A 25 MVA, 24.25 kV, 50 Hz, 4 poles, Y- connected synchronous generator has a synchronous reactance of 9 2 and armature resistance of 0.5 2. At 60 Hz, the total mechanical losses are 2 MW. The no-load saturation curve giving the relationship between output phase voltage, E. and excitation current I, is shown as in Fig. Q2. If the excitation is adjusted so that the terminal line voltage remains fixed at 24.25 kV, calculate the following: Open eire sit eharactecietie 20 18 16 14 12 10 Pield ouent (A) Fig. Q2 Exciting field current required at no-load. (i) Required exciting field current for 20 MW of connected load with 0.8 power factor lagging. (i) Efficiency of the generator at condition ii). (AN) on S-d

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
A 25 MVA, 24.25 KV, 50 Hz, 4 poles, Y- connected synchronous generator has a synchronous
reactance of 9 2 and amature resistance of 0.5 2. At 60 Hz, the total mechanical losses are 2
MW. The no-load saturation curve giving the relationship between output phase voltage, E.
and excitation curent I,is shown as in Fig. Q2. If the excitation is adjusted so that the terminal
line voltage remains fixed at 24.25 kV, calculate the following:
Open cie nit charactecistic
20
18
16
14
12
10
3
Field eurrent (A)
Fig. Q2
Exciting field current required at no-load.
(i) Required exciting field current for 20 MW of connected load with 0.8 power
factor lagging.
(1)
Efficiency of the generator at condition ii).
(iv) Input torque of generator
Transcribed Image Text:A 25 MVA, 24.25 KV, 50 Hz, 4 poles, Y- connected synchronous generator has a synchronous reactance of 9 2 and amature resistance of 0.5 2. At 60 Hz, the total mechanical losses are 2 MW. The no-load saturation curve giving the relationship between output phase voltage, E. and excitation curent I,is shown as in Fig. Q2. If the excitation is adjusted so that the terminal line voltage remains fixed at 24.25 kV, calculate the following: Open cie nit charactecistic 20 18 16 14 12 10 3 Field eurrent (A) Fig. Q2 Exciting field current required at no-load. (i) Required exciting field current for 20 MW of connected load with 0.8 power factor lagging. (1) Efficiency of the generator at condition ii). (iv) Input torque of generator
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 5 steps with 1 images

Blurred answer
Knowledge Booster
Synchronous Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,