A built-up laced column of overall square cross-section, 300 mm size has been formed by placing four angles of ISA 50 x 50 x 6 mm at the corners of the square. If the effective height of column is 10 m, then calculate the load carrying capacity of the column. Also, check the lacing system for safety against: (i) Local buckling of column angles. (ii) Strength of lacing bars in tension and compression against shear load. (iii) Strength of M20 bolts of grade 4.6, check safety of bolt. Lacing system consist of 60 x 10 mm flat bars arranged in a single laced system and inclined to the axis of the column at an angle of 45° kL/r for (MPa) 164 153 135 125 111 98 86 40 50 60 70 80 90 100 145 50 For ISA 50 x 50 x 6 mm, area = 568 mm?, I, =I, = 12.9 x 104 mm4, 14.5 mm, Tmin = 15.1 mm.

Steel Design (Activate Learning with these NEW titles from Engineering!)
6th Edition
ISBN:9781337094740
Author:Segui, William T.
Publisher:Segui, William T.
Chapter9: Composite Construction
Section: Chapter Questions
Problem 9.1.3P
icon
Related questions
Question
1
Q.7 (a) A built-up laced column of overall square cross-section, 300 mm size has been formed
by placing four angles of ISA 50 x 50 x 6 mm at the corners of the square. If the effective
height of column is 10 m, then calculate the load carrying capacity of the column. Also,
check the lacing system for safety against:
(i) Local buckling of column angles.
(ii) Strength of lacing bars in tension and compression against shear load.
(iii) Strength of M20 bolts of grade 4.6, check safety of bolt.
Lacing system consist of 60 x 10 mm flat bars arranged in a single laced system and
inclined to the axis of the column at an angle of 45°
kL./r
fot (MPa) 164 153 135 125 111 98 86
40
50
60
70
80 90 100 145
50
For ISA 50 x 50 x 6 mm, area =
568 mm2, I,
12.9 x 104 mm,
Cy
14.5 mm,
%3D
rmin = 15.1 mm.
%3D
Transcribed Image Text:Q.7 (a) A built-up laced column of overall square cross-section, 300 mm size has been formed by placing four angles of ISA 50 x 50 x 6 mm at the corners of the square. If the effective height of column is 10 m, then calculate the load carrying capacity of the column. Also, check the lacing system for safety against: (i) Local buckling of column angles. (ii) Strength of lacing bars in tension and compression against shear load. (iii) Strength of M20 bolts of grade 4.6, check safety of bolt. Lacing system consist of 60 x 10 mm flat bars arranged in a single laced system and inclined to the axis of the column at an angle of 45° kL./r fot (MPa) 164 153 135 125 111 98 86 40 50 60 70 80 90 100 145 50 For ISA 50 x 50 x 6 mm, area = 568 mm2, I, 12.9 x 104 mm, Cy 14.5 mm, %3D rmin = 15.1 mm. %3D
Expert Solution
steps

Step by step

Solved in 3 steps with 2 images

Blurred answer
Knowledge Booster
Sectioning basics
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, civil-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Steel Design (Activate Learning with these NEW ti…
Steel Design (Activate Learning with these NEW ti…
Civil Engineering
ISBN:
9781337094740
Author:
Segui, William T.
Publisher:
Cengage Learning