51- Two de generators; each having linear external characteristics operate in parallel. one machine has a terminal voltage of 270 V on no load and 220 V at a load current of 35 A, while the other machine has a terminal voltage of 280 V on no load and 220 V at a load current of 50 A. When the total load is 60 A, load voltage will be......V (D) 254 (A) 236 (B) 244 (C) 226 52- For previous problem, the 1" machine current will be.... (A) 60 A (B) 50 A 36 A (D) 24 A

icon
Related questions
Question
100%

Please no hand writing solution

51- Two de generators; each having linear external
characteristics operate in parallel. one machine has
a terminal voltage of 270 V on no load and 220 V at a load
current of 35 A, while the other machine has a terminal
voltage of 280 V on no load and 220 V at a load current of
50 A. When the total load is 60 A, load voltage will be ......V
(A) 236
(B) 244
(C) 226
(D) 254
52- For previous
(A) 60 A
problem, the 1" machine current will be....
36 A
(B) 50 A
(D) 24 A
Transcribed Image Text:51- Two de generators; each having linear external characteristics operate in parallel. one machine has a terminal voltage of 270 V on no load and 220 V at a load current of 35 A, while the other machine has a terminal voltage of 280 V on no load and 220 V at a load current of 50 A. When the total load is 60 A, load voltage will be ......V (A) 236 (B) 244 (C) 226 (D) 254 52- For previous (A) 60 A problem, the 1" machine current will be.... 36 A (B) 50 A (D) 24 A