17. A manufacturing plant has a load of 3,600 kva at a lagging power factor of 0.707. A 500-hp synchronous motor having an efficiency of 90 per cent is installed and is used also to improve the over-all power factor to 0.937 lagging. Calculate the kilovolt-ampere input rating of the synchronous motor and the power factor at which it must operate.
17. A manufacturing plant has a load of 3,600 kva at a lagging power factor of 0.707. A 500-hp synchronous motor having an efficiency of 90 per cent is installed and is used also to improve the over-all power factor to 0.937 lagging. Calculate the kilovolt-ampere input rating of the synchronous motor and the power factor at which it must operate.
Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
Related questions
Question
DEGREE: ELECTRICAL ENGINEERING
SUBJECT/COURSE: AC MACHINES
NOTE: Please solve in this way.
1. Please have a good handwriting, some of the answers are not readable. Thank you!
2. GIVEN.(include symbols and units)
3. REQUIRED/FIND/MISSING (with symbol/s)
4. ILLUSTRATION (Required).
5. STEP-by-STEP SOLUTION with Formulas and Symbols. No Shortcut, No skipping, and detailed as possible
6. Underline twice the FINAL ANSWER.

Transcribed Image Text:17. A manufacturing plant has a load of 3,600 kva at a lagging power factor of 0.707.
A 500-hp synchronous motor having an efficiency of 90 per cent is installed and
is used also to improve the over-all power factor to 0.937 lagging. Calculate the
kilovolt-ampere input rating of the synchronous motor and the power factor at
which it must operate.
Expert Solution

This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
This is a popular solution!
Trending now
This is a popular solution!
Step by step
Solved in 2 steps with 2 images

Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you

Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON

Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning

Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education

Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON

Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning

Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education

Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education

Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON

Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,