8262.5 ▸ A balanced star connected load is connected to a 4 kVA, 415 V, star connected three phase generator via a three wire transmission line. The impedance of each line is 0.3 + j6.0 ohms. The synchronous impedance of the generator is 0.4 + j2.4 ohms. The fixed losses of the generator are 175 W. The field winding is connected to a 120 V source and the field current is 5.5 A. When the generator delivers rated load at rated voltage and at 0.866 power factor lagging, find ▸ The efficiency of the generator (79.8%) The voltage regulation at the load (11.2%) ▸ The efficiency of the entire system. (79.2%) Ts = 8262.5w (401) =65.74 N.m ▸ Draw the power flow diagram of the entire power system indicating on the diagram all the values of the power flows.
8262.5 ▸ A balanced star connected load is connected to a 4 kVA, 415 V, star connected three phase generator via a three wire transmission line. The impedance of each line is 0.3 + j6.0 ohms. The synchronous impedance of the generator is 0.4 + j2.4 ohms. The fixed losses of the generator are 175 W. The field winding is connected to a 120 V source and the field current is 5.5 A. When the generator delivers rated load at rated voltage and at 0.866 power factor lagging, find ▸ The efficiency of the generator (79.8%) The voltage regulation at the load (11.2%) ▸ The efficiency of the entire system. (79.2%) Ts = 8262.5w (401) =65.74 N.m ▸ Draw the power flow diagram of the entire power system indicating on the diagram all the values of the power flows.
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.23MCQ: Does an open- operation, the kVA rating compared to that of the original thr-phase bank is (a) 2/3...
Related questions
Question
100%

Transcribed Image Text:8262.5
▸ A balanced star connected load is connected to a 4 kVA,
415 V, star connected three phase generator via a three
wire transmission line. The impedance of each line is 0.3
+ j6.0 ohms. The synchronous impedance of the
generator is 0.4 + j2.4 ohms. The fixed losses of the
generator are 175 W. The field winding is connected to a
120 V source and the field current is 5.5 A. When the
generator delivers rated load at rated voltage and at 0.866
power factor lagging, find
▸ The efficiency of the generator (79.8%)
The voltage regulation at the load (11.2%)
▸ The efficiency of the entire system. (79.2%)
Ts = 8262.5w
(401)
=65.74 N.m
▸ Draw the power flow diagram of the entire power system
indicating on the diagram all the values of the power
flows.
Expert Solution

This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 2 steps with 3 images

Recommended textbooks for you

Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning

Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning