Compressor
60 kPa
-34°C
Determine the refrigeration load. (Take the required values from saturated refrigerant-134a tables and steam tables.)
(You must provide an answer before moving on to the next part.)
The refrigeration load is
Transcribed Image Text:! Required information NOTE: This is a multi-part question. Once an answer is submitted, you will be unable to return to this part. A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -30°C by rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.29 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 65°C and leaves at 42°C. The inlet state of the compressor is 60 kPa and -34°C and the compressor is estimated to gain a net heat of 430 W from the surroundings. The heat exchanger loses no heat to the environment. 26°C ↑ 42°C Condenser Expansion valve Evaporator OL Water 18°C 2 kW. 1.2 MPa 65°C W; in Compressor 60 kPa -34°C Determine the refrigeration load. (Take the required values from saturated refrigerant-134a tables and steam tables.) (You must provide an answer before moving on to the next part.) The refrigeration load is
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Refrigeration and Air Conditioning
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Elements Of Electromagnetics
Elements Of Electromagnetics
Mechanical Engineering
ISBN:
9780190698614
Author:
Sadiku, Matthew N. O.
Publisher:
Oxford University Press
Mechanics of Materials (10th Edition)
Mechanics of Materials (10th Edition)
Mechanical Engineering
ISBN:
9780134319650
Author:
Russell C. Hibbeler
Publisher:
PEARSON
Thermodynamics: An Engineering Approach
Thermodynamics: An Engineering Approach
Mechanical Engineering
ISBN:
9781259822674
Author:
Yunus A. Cengel Dr., Michael A. Boles
Publisher:
McGraw-Hill Education
Control Systems Engineering
Control Systems Engineering
Mechanical Engineering
ISBN:
9781118170519
Author:
Norman S. Nise
Publisher:
WILEY
Mechanics of Materials (MindTap Course List)
Mechanics of Materials (MindTap Course List)
Mechanical Engineering
ISBN:
9781337093347
Author:
Barry J. Goodno, James M. Gere
Publisher:
Cengage Learning
Engineering Mechanics: Statics
Engineering Mechanics: Statics
Mechanical Engineering
ISBN:
9781118807330
Author:
James L. Meriam, L. G. Kraige, J. N. Bolton
Publisher:
WILEY