300 KVA, 2000/200 V, single-phase, 50 Hz transformer has a primary resistance of 3.5 Q. The secondary resistance is 0.015 02. Find equivalent resistance referred to the primary side.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.28MCQ
icon
Related questions
Question
300 KVA, 2000/200 V, single-phase, 50 Hz transformer has a primary resistance of 3.50. The secondary resistance is 0.015 02.
Find equivalent resistance referred to the primary side.
Transcribed Image Text:300 KVA, 2000/200 V, single-phase, 50 Hz transformer has a primary resistance of 3.50. The secondary resistance is 0.015 02. Find equivalent resistance referred to the primary side.
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning