5. A substation takes 1,200 kW, 3-phase power, @ 66kV, and this power is stepped down to 4,800V by two V-connected transformers. The load power factor is 0.866 lagging. Determine (a) minimum rating of each transformer; (b) current and voltage rating of each winding; (c) power factor at which each winding operates. Neglect losses. A third transformer of the same rating as these two is added. Determine (d) rating in kilowatts of substation at power factor of 0.866 lagging: (e) percentage increase, in kilowatt rating and percentage increase in transformer investment. . Answer: (a) kVArach 799.54kVA; (b) In 1.0 (Unity). P.F.2 0.50 lagging; (d) kW Investment 50% 12.12A, Is-166.67A, Vp 66,000V, Vs 4,800V: (c) P.F.:- 2,077.20kW; (e) %increase in kWR 73.10 %, %increase in

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
5.
A substation takes 1,200 kW, 3-phase power, @ 66kV, and this power is stepped down to 4,800V by
two V-connected transformers. The load power factor is 0.866 lagging. Determine (a) minimum
rating of each transformer; (b) current and voltage rating of each winding; (c) power factor at which
each winding operates. Neglect losses. A third transformer of the same rating as these two is added.
Determine (d) rating in kilowatts of substation at power factor of 0.866 lagging: (e) percentage
increase, in kilowatt rating and percentage increase in transformer investment.
Answer: (a) kVAeach 799.54kVA; (b) Ir
1.0 (Unity). P.F.2 0.50 lagging; (d) kW
Investment - 50%
12.12A, Is 166.67A, Vp 66,000V, Vs 4,800V: (c) P.F.:-
2,077.20kW; (e) %increase in kWR 73.10%, % increase in
Transcribed Image Text:5. A substation takes 1,200 kW, 3-phase power, @ 66kV, and this power is stepped down to 4,800V by two V-connected transformers. The load power factor is 0.866 lagging. Determine (a) minimum rating of each transformer; (b) current and voltage rating of each winding; (c) power factor at which each winding operates. Neglect losses. A third transformer of the same rating as these two is added. Determine (d) rating in kilowatts of substation at power factor of 0.866 lagging: (e) percentage increase, in kilowatt rating and percentage increase in transformer investment. Answer: (a) kVAeach 799.54kVA; (b) Ir 1.0 (Unity). P.F.2 0.50 lagging; (d) kW Investment - 50% 12.12A, Is 166.67A, Vp 66,000V, Vs 4,800V: (c) P.F.:- 2,077.20kW; (e) %increase in kWR 73.10%, % increase in
Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,